3
Setting the time delay (TIME 1)
If the motion detector detects no further movement, it swit-
ches off after the set time delay.
If you want to change the preset time
Set the potentiometer to the desired time (5 s - 30 min).
If you want to use the pulse function (e.g. for a staircase light
timer switch)
Set the potentiometer to . The presence detector for
"staircase light timer switch" operation is on for 1 s and off
for
9 s.
Setting the HVAC time (TIME 2) (only LUXA 103-101 DE)
Set the potentiometer to the desired time (10 s - 60 min.).
Setting the sensitivity (METRES)
You can reduce the sensitivity in order to avoid switching
errors.
Set potentiometer METRES to the desired
sensitivity.
Manual operation
The lighting can be manually switched on/off via a button.
L NLL‘ N R
N
L
When the light is on
Briey press button once (< 1 s)
▻Light is off
When the light is off
Briey press button once
▻The light is on for the time set on the potentiometer;
then the detector goes into automatic mode
Limiting the detection area
Use the supplied cover clips to adjust the motion detector
to the desired detection area.
Remove the required section of the cover clip by using
pliers or similar.
Then place it on the lens.
A
B
7. Technical data
Operating voltage 230 V AC ±10%
Frequency 50 Hz/60 Hz
Upstream protection device 10 A
Standby output 0.5 W
Switching capacity min. 10 mA
Protection rating IP 44 (detector), IP 20 (power supply
unit) in accordance with EN 60529
Protection class II
Operating temperature 0 °C … +45 °C
Brightness setting range 10 – 2000 lx/∞
Duty cycle range LUXA 103-100: 5 s – 30 min for
lighting
LUXA 103-101: 5 s – 30 min for
lighting
10 s – 60 min for HVAC
Detection angle 360°
Detection area lateral/frontal: 7 m/4 m
Installation height 2 – 3 m (2.5 m recommended)
Light switch output µ contact 230 V AC, zero-cross
switching
Switch output HVAC (D1/D2) LUXA 103-101: 5 A (at 250 V AC,
cos ϕ= 1) µ contact
Min. switching capacity 10 mA
Incandescent lamp load max. 2000 W
Halogen lamp load max. 2000 W
Low-voltage halogen lamps
(transformer)
max. 1000 VA
Fluorescent lamps (LLB low-loss
ballasts):
parallel compensated
max. 900 VA, 100 µF
Fluorescent lamps (EB – electronic
ballasts)
600 W
Compact uorescent lamps (EB) 400 W
LED lamps (< 2 W) 35 W
LED lamps (> 2 W) 400 W