On the "theSenda P" installation remote control, the sensi-
tivity can be increased or decreased by one increment each
time the button is pushed.
Incre-
ment
Sensitivity
1 very insensitive
2 insensitive
3 Standard
4 sensitive
5 very sensitive
Group address Channel A light
This parameter is applied when using the "theSenda S" user
remote control. A group address can be assigned to Channel
A light.
The "SendoPro 868-A" or "theSenda S" can be used to pro-
gram the group addresses in the detector.
Group address value range
Adjustable values "SendoPro 868-A" I, II, III, All
Adjustable values "theSenda S" I, II
LED display motion
The motion detection can be displayed via the LED.
Value range (only with management remote control
"SendoPro 868-A")
No display of motion detection. Off
The LED is switched on when motion is detected, otherwise
switched off.
On
Factory settings
The theRonda S360-100 presence detector is supplied with
the following parameter values:
Parameters Value
Brightness switching value Channel A light 300 lux
Time delay Channel A light 10min
Channel H presence time delay 10min
Detection sensitivity (PIR) Increment 3
Group address Channel A light I
LED display motion Off
9. Start-up
Switch-on behaviour
Every time the power supply is switched on, the presence
detector rst runs through a start-up phase of 30s, and then
switches to normal operation. An LED displays the current
status:
1. Start-up phase (30s)
•The red LED ashes at one second intervals, the switch
contact is closed (light on).
•The detector does not react to remote control commands.
•When no one is present, both contacts open after 30s.
2. Operation
The detector is ready for operation (LED off).
Test detection area
The test mode detection area is used to test presence detec-
tion and wiring. Presence test mode can be activated with the
"SendoPro 868-A" management remote control and with the
"theSenda P" installation remote control.
Setting test mode detection area with remote control
•The detector goes directly into test mode when the test
mode is set via the remote control:
Every movement is indicated by the LED.
When movement occurs, the light switch contact closes.
When no one is present, the light switch contact opens
after 10 seconds.
Brightness measurement deactivated, detector does not
react to brightness.
Teach-in cannot be activated in test mode.
•Test mode ends automatically after 10min.
The detector restarts itself (see switch-on behaviour).
10. Technical Data
Operating voltage 230V AC +- 10%
Frequency 50Hz
Upstream protection device: 13A
Power consumption approx. 0.5W
Type of installation Ceiling installation
Recommended installation height 2,0 – 3,0 m/max. 4 m
Minimum height > 1.7m
Detection area horizontal
vertical
360°
120°
Maximum range Ø 4m (Mh. 3m) /13m2 seated
Ø 4m (Mh. 3m) /13m2radially
moving
Ø 8m (Mh. 3m) /50m2tangenti-
ally moving
Setting range brightness switching value 30 – 3000 lux
Lighting time delay A light 10s – 60min/pulse
Channel A light Relay 230V /10A, µ-contact
Max. switching capacity cos j1 resistive 2300W
Max. switching capacity cos j0.5 1150VA
Max. switching capacity LED
Guide values
LED lamps < 2 W
LED lamps ≥ 2 W
see manufacturer concerning
cos j
25 W
70 W
Guidance value max. inrush current level 400A /200µs
Maximum number EBs T5/T8 10 x 54/58W, 16 x 35/36W
5 x 2 x 54/58W
8 x 2 x 35/36W
Connection type Plug-in terminals
Max. cable cross-section max. 2.5mm²
Protection rating: theRonda S360-100DE
Protection rating: theRonda S360-100AP
IP 20
IP 54 in installed state
IP 54
Ambient temperature -15°C to +50°C
CE Declaration of Conformity This device conforms to the
safety regulations of the EMC
directive 2014/30/EC and of
directive 2014/35/EC.