5 / 6
Siemens Flow switch QVE1902.0.. CM1N1596en
Building Technologies 2017-02-16
Disposal
The device is considered an electronics device for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic garbage.
xDispose of the device through channels provided for this purpose.
xComply with all local and currently applicable laws and regulations.
Technical data
Field of use
Permissible media
Medium temperature
Piping diameter
Nominal pressure
All liquids
(not suitable for ammonia)
-20…100 °C (Medium may not freeze)
DN 10…25
PN 10
(piping approved for PN 25)
Contact
Type of switch
Max. contact rating
Max. switching capacity
Length of connecting cable/cross section
External supply line protection (EU)
Closes as flow increases
Opens as flow decreases *)
Reed contact
AC 230 V, 1 A / DC 48 V, 1 A
26 VA or 20 W
1.5 m / 0.5 mm2
Fuse slow max. 10 A
or
Circuit breaker max. 13 A
Characteristic B, C, D according to
or
Power source with current limitation of
max. 10 A
Switching point adjustment
Setting range
Manual, set at the factory to
the setting range
See Sizing on page 2
Protection class
Housing
II according to EN 60730-1
IP65 according to EN 60529
Storage, transportation, operation
Temperature
Humidity
0…70 °C
<95 % r.h.
Product standard EN 60204-1
Safety of machinery - Electrical
equipment of machines
EU Conformity (CE) CM1T1596xx
The product environmental declaration CE1E1596
contains data on
environmentally compatible product design and assessments (RoHS compliance,
materials composition, packaging, environmental benefit, disposal).
Excl. packaging See under "Dimensions and weight"
Switching unit/connecting cable
Housing and paddle system/piping
Polyamide / PVC
PPE+PS Noryl FE1630PW / brass
Black
*) Applies to delivery state (switching function can be inverted as needed).
**) The documents can be downloaded from http://siemens.com/bt/download.
Functional data
general
Switching function
Degree of protection
Environmental conditions
Standards and Directives
Environmental
compatibility
Dimensions / Weight
Material
Housing color
Hindustan Hydraulics & Pneumatics, Chennai - 01.
Phone : 2534 3066, 2534 5625, 2534 5587
E-Mail : hhp@hindustanhydraulic.in
Contact person : V. Anandha krishnan - 98409 21885