SMC Networks VV100 Series User manual

Other manuals for VV100 Series

1

Other SMC Networks Control Unit manuals

SMC Networks JSXF Series User manual

SMC Networks

SMC Networks JSXF Series User manual

SMC Networks VQC2000 Manual

SMC Networks

SMC Networks VQC2000 Manual

SMC Networks AKP Series User manual

SMC Networks

SMC Networks AKP Series User manual

SMC Networks CP96 Series User manual

SMC Networks

SMC Networks CP96 Series User manual

SMC Networks VF1000 Series Manual

SMC Networks

SMC Networks VF1000 Series Manual

SMC Networks ASR Series User manual

SMC Networks

SMC Networks ASR Series User manual

SMC Networks 56-VQC1000 Series Manual

SMC Networks

SMC Networks 56-VQC1000 Series Manual

SMC Networks EX250-SAS7 User manual

SMC Networks

SMC Networks EX250-SAS7 User manual

SMC Networks 4501 Series User manual

SMC Networks

SMC Networks 4501 Series User manual

SMC Networks VHS20 Series User manual

SMC Networks

SMC Networks VHS20 Series User manual

SMC Networks VQ1000 Series User manual

SMC Networks

SMC Networks VQ1000 Series User manual

SMC Networks VO317 Series User manual

SMC Networks

SMC Networks VO317 Series User manual

SMC Networks VP500 Series User manual

SMC Networks

SMC Networks VP500 Series User manual

SMC Networks VJ100 Manual

SMC Networks

SMC Networks VJ100 Manual

SMC Networks EX260 Series User manual

SMC Networks

SMC Networks EX260 Series User manual

SMC Networks XLS Series User manual

SMC Networks

SMC Networks XLS Series User manual

SMC Networks DXT1215 User manual

SMC Networks

SMC Networks DXT1215 User manual

SMC Networks LLB4 User manual

SMC Networks

SMC Networks LLB4 User manual

SMC Networks VQC4000 User manual

SMC Networks

SMC Networks VQC4000 User manual

SMC Networks AVA2000 Series User manual

SMC Networks

SMC Networks AVA2000 Series User manual

SMC Networks SYA5000 Series User manual

SMC Networks

SMC Networks SYA5000 Series User manual

SMC Networks VM200-A Series User manual

SMC Networks

SMC Networks VM200-A Series User manual

SMC Networks SZ3000 Series User manual

SMC Networks

SMC Networks SZ3000 Series User manual

SMC Networks XGTP31 50336 Series User manual

SMC Networks

SMC Networks XGTP31 50336 Series User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

3 Port Solenoid Valve
• Connector entry direction
Upward Lateral
Standard
(Same direction as the cylinder
ports)
Side
Plug-in
Connector type manifold Non Plug-in
Individual wiring manifold
2
direct-operated 3-port valves on
1
station
Individually wired valve can be added.
Connector
(For plug-in connection)
SUP/EXH block fittings
ø2 One-touch fitting connection is possible.
• Fitting entry direction
D-sub connector
Number of connectors: 15 pins, 26 pins (for plug-in connection)
Highly Integrated Unit Manifold
CAT.ES11-98A
Series VV100
Compact manifold with
two 3-port valves on 1 station
Bracket mounting example
Straight fitting Elbow fitting
(Upward entry)
Elbow fitting
(Downward entry)
50.3
40L
(5.9)
Stations
L
1
34.2
2
44.4
3
54.6
4
64.8
5
75
6
85.2
7
95.4
8
105.6
9
115.8
10
126
11
136.2
12
146.4
L: Dimensions
Mounting
Piping Variations
• Metric size: ø2, ø4 one-touch fitting
• Inch size: ø1/8", ø5/32" one-touch fitting
Applications
Operating a small bore
size cylinder such as a
pin cylinder
Air-operated valve for
chemical valve
Possible to shut the signal of each valves
individually.
With Switch
• The valve coil is not
energized even if an
electric signal is fed by
the manifold's connec-
tor.
• Effective use as a safe-
ty measure for mainte-
nance.
Switch
ON
OFF
Scale:
100
%
Scale:
100
%
Direct mounting Bracket mounting
4 x M3 x 0.5
Features 1
INDEX
Common Specifications
Construction
P.2
P.3
Connector Type Manifold
How to Order
Manifold Electrical Wiring
Connector Wiring Diagram
Dimensions
P.4, 5
P.6
P.6
P.7 to 11
Individual Wiring Manifold
How to Order
Dimensions
P.12, 13
P.14, 15
Manifold Exploded View
Manifold Options
Safety Instructions
Specific Product Precautions
P.16
P.17 to 19
Back page 1, 2
Back page 3 to 7
Plug-in
Non Plug-in
1
Manifold Specifications
Response Time
Solenoid Valve Specifications
Fluid Air
0 to 0.7
1 port: –100 kPa to 0.6/3 ports: –100 kPa to 0
1 port: –100 kPa to 0/3 ports: –100 kPa to 0.6
–10 to 50 (No freezing)
20
Not required
Unrestricted
150/30
Dustproof
24 VDC, 12 VDC
±10% of rated voltage Note 2)
0.4
0.15
Diode
LED
Operating pressure
range (MPa)
Ambient and fluid temperature (°C)
Maximum operating frequency (Hz)
Lubrication
Mounting orientation
Shock/Vibration resistance (m/s2) Note 1)
Enclosure
Coil rated voltage
Allowable voltage fluctuation
Surge voltage suppressor
Indicator light
Power
consumption
(W)
Positive pressure
N.C.
N.O.
Vacuum
pressure
Standard
With power saving circuit
(Continuous duty type)
Note 1) Impact resistance: No malfunction occurred when it is tested with a drop tester in the axial direction and
at the right angles to the main valve and armature in both energized and de-energ-
ized states every once for each condition. (Value in the initial state)
Vibration resistance: No malfunction occurred in one sweep test between 45 and 2000Hz. Test was per-
formed in the axial direction and at the right angles to the main valve and armature in
both energized and de-energized states for each condition. (Value in the initial state)
Note 2) For the allowable voltage fluctuation for Z and T types (with power saving circuit), observe the following
range because there is voltage drop due to internal circuit.
Response time ms (at 0.5 MPa)
7 or less
Mass
Valve model
V110-C2/C4
Number of solenoids
1 pc. (Single)
2 pcs. (Double)
Port size
C2, C4
(ø2, ø4 one-touch fitting)
Mass (g)
31
40
Flow Characteristics
Port size
1(P)
C6
2a, 2b 1(P)→2a/2b
C [dm3/(s·bar)] C [dm3/(s·bar)]
2a/2b→3(E)
C2
C4
0.03
0.03
0.22
0.19
0.05
0.05
0.31
0.29
bb
Flow characteristics
Model D-sub connector
Type 10FA
Connector type
1 to 12 stations
Individual wiring
Non-polar, +COM +COM
Common SUP, EXH
Valve
Side, Upward, Downward (Using elbow fittings for upward or downward)
C4, C6, N3, N7
C2, C4, N1, N3
W = 56 + n
Type 10FB Type 10
Non plug-in
Manifold type
1 (SUP), 3 (EXH)
Applicable connector
Internal wiring
Mass W (g) n: Valve stations
Location
Direction
1 (SUP), 3 (EXH) port
2a, 2b port
∗The mass W is the value for the manifold only. (It is applied when the SUP/EXH block fitting is straight type.)
The mass of solenoid valve should be added by the number of stations.
∗The effective area S (mm2) is approximately 5 times as large as the sonic conductance (S ≈C x 5).
1 to 12 stations
1 to 12 stations
Valve stations
D-sub connector 15 pins D-sub connector 26 pins
Refer to page 19.
2a, 2b port piping
specification
Port size
Z type 24 VDC: –7% to +10%
12 VDC: –4% to +10%
T type 24 VDC: –5% to +10%
12 VDC: –6% to +10%
Max. 7 stations
if all valves
have double
solenoid.
2
Series VV100
SOL.b
SOL.a
13
2a 2b t
o
r wueyqi!0 !1
!2 !3
2a
31
JIS symbol
(N.C.)
(N.O.)
(N.C.)
(N.O.)
2b2a
31
SOL.a SOL.b
13
2a
!2
!1!0
t
rwuey iq
!3o
t
o
r wueyqi!0 !1
!2 !3
2a
2b
2a
Construction
JIS symbol
1
2
3
4
5
6
7
8
9
10
11
12
DescriptionNo. Material
Component Parts
Body
Cover
Push rod
Armature assembly
Core
Poppet
Return spring
Poppet spring
Coil assembly
Pilot adapter
Port block
Clip
Resin
Stainless steel
Resin
Stainless steel/Resin
Stainless steel
FKM
Stainless steel
Stainless steel
—
Resin
Resin
Stainless steel
13
Port Port size Part no.No.
Replacement Parts
One-touch Fitting (Metric Size)
2a, 2b
ø2 one-touch fitting (Straight)
ø4 one-touch fitting (Straight)
ø2 one-touch fitting (Elbow)
ø4 one-touch fitting (Elbow)
ø2 one-touch fitting (Long elbow)
ø4 one-touch fitting (Long elbow)
ø4 one-touch fitting (Straight)
ø6 one-touch fitting (Straight)
ø4 one-touch fitting (Elbow)
ø6 one-touch fitting (Elbow)
ø4 one-touch fitting (Long elbow)
ø6 one-touch fitting (Long elbow)
KJH02-C1
KJH04-C1
KJL02-C1
KJL04-C1-N
KJW02-C1
KJW04-C1-N
VVQ1000-50A-C4
VVQ1000-50A-C6
SZ3000-73-1A-L4
SZ3000-73-1A-L6
SZ3000-73-2A-L4
SZ3000-73-2A-L6
1(P), 3(E)
13
No.
One-touch Fitting (Inch Size)
2a, 2b
1(P), 3(E)
ø1/8" one-touch fitting (Straight)
ø5/32" one-touch fitting (Straight)
ø5/32" one-touch fitting (Straight)
ø1/4" one-touch fitting (Straight)
KJH01-C1
KJH03-C1
VVQ1000-50A-N3
VVQ1000-50A-N7
Single
Double
Port Port size Part no.
3
3 Port Solenoid Valve
Series VV100
• The valve arrangement is numbered as the 1st station from D side.
• Indicate the valves to be attached below the manifold part number, in order
starting from station 1 as shown in the drawing.
The asterisk denotes the symbol for assembly.
Prefix to the part no. of the solenoid valve, etc.
VV100-10FAD2-05U1-C6 1 set (Manifold part no.)
∗ V110-D5CU-C4 3 sets (Double solenoid part no.)
∗ V110-D5CZJ-C4
1 set (Double solenoid, with switch part no.)
∗ V110-D5MZ-C4
1 set (Double solenoid, individual wiring/
lead wire length 300 mm part no.)
Ordering example (VV100-10FA)
····
·················
················
·················
Series VV100
/D-sub Connector
3 Port Solenoid Valve
Plug-in Connector Type Manifold
How to Order Manifold
D-sub connector type
Number of poles
15
26
Symbol
A
B
Connector block
mounting position: D side
SUP/EXH block
mounting position: U side
Valve stations
A: D-sub connector 15 pins
Note
Up to 14
solenoids
possible.
1 station
12 stations
Symbol Stations
01
12
B: D-sub connector 26 pins
Note
Up to 24
solenoids
possible.
1 station
12 stations
Symbol Stations
01
12
∗
If the mounted valve is N.O., apply pressure to the 3(E) port and exhaust air from the 1(P) port.
SUP/EXH block port size
ø4 one-touch fitting (Straight)
ø6 one-touch fitting (Straight)
ø4 elbow fitting (Upward entry)
ø6 elbow fitting (Upward entry)
ø4 elbow fitting (Downward entry)
ø6 elbow fitting (Downward entry)
C4
C6
L4
L6
B4
B6
One-touch fitting (Metric size)
ø5/32" one-touch fitting (Straight)
ø1/4" one-touch fitting (Straight)
N3
N7
One-touch fitting (Inch size)
SUP/EXH block fitting entry direction
1 2
Standard
(Same direction as
the cylinder
ports)
Side
Mounting option
U 1
VV100 10F C605DA 2
How to Order Valve Manifold Assembly
D side
U side
1
32
Stations
V110-D5MZ-C4 (1 set)
Double solenoid, individual wiring/lead wire length 300 mm (24 VDC)
V110-D5CZJ-C4 (1 set)
Double solenoid (24 VDC)
V110-D5CU-C4 (3 sets)
Double solenoid (24 VDC)
Connector entry direction
1
Upward
2
Lateral
Note) If the mounting option “N” (Mounting nut:
Inch size) is selected, the bracket cannot be
mounted.
F1
With bracket
(Standard)
F2
With bracket
(Port
downward)
Nil
Manifold direct mounting type
Manifold direct mounting type
With mounting nut
M3 x 0.5
With mounting nut
No. 10-32 UNF
(Inch size)
N
Symbol
Mounting
Note)
4
How to Order Valve for Connector Type
Standard V1 1 U0 C4
With switch V1
Note 1) See page 13 for the dedicated non plug-in
individual wiring.
V1 1 Z0 C4
1
5
5M
5
C
CZJ0 C4
Normally closed (N.C.)
Normally open (N.O.)
Type of actuation
1
2
Rated voltage
24 VDC
12 VDC
5
6
Single wiring
Double wiring
Single solenoid
wiring specification
Nil
D
∗ Nil for the double solenoid.
Select this when the unused
numbers to wiring are set. See
page 6 for details.
Individual wiring
[For plug-in mixed mounting] Note 1)
With light/surge voltage suppressor
(Non-polar type)
With light/surge voltage suppressor
(Polar type)
Light/surge voltage suppressor
U
Z
∗When the types with power saving circuit, with
switches, and individual wiring are used, the
non-polar type cannot be selected.
∗“Z” is positive common specification.
Standard
With power saving circuit (Continuous duty type)
Coil specification
Nil
T
∗ Be certain to select “with power saving circuit” when the solenoid
valve will be energized continuously for long periods of time.
∗ Normally closed and normally open
type cannot be mounted on the
same manifold.
Specifications
Number of solenoids
Symbol
1 pc. (Single solenoid)
2 pcs. (Double solenoid)
S
D
T
T
D
D
D
∗Connector entries with the symbol
“M” cannot use the switch signal
from the D-sub connector on the
manifold. For details, refer to Mani-
fold Electrical Wiring on page 6.
∗When ordering a connector assem-
bly separately, see back pages 6
and 7.
Connector entry
C: Dedicated for centralized wiring
M: Individual wiring, With lead wire
Length 300 mm
MN: Individual wiring, Without lead wire
(With connector, socket)
MO: Individual wiring, Without
connector
With switch
Note 2) The electric connection to the
manifold will be positive
common specification when
light/surge voltage
suppressor is “Z” (Polar type).
2a/2b fitting port size
Straight fitting
(Metric size)
C2: ø2 one-touch fitting
C4: ø4 one-touch fitting
(Inch size)
N1: ø1/8" one-touch fitting
N3: ø5/32" one-touch fitting
Elbow fitting (Upward entry)
(Metric size)
L2: ø2 one-touch fitting
L4: ø4 one-touch fitting
(Inch size)
LN1: ø1/8" one-touch fitting
LN3: ø5/32" one-touch fitting
Elbow fitting (Downward entry)
(Metric size)
B2: ø2 one-touch fitting
B4: ø4 one-touch fitting
(Inch size)
BN1: ø1/8" one-touch fitting
BN3: ø5/32" one-touch fitting
With linkage
printed
circuit board
With linkage
printed
circuit board
With linkage
printed
circuit board
5
Series VV100
3 Port Solenoid Valve/D-sub Connector
Connector Type Manifold
Plug-in
Station 3
SOL.a
SOL.b
SOL.a
SOL.b
SOL.a
Station 4
Station 1
baCommon (+)
Individual wiring (M type)
Station 2
Single solenoid
Station 4
Double solenoid
Station 3
Double solenoid
Station 1
(D-sub connector)
Connector side
Solenoid
Common (+, –)
SOL.b
SOL.a
Station 3
SOL.a
Unused terminal
Station 2
SOL.a
SOL.b
Station 1
Double solenoid
Station 3
Common (+, –)
Single solenoid
(Double wiring specification)
Station 2
Double solenoid
Station 1
(D-sub connector)
Connector side
Solenoid
Connector side
Solenoid
Station 3
Station 2
Station 1
Double solenoid
Station 3
Double solenoid
Station 1
(D-sub connector)
SOL.b
SOL.a
SOL.a
SOL.b
SOL.a
Common (+, –)
Single solenoid
Station 2
Station 1
Station 5
Station 9
Station 4
Station 8
Station 12
SOL.a
SOL.b
SOL.a
SOL.b
SOL.b
SOL.a
SOL.a
SOL.b
SOL.a
SOL.b
Common
SOL.a
SOL.b
25
26
16
7
1
17
11
20
10
18
8
9
19
2
Station 7
SOL.b
SOL.a
Station 6
SOL.b
SOL.a
Station 2
Station 1
10
2
SOL.b
SOL.a
SOL.b
6
7
8
15
14
SOL.a
Common
9
1
Manifold Electrical Wiring (Image)
When a valve is added, the signals of the connector are assigned to the valve. This makes it completely unnecessary to disassemble the connector unit.
∗The connector arrangement shown below differs from the actual arrangement. Refer to the Connector Wiring Diagram below.
Individually Wired Valve
Single Solenoid with Double Wiring Specification
Single Solenoid and Double Solenoid
Type FA: D-sub connector (15 pins) Type FB: D-sub connector (26 pins)
Note) This circuit is for the specification with up to 7 stations of double solenoid
valves. This should be wired in order 1→9→2→10 without skipping or leav-
ing any connectors remaining.
Note) This circuit is for the specification with up to 12 stations of double solenoid
valves. This should be wired in order 1→2→3→4 with the exception of 9, 18
(Common) without skipping or leaving any connectors remaining.
Connector Wiring Diagram
When the non-polar type (U) valves are used, either +COM or –COM wiring of the manifold is possible. However, the valve does not switch with –COM if a
type (Z) is used. Be certain to use +COM.
Caution
6
Series VV100
AB
(8.9)
(9.4)
50.3
5.3
(When equipped with switch)
9.9
(For individual wiring)
22
9.8
2 x M2.6 x 0.45
No. 4-40 UNC
if the fitting size is inch 30.6
Approx. 300
(Lead wire length)
(Station 1)(Station n)
2a
2b
2a
2b
2a
2b
2a
2b
3
1
2a
2b
(Pitch)
P = 10.2
One-touch fitting
[1(P), 3(E) port]
Applicable tubing O.D: ø2
ø4
ø1/8"
ø5/32"
One-touch fitting
(2a, 2b port)
Applicable tubing O.D: ø4
ø6
ø5/32"
ø1/4"
4 x M3 x 0.5
Thread depth 4.8, hole depth 7 Note 3)
(For direct mounting)
11.8 18.7
40
11.45.7
12 14
4.531.1
L2 26.4
36.6
L1
(8.9)
If the fittings are
mounted on side.
4 x No. 10-32 UNF if the
mounting option “N” is selected
13
If the fittings are mounted on side.
(6.3)
Solenoid No. 13
ON
OFF
ON
OFF
Solenoid No.
Light/surge voltage suppressor
SOL.a: Orange
SOL.b: Green
Switch
(When equipped with switch)
24
U side D side
Dimensions
VV100-10F D1- U -
Stations 1
2
A
B
n: Stations
Ln
L: Dimensions
L1
L2
1
53.7
20.4
2
63.9
30.6
3
74.1
40.8
4
84.3
51
5
94.5
61.2
6
104.7
71.4
7
114.9
81.6
8
125.1
91.8
9
135.3
102
10
145.5
112.2
11
155.7
122.4
12
165.9
132.6
Note 1) 10FA and 10FB types have the same L1
and L2 dimensions, and the only difference
is the number of poles of the connector.
See page 6 for the pin arrangement.
Note 2) For manifold dimensions including elbow
fitting, see page 11.
Note 3) As the distance between the block end to
the thread is 2.5 mm, the screw depth
should be 5 to 7 mm.
7
Series VV100
3 Port Solenoid Valve/D-sub Connector
Connector Type Manifold
Plug-in
AB
4 x M3 for mounting
(Bracket)
(9.4)50.39.9
(For individual wiring)
5.3
(When equipped with switch)
6.7
56.9
L2
L3
8
(4.4)
3.2
3.322
9.75
15.5
11.5
(8.9)
6.7
13
Solenoid No.
(Station 1)(Station n)
For F2
30.6
Approx. 300
(Lead wire length)
(1.2)
ON
OFF
ON
OFF
24
Solenoid No.
Light/surge voltage suppressor
SOL.a: Orange
SOL.b: Green
Switch
(When equipped with switch)
2a
2b
2a
2b
2a
2b
2a
2b
2a
2b
3
1
(Pitch)
P = 10.2
Applicable tubing O.D: ø2
ø4
ø1/8"
ø5/32"
Bracket for side ported 36.6
One-touch fitting
(2a, 2b port)
Applicable tubing O.D: ø4
ø6
ø5/32"
ø1/4"
One-touch fitting
[1(P), 3(E) port]
40
11.8 18.7
1.2
1412
L1
(8.9)
If the fittings are
mounted on side.
11.45.7
2a
2b
2a
2b
2a
2b
2a
2b
2a
2b
3
1
4 x M3
for mounting
(Bracket)
Bracket for bottom ported
4
33 3.5
40
20 39
L4
L5
13
If the fittings are
mounted on side.
(6.3)
U side D side
2 x M2.6 x 0.45
No. 4-40 UNC
if the fitting size is inch
Dimensions
VV100-10F D1-
A
BF1
F2
U -
Stations 1
2
n: Stations
Ln
L: Dimensions
L1
L2
L3
L4
L5
1
53.7
42.2
50.2
61.2
68.6
2
63.9
52.4
60.4
71.4
78.8
3
74.1
62.6
70.6
81.6
89
4
84.3
72.8
80.8
91.8
99.2
5
94.5
83
91
102
109.4
6
104.7
93.2
101.2
112.2
119.6
7
114.9
103.4
111.4
122.4
129.8
8
125.1
113.6
121.6
132.6
140
9
135.3
123.8
131.8
142.8
150.2
10
145.5
134
142
153
160.4
11
155.7
144.2
152.2
163.2
170.6
12
165.9
154.4
162.4
173.4
180.8
Bracket option: F1 (For side ported)
Bracket option: F2 (For bottom ported)
Note 1) 10FA and 10FB types have the same L1 to
L5 dimensions, and the only difference is
the number of poles of the connector. See
page 6 for the pin arrangement.
Note 2) For manifold dimensions including elbow
fitting, see page 11.
8
Series VV100