Simplex TrueAlert 4906-9207 User manual

Features
Individually addressed and controlled
multi-candela V/O (visible only) notification
appliances provide:
Amber lens with “ALERT” lettering produces a signal
unique from clear lens fire alarm evacuation strobes for
use with Emergency Communications Systems
Multi-candela xenon strobe with synchronized 1 Hz
flash rate and with intensity programmable from the
control panel or jumper selected as 15, 30, 75, or
110 cd
Advanced addressable notification controlled by IDNAC
SLCs from Simplex®4100ES fire alarm control panels
with EPS/EPS+ power supplies (and 4009 IDNAC
Repeaters) providing regulated 29 VRMS allowing
strobes to operate with lower current even under battery
backup
Separate device type allows connection on same SLC as
clear lens strobes with independent operation; clear
strobes for Fire Alarm, amber strobes for Alert
(Operation is clear/Fire OR amber/Alert, not both)
Wiring supervision to each strobe allowing “T-tapped”
connections for Class B circuits to simplify wiring
(Class A circuits require in/out wiring)
TrueAlert Device Reports at the control panel detailing
appliance point ID, custom label, type, and candela
setting (see sample on page 3)
Magnet test diagnostics to assist checkout and testing of
appliances and wiring
Compatibility with ADA requirements; (refer to
important installation information on page 3)
Compatibility with legacy TrueAlert addressable
systems for upgrade and replacement (see page 4)
UL listed to Standard 1638 (due to non-white lens);
verified by UL testing to provide light dispersion
patterns of UL Standard 1971 at rated candela (no
derating necessary for amber lens)
ULC listed to Standard S526
LED indicator and magnet test feature:
Appliance LED can be selected to display each polling
cycle to indicate appliance supervision
In diagnostic mode, the magnet test pulses the LED to
indicate appliance address AND pulses to indicate the
intensity selection; a brief output of the strobe is also
selectable to confirm operation
Mechanical design features:
Rugged, high impact, flame retardant thermoplastic
white housing
Rear of housing does not extend into box and easily
mounts to standard electrical boxes
Options include box adapters and red wire guards
Ceiling Mount Addressable Amber Lens V/Os
Description
Multi-Candela TrueAlert addressable amber lens
strobes provide convenient installation to standard
electrical boxes. The strobe is individually addressed and
individually controlled with power, supervision, and
control supplied from a Simplex fire alarm control panel
providing IDNAC Signaling Line Circuits (SLCs). (See
compatibility list on page 4.)
These amber lens multi-candela strobes provide non-fire
alarm alert notification for use with Emergency
Communications systems where additional response
information is provided by audio or textual appliances.
Strobe Application Reference
Amber strobes used as part of an Emergency
Communications system are located to provide the same
area coverage as required of clear lens fire alarm strobes.
Specific Emergency Communications requirements are
discussed in detail in document UFC 4-021-01 (USA
Department of Defense, United Facilities Criteria) and in
NFPA 72, Chapter 24 (2010 and 2013 editions).
Proper strobe coverage criteria is further described in the
National Fire Alarm Code (NFPA 72), ANSI A117.1; the
appropriate model building code: BOCA, ICBO, or SBCCI;
and the application guidelines of the Americans with
Disabilities Act (ADA).
*See page 2 for wire guard listings. This product has been approved by the California State
Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety
Code. See CSFM Listing 7300-0026:325 for allowable values and/or conditions
concerning material presented in this document. FM approval and MEA acceptance are
not applicable. Additional listings may be applicable; contact your local Simplex product
supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are
the property of Tyco Fire Protection Products.
TrueAlert Addressable Notification Appliances
UL, ULC, CSFM Listed* Multi-Candela Visible Only (V/O) Amber Lens Ceiling
Mount Strobes for Emergency Communications
S4906-0007-7 8/2014
IDNAC SLC Operation Advantage
TrueAlert V/O Appliances with Addressable
Amber Strobes on IDNAC SLCs provide visible
notification using a single two-wire circuit that also
confirms connection to the individual notification
appliance’s electronic circuit. This operation increases
circuit supervision integrity by providing supervision that
extends beyond the appliance wiring connections.
Reduced current allows efficient IDNAC SLC
operation. With IDNAC SLCs, a constant 29 VRMS
source voltage is maintained, even during battery standby,
allowing strobes to operate at higher voltage with lower
current and ensuring a consistent current draw and voltage
drop margin under both primary power and secondary
battery standby. Efficiencies include wiring distances up
to 2 to 3 times farther than with conventional notification,
or support for more appliances per IDNAC SLC, or use of
smaller gauge wiring, or combinations of these benefits,
all providing installation and maintenance savings with
high assurance that appliances that operate during normal
system testing will operate during worst case alarm
conditions.
Reducing Installation and Testing Time.With
separate controls on the same two-wire SLC, installation
time and expense for both retrofit and new construction
can be significantly reduced. When Class B wiring is
used, wiring can be “T” tapped, allowing more savings in
distance, wire, conduit (size and utilization), and overall
installation efficiency. Use of the magnet test feature
improves installation efficiency. TrueAlert device reports
conveniently identify information about each connected
appliance.
TrueAlert Addressable Diagnostics
Test Features. Controllers can be selected to pulse each
appliance’s LED when it receives a supervision poll. When
the controller is selected for diagnostic mode, the appliance
magnet test feature provides a response at the individual
appliance being tested.
Silent Appliance Magnet Test. In this test mode, in
response to the magnet test, the appliance LED pulses
sequentially to conveniently indicate the appliance’s
address.
Operational Appliance Testing. In this test mode, after
the address is indicated by pulsing the appliance LED, the
strobe will briefly flash to indicate proper operation.
TrueStart Instrument Two (TSIT). The 2nd generation
of the Simplex TrueStart Test Instrument adds testing of
IDNAC SLC wiring and TrueAlert (and TrueAlert ES)
appliances to its ability to test IDCs, NACs, and IDNet
communications before connection to the control panel.
Please contact your local Simplex representative for
additional information.
TrueAlert Addressable Wiring Isolator
Isolator Model 4905-9929 is available for remote
mounting on TrueAlert addressable circuits to isolate
short circuited wiring from functioning wiring. (Refer to
data sheet S4905-0001 for additional information.)
Multi-Candela Addressable Strobe with Amber Lens
Model Description Dimensions
4906-9207
Multi-Candela Addressable Ceiling Mount Strobe, white with red “ALERT”
lettering with amber lens; intensity selectable as: 15, 30, 75, or 110
candela
4 ¾” x 2 5⁄16” x 2 ⅝” D
(121 mm x 75 mm x 67 mm)
V/O Adapter and Wire Guard
Model Description Dimensions
4905-9910 Surface Mount Adapter Plate, zinc plated; required for ceiling surface
mount boxes 4 ⅞” x 3 ⅛” (124 mm x 79 mm)
4905-9926* Ceiling Mount red wire guard with mounting plate, compatible with
semi-flush or surface mounted boxes (see diagram on page 3)
6 ⅛” x 4 ⅜” x 2 ⅞”
(156 mm x 111 mm x 73 mm)
* UL listed by Space Age Electronics Inc.
2 S4906-0007-7 8/2014
Service Port
P
age 1
REPORT 5 : TrueAlert Device Report
1
2:34:56am MON
1
1
-
A
ug
-
1
4
POINT ID
CUSTOM LABEL DEVICE
T
YPE
CANDELA
T14-1-1 Location Label . . . up to 40 characters
V
/O 15
T14-1-2 Break Room 5
A
/V 110
T14-1-3 Boiler Room Fire
A
/V 75
T14-1-4 Boiler Room Alert
A
MB 75
Product Selection
TrueAlert Device Reports Reference
3 S4906-0007-7 8/2014
Compatible Controller Data Sheet
Reference Controller
Output IDNAC SLC
Output Voltage Appliance Voltage
Design Reference
4100ES with EPS+ or EPS Power Supply S4100-0100 IDNAC SLC 29 VRMS
(regulated)
23 VRMS
(with 6 VRMS drop)
4009 IDNAC Repeater S4009-0004
Common Specifications (see page 2 for appliance dimensions)
Environmental 32° to 122° F (0° to 50° C); 10% to 93%, non-condensing at 100° F (38° C)
Connections Terminal blocks for 18 AWG to 12 AWG (0.82 mm2to 3.31 mm2); two wires per terminal for in/out wiring
Installation Instructions 579-828
Strobe Specifications
Typical Operating Voltage Range 23 VRMS to 31 VRMS, Special Application (see below for 17 VRMS rating)
Flash Rate and Synchronized SLC Loading 1 Hz; with up to 46 synchronized strobes maximum per NAC; maximum 30 Ω
resistance between appliances
23 VRMS Current Ratings,
for connection to IDNAC
Addressable SLCs
Candela Setting 15 cd 30 cd 75 cd 110 cd
60 mA 92 mA 180 mA 240 mA
Compatible Controller Data Sheet
Reference Controller
Output Available Strobe
Intensity Appliance
Voltage Minimum
4100ES or 4100U with TrueAlert Power Supply S4100-0031 TrueAlert
Addressable SLC
15, 30, 75, and
110 cd 17 VRMS4009 TPS, Remote TrueAlert Power Supply S4100-0037
TrueAlert Addressable Controller (4009T) S4009-0003
Electrical Ratings Difference for Retrofit Applications
Voltage Range 17 VRMS to 31 VRMS, Special Application
17 VRMS Current Ratings,
use when connected to
TrueAlert Addressable SLCs
per above
Candela Setting 15 cd 30 cd 75 cd 110 cd
76 mA 128 mA 242 mA 328 mA
15
110
75
30
FACP
Strobe intensity viewing slot
Intensity selection plug,
accessible only from rear of lens
housing; factory setting is FACP,
controlled by panel
4905-9910 Adapter Plate, required for surface
mount with handy box unless using the 4905-9926
wire guard
Handy box, 1-1/2" ( 38 mm) deep (RACO 650 or
equal) or single gang box, 2-1/2" (64 mm) deep
(RACO 519 or equal) supplied by others
Also can be attached to boxes mounted to drop
ceiling T-bar with clips (ERICO No. 512 or equal)
Ceiling mount strobe
Optional 4905-9926 wire
guard with mounting plate
Magnetic
test location
Bottom view
LED indicator
Address setting DIPswitch is behind strobe
assembly, select address and strobe
candela setting before inserting into housing
Single gang box (Wiremold V5744S)
2-1/4" (57 mm) deep, supplied by others
TrueAlert Amber Strobe and IDNAC SLC Controller Compatibility Reference
Specifications
TrueAlert Strobe LEGACY Compatibility Reference
Ceiling Mount V/O and Guard Installation Reference
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4906-0007-7 8/2014
www.simplex-fire.com
© 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code
are trademarks of the National Fire Protection Association (NFPA).

This manual suits for next models

2

Other Simplex Security System manuals

Simplex MINIPLEX 4100ES Series User manual

Simplex

Simplex MINIPLEX 4100ES Series User manual

Simplex TrueAlert 4906-9208 User manual

Simplex

Simplex TrueAlert 4906-9208 User manual

Simplex TrueAlert 4901 Service manual

Simplex

Simplex TrueAlert 4901 Service manual

Simplex SafeLINC 4100 User manual

Simplex

Simplex SafeLINC 4100 User manual

Simplex TrueAlert ES Service manual

Simplex

Simplex TrueAlert ES Service manual

Simplex SafeLINC 4100U Manual

Simplex

Simplex SafeLINC 4100U Manual

Simplex LifeAlarm 4005 Series User manual

Simplex

Simplex LifeAlarm 4005 Series User manual

Simplex TrueAlert 4906-9228 User manual

Simplex

Simplex TrueAlert 4906-9228 User manual

Simplex 4010ES User manual

Simplex

Simplex 4010ES User manual

Simplex MINIPLEX 4100ES Series User manual

Simplex

Simplex MINIPLEX 4100ES Series User manual

Simplex 4010ES User manual

Simplex

Simplex 4010ES User manual

Simplex 4099-5211 User manual

Simplex

Simplex 4099-5211 User manual

Simplex TrueAlert 4906-9202 User manual

Simplex

Simplex TrueAlert 4906-9202 User manual

Simplex TrueAlert Isolator+ User manual

Simplex

Simplex TrueAlert Isolator+ User manual

Popular Security System manuals by other brands

Intelligent Home DT-610 user manual

Intelligent Home

Intelligent Home DT-610 user manual

teko Astra-321 operating manual

teko

teko Astra-321 operating manual

Anviz M5 user manual

Anviz

Anviz M5 user manual

Satel ROP-101/EU manual

Satel

Satel ROP-101/EU manual

Absolute Process Instruments APD 1431 quick start guide

Absolute Process Instruments

Absolute Process Instruments APD 1431 quick start guide

Datatool S4 user guide

Datatool

Datatool S4 user guide

Unisto e-Guard manual

Unisto

Unisto e-Guard manual

Teletek electronics SensoMAG MHB50 installation instructions

Teletek electronics

Teletek electronics SensoMAG MHB50 installation instructions

Sensocon Siren Air Flow Alarm installation manual

Sensocon

Sensocon Siren Air Flow Alarm installation manual

Se-Kure Controls Klothing Kontrols SK-3600 Series installation instructions

Se-Kure Controls

Se-Kure Controls Klothing Kontrols SK-3600 Series installation instructions

Renkforce AC-239 operating instructions

Renkforce

Renkforce AC-239 operating instructions

FBII XL-5 user guide

FBII

FBII XL-5 user guide

Voyager AOS-33 Operation manual

Voyager

Voyager AOS-33 Operation manual

2gig Technologies Go Control 2GIG-CNTRL2 Operation & User’s Guide

2gig Technologies

2gig Technologies Go Control 2GIG-CNTRL2 Operation & User’s Guide

APLIC 301813 user manual

APLIC

APLIC 301813 user manual

X-10 POWERHOUSE PS561 owner's manual

X-10

X-10 POWERHOUSE PS561 owner's manual

Cooper Wheelock SQA-DC specification

Cooper Wheelock

Cooper Wheelock SQA-DC specification

Honeywell FBII OMNI 600 user guide

Honeywell

Honeywell FBII OMNI 600 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.