SMC Networks S070 Series User manual

Other SMC Networks Control Unit manuals

SMC Networks EX600-SMJ Series User manual

SMC Networks

SMC Networks EX600-SMJ Series User manual

SMC Networks EX430-SIL1 User manual

SMC Networks

SMC Networks EX430-SIL1 User manual

SMC Networks VHS20 Series User manual

SMC Networks

SMC Networks VHS20 Series User manual

SMC Networks EX250-SCF1-X200 User manual

SMC Networks

SMC Networks EX250-SCF1-X200 User manual

SMC Networks VF1000 Series Manual

SMC Networks

SMC Networks VF1000 Series Manual

SMC Networks IBV1 Series User manual

SMC Networks

SMC Networks IBV1 Series User manual

SMC Networks 56-VQC1000 Series Manual

SMC Networks

SMC Networks 56-VQC1000 Series Manual

SMC Networks 4501 Series User manual

SMC Networks

SMC Networks 4501 Series User manual

SMC Networks VQC2000 Manual

SMC Networks

SMC Networks VQC2000 Manual

SMC Networks VQ2000 Series Manual

SMC Networks

SMC Networks VQ2000 Series Manual

SMC Networks VJ3000 Manual

SMC Networks

SMC Networks VJ3000 Manual

SMC Networks VQZ100 Series User manual

SMC Networks

SMC Networks VQZ100 Series User manual

SMC Networks VCC Series User manual

SMC Networks

SMC Networks VCC Series User manual

SMC Networks SYJ3000 User manual

SMC Networks

SMC Networks SYJ3000 User manual

SMC Networks VQZ 1000 Manual

SMC Networks

SMC Networks VQZ 1000 Manual

SMC Networks AV2000-02-1 User manual

SMC Networks

SMC Networks AV2000-02-1 User manual

SMC Networks EX12 SMJ1 Series User manual

SMC Networks

SMC Networks EX12 SMJ1 Series User manual

SMC Networks VQ100 Series User manual

SMC Networks

SMC Networks VQ100 Series User manual

SMC Networks CP96 Series User manual

SMC Networks

SMC Networks CP96 Series User manual

SMC Networks VFR4000 Series User manual

SMC Networks

SMC Networks VFR4000 Series User manual

SMC Networks 5100 IT Series User manual

SMC Networks

SMC Networks 5100 IT Series User manual

SMC Networks VXS23 Manual

SMC Networks

SMC Networks VXS23 Manual

SMC Networks EX260-SDN1 Instruction Manual

SMC Networks

SMC Networks EX260-SDN1 Instruction Manual

SMC Networks JSXF Series User manual

SMC Networks

SMC Networks JSXF Series User manual

Popular Control Unit manuals by other brands

Festo Compact Performance CP-FB6-E Brief description

Festo

Festo Compact Performance CP-FB6-E Brief description

Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

Elo TouchSystems

Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

JS Automation MPC3034A user manual

JS Automation

JS Automation MPC3034A user manual

JAUDT SW GII 6406 Series Translation of the original operating instructions

JAUDT

JAUDT SW GII 6406 Series Translation of the original operating instructions

Spektrum Air Module System manual

Spektrum

Spektrum Air Module System manual

BOC Edwards Q Series instruction manual

BOC Edwards

BOC Edwards Q Series instruction manual

KHADAS BT Magic quick start

KHADAS

KHADAS BT Magic quick start

Etherma eNEXHO-IL Assembly and operating instructions

Etherma

Etherma eNEXHO-IL Assembly and operating instructions

PMFoundations Attenuverter Assembly guide

PMFoundations

PMFoundations Attenuverter Assembly guide

GEA VARIVENT Operating	 instruction

GEA

GEA VARIVENT Operating instruction

Walther Systemtechnik VMS-05 Assembly instructions

Walther Systemtechnik

Walther Systemtechnik VMS-05 Assembly instructions

Altronix LINQ8PD Installation and programming manual

Altronix

Altronix LINQ8PD Installation and programming manual

Eaton Powerware Series user guide

Eaton

Eaton Powerware Series user guide

WAGO 750-407/040-000 manual

WAGO

WAGO 750-407/040-000 manual

Sony CCU-590 Operation manual

Sony

Sony CCU-590 Operation manual

Graco 25D614 instructions

Graco

Graco 25D614 instructions

Task Force Tips YE-RF-900 Instructions for installation, safe operation and maintenance

Task Force Tips

Task Force Tips YE-RF-900 Instructions for installation, safe operation and maintenance

Shini SPV-U Series manual

Shini

Shini SPV-U Series manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

S070-TF2Z543EN
Page 1 of 2
Instruction Manual
3 Port Solenoid Valve
Series S070
The intended use of this valve is to control the movement of an actuator.
1 Safety Instructions
These safety instructions are intended to prevent hazardous situations
and/or equipment damage. These instructions indicate the level of
potential hazard with the labels of “Caution,” “Warning” or “Danger.”
They are all important notes for safety and must be followed in addition
to International Standards (ISO/IEC)*1), and other safety regulations.
*1) ISO 4414: Pneumatic fluid power - General rules relating to systems.
ISO 4413: Hydraulic fluid power - General rules relating to systems.
IEC 60204-1: Safety of machinery - Electrical equipment of machines.
(Part 1: General requirements)
ISO 10218-1: Robots and robotic devices - Safety requirements for
industrial robots - Part 1: Robots.
•Refer to product catalogue, Operation Manual and Handling
Precautions for SMC Products for additional information.
•Keep this manual in a safe place for future reference.
Caution
Caution indicates a hazard with a low level of risk which, if
not avoided, could result in minor or moderate injury.
Warning
Warning indicates a hazard with a medium level of risk
which, if not avoided, could result in death or serious injury.
Danger
Danger indicates a hazard with a high level of risk which, if
not avoided, will result in death or serious injury.
Warning
•Always ensure compliance with relevant safety laws and
standards.
•All work must be carried out in a safe manner by a qualified person in
compliance with applicable national regulations.
Caution
•The product is provided for use in manufacturing industries only. Do
not use in residential premises.
2 Specifications
2.1 Valve specifications
Valve construction
Poppet
Fluid
Air / Low vacuum (1.33 x 102Pa)
Maximum operating
pressure [MPa] Note 1)
0.35 W / 0.1 W
0.3
0.5 W
0.5
Proof pressure [MPa]
1
Ambient and fluid temperature [˚C] Note 2)
-10 to 50 (no freezing)
Flow rate characteristics
Refer to catalogue
Response time
Duty cycle
Contact SMC
Minimum operating frequency [Hz]
1 cycle / 30 days
Manual override
None
Lubrication
Not required
Impact/Vibration
resistance [m/s2] Note 3)
0.35 W / 0.5 W
150 / 30
0.1 W
50 / 10
Enclosure (based on IEC60529)
IP40
Mounting orientation
Unrestricted
Weight [g] (valve only)
5
Table 1.
2 Specifications - continued
Note 1) With the low vacuum specification, the operating pressure range is 1.33 x
102Pa to the maximum operating pressure.
Note 2) Use dry air to prevent condensation when operating at low temperatures.
Note 3) Impact resistance: No malfunction resulted in an impact test using a drop
impact tester. The test was performed one time each in the axial and right
angle directions of the main valve and armature, for both energized and de-
energized states. (Values quoted are for a new valve).
Vibration resistance: No malfunction resulted in 45 to 2000 Hz, a one-
sweep test performed in the axial and right angle directions of the main
valve and armature for both energized and de-energized states. (Values
quoted are for a new valve).
2.2 Solenoid specifications
Electrical entry
Grommet (G), Plug lead (C)
Coil rated voltage [VDC]
24, 12, 6, 5, 3
Allowable voltage fluctuation Note 1)
±10% of rated voltage
Coil insulation class
Class B or equivalent
Power
consumption [W]
Note 2)
Standard
0.35
High voltage
0.5
Holding Note 3)
0.1
Surge voltage
suppressor
0.35 W / 0.5 W
Varistor
0.1 W
Diode
Indicator light
LED
Table 2.
Note 1) Care should be taken about the voltage drop when the rated voltage is 6
VDC or less or when the response speed is important.
Note 2) With a light/surge voltage suppressor and power saving circuit, the light
consumes a power equivalent to 2 mA.
Note 3) 0.1 W specification is only available with 24 VDC plug lead type.
2.3 Manifold specifications
Refer to catalogue.
2.4 Indicator light
Figure 1. Only for Plug lead (C) type
2.5 Special products Warning
Special products (-X) might have specifications different from those
shown in this section. Contact SMC for specific drawings.
3 Installation
3.1 Installation Warning
•Do not install the product unless the safety instructions have been read
and understood.
3.2 Environment Warning
•Do not use in an environment where corrosive gases, chemicals, salt
water or steam are present.
•Do not use in an explosive atmosphere.
•Do not expose to direct sunlight. Use a suitable protective cover.
•Do not install in a location subject to vibration or impact in excess of
the product’s specifications.
•Do not mount in a location exposed to radiant heat that would result in
temperatures in excess of the product’s specifications.
3 Installation - continued
3.3 Piping Caution
•Before connecting piping make sure to clean up chips, cutting oil, dust
etc.
•When installing piping or fittings, ensure sealant material does not
enter inside the port. When using seal tape, leave 1 thread exposed
on the end of the pipe/fitting.
•Tighten M3screws 1/4turn past hand tightness, andM5 screws by 1/6
turn past hand tightness (1/4 turn for miniature fittings) and to the
specified tightening torque as per below table.
Connection threads
Proper tightening torque [N∙m]
M3
0.4 to 0.5
M5
1 to 1.5
Table 3.
3.3.1 Tubing installation
Figure 2.
3.4 Lubrication Caution
•SMC products have been lubricated for life at manufacture, and do not
require lubrication in service.
•If a lubricant is used in the system, refer to catalogue for details.
3.5 Air supply Warning
•Use clean air. If the compressed air supply includes chemicals,
synthetic materials (including organic solvents), salinity, corrosive gas
etc., it can lead to damage or malfunction.
Caution
•Install an air filter upstream of the valve. Select an air filter with a
filtration size of 5 μm or smaller.
3.6 Mounting
Caution
•Ensure gaskets are in good condition, not deformed and are dust and
debris free.
•When mounting valves ensure gaskets are present, aligned and
securely in place. After tightening by hand, tighten an additional 1/4
rotation for M3 and 1/6 rotation for M5. Tighten the screws to torque
levels as per figure below.
•Refer to catalogue for additional information.
Base mounted with screws
Base mounted with clips
Solenoid valve fixing procedure (body ported single unit)
Figure 3.
3 Installation - continued
3.7 Electrical circuits Caution
Surge suppression should be specified by using the appropriate part
number. If a valve type without suppression (Type ‘G’) is used,
suppression must be provided by the host controller as close as possible
to the valve.
Grommet
Plug lead
(With light/surge voltage suppressor)
With power saving circuit
(Energizing time before holding power kicks in: 100 ms)
Table 4.
Note) There is no polarity for Grommet type or Plug lead type.
3.8 Residual voltage of the surge voltage suppressor
Caution
•The suppressor arrests the back EMF voltage from the coil to a level
in proportion to the rated voltage.
•Ensure the transient voltage is within the specification of the host
controller.
•Contact SMC for the varistor residual voltage.
•In the case of a diode, the residual voltage is approximately 1 V.
•Valve response time is dependent on surge suppression method
selected.
3.9 Countermeasure for surge voltage
Caution
•At times of sudden interruption of the power supply, the energy stored
in a large inductive device may cause non-polar type valves in a de-
energized state to switch.
•When installing a breaker circuit to isolate the power, consider a valve
with polarity (with polarity protection diode), or install a surge
absorption diode across the output of the breaker.
3.10 Extended periods of continuous energization
Warning
If a valve will be continuously energized for an extended period of time,
the temperature of the valve will increase due to the heat generated by
the coil assembly. This will likely adversely affect the performance of the
valve and any nearby peripheral equipment. Therefore, if the valve is to
be energized for periods of longer than 30 minutes at a time or if during
the hours of operationthe energized period per day is longer than thede-
energized period, we advise using valves with power saving circuit (type
E or F).
3.11 Effect of back pressure when using a manifold
Warning
Use caution when valves are used on a manifold because an actuator
may malfunction due to back-pressure.
4 How to Order
Refer to catalogue for ‘How to Order’.
5 Outline Dimensions
Refer to catalogue for outline dimensions.
6 Maintenance
6.1 General maintenance Caution
•Not following proper maintenance procedures could cause the product
to malfunction and lead to equipment damage.
•If handled improperly, compressed air can be dangerous.
ORIGINAL INSTRUCTIONS
Indicator light
Mounting
bracket
Manifold base
Manifold bracket
Mounting screws
Tightening torque:
0.1 N∙m to 0.14 N∙m
Solenoid
valve body
Solenoid cover (Metal)
Body (Resin)
Mounting screws (secures the body)
Tightening torque: 0.05 N∙m to 0.07 N∙m
SOL.
SOL.
SOL.
Diode
Varistor
.
LED
Power
saving
circuit
S070-TF2Z543EN
Page 2 of 2
6 Maintenance - continued
•Maintenance of pneumatic systems should be performed only by
qualified personnel.
•Before performing maintenance, turn off the power supply and be sure
to cut off the supply pressure. Confirm that the air is released to
atmosphere.
•After installation and maintenance, apply operating pressure and
power to the equipment and perform appropriate functional and
leakage tests to make sure the equipment is installed correctly.
•If any electricalconnections are disturbed during maintenance, ensure
they are reconnected correctly and safety checks are carried out as
required to ensure continued compliance with applicable national
regulations.
•Do not make any modification to the product.
•Do not disassemble the product, unless required by installation or
maintenance instructions.
6.2 Replacement parts
Refer to catalogue for replacement parts.
6.3 Addition and removal of manifold stations
Refer to catalogue for additional information.
7 Limitations of Use
7.1 Limited warranty and disclaimer/compliance requirements
Refer to Handling Precautions for SMC Products.
Warning
7.2 Return of the valve to the de-energised position
When electricity is cut, the valve returns to the de-energised position by
spring force.
7.3 Holding of pressure
Since valves are subject to air leakage, they cannot be used for
applications such as holding pressure (including vacuum) in a system.
7.4 Cannot be used as an emergency shut-off valve
This product is not designed for safety applications such as an
emergency shut-off valve. If the valves are used in this type of system,
other reliable safety assurance measures should be adopted.
Caution
7.5 Leakage voltage
Ensure that any leakage voltagecaused by the leakage current when the
switching element is OFF causes ≤ 2% of rated voltage across the valve.
7.6 Low temperature operation
Unless otherwise indicated in the specifications for each valve, operation
is possible to -10˚C, but appropriate measures should be taken to avoid
solidification or freezing of drainage and moisture, etc.
7.7 Vacuum release application
•Use 3 (R) port for vacuum pressure and 1 (P) port for vacuum release
pressure.
•Set the pressure so that the pressure difference between the 3(R) and
1(P) ports does not exceed the maximum operating pressure of the
valve.
•When the 3(R) port is used for the vacuum release (atmospheric
pressure to positive pressure) and the 1(P)port is used forthe vacuum,
use the normally open (N.O.) specifications.
Figure 4.
8 Product Disposal
This product shall not be disposed of as municipal waste. Check your
local regulations and guidelines to dispose this product correctly, in order
to reduce the impact on human health and the environment.
9 Contacts
Refer to www.smcworld.com or www.smc.eu for your local
distributor/importer.
URL : https:// www.smcworld.com (Global) https:// www.smc.eu (Europe)
SMC Corporation, 4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021, Japan
Specifications are subject to change without prior notice from the manufacturer.
© 2022 SMC Corporation All Rights Reserved.
Template DKP50047-F-085M
Vacuum supply
Vacuum pad
Air supply (positive pressure)