  9. Swegon HAWK Ceiling a Guide

Swegon HAWK Ceiling a Guide

Accessories
Commissioning box:
ALS. The ALS box is made of galvanized sheet steel and contains
a removable commissioning damper, fixed measurement tappings
and sound absorbing material*
)
with reinforced surface layer.
The ALS commissioning box is available with one or two differences
in dimension between the inlet and the outlet and also a version
for low installation where a low overall height is required. The ALS
commissioning box is then supplied without outlet branch.
*Fire resistance rated to B-s1,d0 in accordance with EN ISO 11925-2.
Frame:
SAR K. For aesthetic installation of a lowered air diffuser.
Adapter:
ADAPTER, for adaptation to various variants and makes of
systemized false ceilings: Ecophon, Gyproc, Dampa etc. Also
used for adaptation to optional sizes of lay-in ceilings, for
instance 625 x 625 or 675 x 675.
Installation
To dismantle the diffuser face, insert a thin object, for example a
Quick Access card or the equivalent, in between the diffuser face
and the diffuser backing box in order to release the springs. Move
the card from the centre out towards the corner, see Figure 2.
The inlet spigot of the air diffuser backing box can be secured to
the connecting duct by means of self-tapping screws or a blind
rivets. For flush-mounting in fixed false ceiling constructions,
secure the terminal by means of screws into place in the frame-
work through either the sides or top of the diffuser backing box.
The air diffuser and commissioning box in the version for low
installation height must be centred and jointed together using the
locking strip supplied. Secure the air diffuser in the correct posi-
tion with self-tapping screws or pop rivets in the underside of the
commissioning box.
For mounting in modular false ceilings, it is advisable to select air
diffusers with outer dimensions of 595 x 595 mm. Position these
directly down in the T-bar framework, and then secure them to
the duct system or to the commissioning box.
If an ALS commissioning box is used, it must be secured to the
building structure by means of hangers or mounting brackets.
The distance between the commissioning box and the air diffuser
can be increased by as much as 500 mm with an ordinary circular
duct without having to lengthen the measuring tubes and damper
adjustment cords. See Figures 3 and 4.
Commissioning
Commissioning should be carried out with the air diffuser face
mounted. Pull the measuring tubes and damper adjustment cords
out through the air diffuser face. Then connect the manometer to
the correct measuring tube. The red and the blue tubes respectively
from the ALS commissioning box of the one or two-step version
are used for supply air. For extract air, always use the transparent
tube. The rated coefficient of performance of the air diffuser can
Figure 1. Commissioning.
Quick
Access
HAWK CEILING
Tomelilla
Sweden
200-600
+ALS 160 -200/125 -200
k
q
k = XX / XX
P
T
I
L
L
U
F
T
/
S
U
P
P
L
Y
A
I
R
T
I
L
L
U
F
T
/
S
U
P
P
L
Y
A
I
R
F
R
Å
N
L
U
F
T
/
E
X
T
R
A
C
T
A
I
R
kPq⋅=
k
Pq
=
( )2
be used in a calculation to determine the required commissioning
pressure. Conclude commissioning by adjusting the damper to the
correct blade position, tie a commissioning knot in the damper
cords to indicate the damper position. See Figure 1.
Measurement accuracy and requirement on straight duct before
the commisioning box, see Figure 3. The requirements of straigh
duct depends on the type of disturbance before the commis-
sioning box. Figure 3 shows a bend, a dimensional change and a
T-piece. Other types of disturbances requires at least 2xD straight
(D = connection dimension) for measurement accuracy of ± 10%
of the flow.
The rated coefficient of performance (K-factor) is specified on the
identification label of the product and in the relevant commission-
ing instructions at www.swegon.com.
Maintenance
The air diffuser can be cleaned, if necessary, using lukewarm water
with dishwashing detergent added or by vacuum cleaning using a
brush nozzle. The duct system can be reached for cleaning after
opening the air diffuser face. If a type ALS commissioning box is
used, swing the air diffuser face to the side on its hinges so that
you then can grip the handle of the tubular damper casing and
rotate it out of its holder. See Figure 6.
q= flow reading l/s
p= current pressure reading (Pa)
k= commissioning factor
k-factor
HAWK Ceiling a
Installation – Commissioning – Maintenance 20180814
Figure 4. Installation of air diffusers and commissioning box with
low installation height.
Figure 3. Installation alternatives.
Figure 2. Quick Access.
Installation
Figure 5. To dismantle the damper.
0xD / ±5% 0xD / ±5% 2xD / ±10%
HAWK Ceiling
2Swegon reserves the right to alter specications. 20180814
B
AxA
Figure 7. HAWK Ca with ALS. CL = Centerline.
Figure 9. SARb K frame.
1
Figure 8. HAWK Ca with ALS. Low installation height.
Figure 6. HAWK Ceiling
Dimensions and Weights
HAWK Ceiling
Size AØD ØD1 I M Weight, kg
125-600 595 340 124 575 70 3.5
160-600 595 340 159 575 70 3.5
200-600 595 420 199 575 70 3.5
250-600 595 500 249 575 70 3.5
315-600 595 500 314 575 50 3.5
400-600 595 500 399 575 50 3.5
Dimensions of opening in ceiling = l x l
HAWK Ceiling with ALS – 1 step
Size ABCØD Ød E1 E2
125-600 595 282 217 99 125 255 212
160-600 595 342 252 124 160 279 236
200-600 595 404 288 159 200 314 271
250-600 595 504 332 199 250 354 311
315-600 595 622 388 249 315 395 352
400-600 595 767 488 314 400 455 –
Size F1 F2 G1 G2 H K Weight, kg
125-600 113 70 175 132 270 80 5.5
160-600 113 70 188 145 315 80 6.2
200-600 113 70 205 162 375 100 7.0
250-600 113 70 225 182 465 115 8.7
315-600 93 50 230 187 575 140 11.8
400-600 93 –262 –712 175 15.0
HAWK Ceiling with ALS – 2 steps
Size A B C ØD Ød E1 E2
160-600 595 342 252 99 160 255 212
200-600 595 404 288 124 200 279 236
250-600 595 504 332 159 250 314 271
315-600 595 622 388 199 315 334 291
Size F1 F2 G1 G2 H K Weight, kg
160-600 113 70 175 132 315 80 5.5
200-600 113 70 188 145 355 80 4.2
250-600 113 70 205 162 450 100 7.0
315-600 93 50 205 162 550 115 8.7
CL = Center line
3
20180814 Swegon reserves the right to alter specications.
HAWK Ceiling
Coefficient of performance, HAWK C
Supply air
ALSd HAWK C, supply air
Size Size Standard Low version Colour of the tube
100 -125 125- 400 8.4 8.0 Red
100-160 160-400 11.7 10.9 Blue
125-160 160-400 12.3 11.9 Red
125-200 200-500 19.1 17.0 Blue
160-200 200-500 20.9 18.2 Red
160-200 200-600 29.1 25.7 Blue
200-250 250-500 28,4 -Red
200-250 250-600 32.5 28.5 Red
200-315 315-500 30,3 -Blue
250 -315 315-500 31,8 -Red
200-315 315-600 37.0 34.2 Blue
250 -315 315-600 39.4 35.3 Red
315-400 400-600 50.9 -Red
Number of measuring tubes: 1
Extract air
ALSd HAWK C, extract air
Size Size Standard Colour of the tube
200-250 250-600 19.1 Transparent
250 -315 315-600 25.4 Transparent
315-400 400-600 34.9 Transparent
Number of measuring tubes: 1
HAWK Ceiling
4Swegon reserves the right to alter specications. 20180814

Other Swegon Fan manuals

Swegon PARAGON-X m User manual

Swegon

Swegon PARAGON-X m User manual

Swegon ADAPT Extract Guide

Swegon

Swegon ADAPT Extract Guide

Swegon DRIF Instructions for use

Swegon

Swegon DRIF Instructions for use

Swegon EAGLE Free e Guide

Swegon

Swegon EAGLE Free e Guide

Swegon EAGLE Ceiling Guide

Swegon

Swegon EAGLE Ceiling Guide

Swegon ADAPT Extract Guide

Swegon

Swegon ADAPT Extract Guide

Swegon COMPACT Air User manual

Swegon

Swegon COMPACT Air User manual

Swegon HAWK Ceiling User manual

Swegon

Swegon HAWK Ceiling User manual

Swegon GOLD RX User manual

Swegon

Swegon GOLD RX User manual

Swegon ADAPT Colibri Guide

Swegon

Swegon ADAPT Colibri Guide

Swegon CASA W100B Programming manual

Swegon

Swegon CASA W100B Programming manual

Swegon ADAPT Parasol b User manual

Swegon

Swegon ADAPT Parasol b User manual

Swegon CASA R120 Operator's manual

Swegon

Swegon CASA R120 Operator's manual

Swegon PARASOL Zenith a Series User manual

Swegon

Swegon PARASOL Zenith a Series User manual

Swegon ADAPT Free b Guide

Swegon

Swegon ADAPT Free b Guide

Swegon PARASOL VAV Series Guide

Swegon

Swegon PARASOL VAV Series Guide

Swegon COMPACT Air User manual

Swegon

Swegon COMPACT Air User manual

Swegon ROWb Guide

Swegon

Swegon ROWb Guide

Swegon EAGLE Wall b Guide

Swegon

Swegon EAGLE Wall b Guide

Swegon ADAPT Colibri d Guide

Swegon

Swegon ADAPT Colibri d Guide

Swegon ADAPT Sphere c User manual

Swegon

Swegon ADAPT Sphere c User manual

Swegon CASA W3 Smart User manual

Swegon

Swegon CASA W3 Smart User manual

Swegon SWAN a Guide

Swegon

Swegon SWAN a Guide

Swegon GOLD LP Troubleshooting guide

Swegon

Swegon GOLD LP Troubleshooting guide

Popular Fan manuals by other brands

Eberg FYN user manual

Eberg

Eberg FYN user manual

HOMCOM 824-017V70 Assembly instruction

HOMCOM

HOMCOM 824-017V70 Assembly instruction

Duraflo 60PRO130 manual

Duraflo

Duraflo 60PRO130 manual

Royal Sovereign TFN-508N owner's manual

Royal Sovereign

Royal Sovereign TFN-508N owner's manual

Jocel JVM030573 instruction manual

Jocel

Jocel JVM030573 instruction manual

HAEGER TF-029 003A User instructions

HAEGER

HAEGER TF-029 003A User instructions

Hunter 21100 Owner's guide and installation manual

Hunter

Hunter 21100 Owner's guide and installation manual

Westinghouse Techno II manual

Westinghouse

Westinghouse Techno II manual

Fakir TVL 30 operating instructions

Fakir

Fakir TVL 30 operating instructions

Ruck Ventilatoren MPC D.F4 T Series Installation, Operating and Maintenance Instructions for the Installer and the User

Ruck Ventilatoren

Ruck Ventilatoren MPC D.F4 T Series Installation, Operating and Maintenance Instructions for the Installer and the User

Fanimation ROTATION FP8018 series manual

Fanimation

Fanimation ROTATION FP8018 series manual

Taurus ALPATEC Forest manual

Taurus

Taurus ALPATEC Forest manual

Kampmann Venkon Series Assembly, installation and operating instructions

Kampmann

Kampmann Venkon Series Assembly, installation and operating instructions

Vortice Vort Penta ES instruction manual

Vortice

Vortice Vort Penta ES instruction manual

Lasko M16900 Important instructions & operating manual

Lasko

Lasko M16900 Important instructions & operating manual

Home YG442-ORB Use and care guide

Home

Home YG442-ORB Use and care guide

Rasonic RLF-8KIR Operation manual

Rasonic

Rasonic RLF-8KIR Operation manual

Hydor HIMF100 Installation and maintenance instructions

Hydor

Hydor HIMF100 Installation and maintenance instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.