(4) Discharge Pipe High-temp. Protection
After the compressor is started, if the discharge temperature is too high or exhaust sensor is in short circuit (or open
circuit), the indicator will flicker and the unit will be stopped when the indoor ambient temperature reaches the preset
value.After the compressor is stopped for 3 mins, the complete unit will be restarted when the discharge
temperature is resumed to normal range.
If above phenomena occurs twice continuously, the complete unit cannot be restarted automatically, the indicator will
blink and E4 will be displayed. Press ON/OFF button to switch off the unit and press it again to switch on the unit. If the
discharge temperature is normal, the unit will run under preset mode.
5.Under heating mode,if compresoor is running while outdoor fan is stopped(Hi-temp. protection),the detection will be
shield till the outdoor fan resumes running.
4.Under heating mode,if the outdoor ambient temp. is lower than 0 or equal to 0,this detection will be shielded.
the indicator will blink and E3 will be displayed, in which case the unit cannot be restarted automatically. You have to
press ON/OFF button to switch off the unit and press this button again to restart.
6.If it is detected that the low-pressure switch is off when the compressor is stopped, the complete unit will be stopped,
will blink and E2 will be displayed, in which case the compressor and the outdoor fan will stop running, while indoor fan and
5Protection
(1) Indoor Antifreeze Protection
When the unit is cooling under cooling or dry mode . If it is detected that the system is under antifreeze protection, the indicator
The button is not shielded under antifreeze protection.
resume its display and the controller runs in preset mode.
swing motor will maintain the original status. When antifreeze protection is released, the indicator will be black, LCD will
(2) Compressor High-pressure Protection
If high-pressure protection is detected, the unit will close all loads and shield all buttons and remote-control signal,
Upon detecting that the compressor high-pressure protection is released, the indicator will still blink and E1 wil be
displayed, in which case you have to press ON/OFF button to switch off the unit before you can clear E1 display and turn
the indicator. Press ON/OFF button to resume the operation.
(3) Compressor Low-pressure Protection
meanwhile,the indicator will blink and E1 will be displayed.
the complete unit will be stopped and the indicator will flicker. In 3 minutes, the unit will restore running automatically. If
1.After the compressor is started for 3mins, if it is detected for 3 minutes successively that the low-pressure switch is broken,
it again to restore operation.
restore running automatically, so as to remind the user of air leakage. Press ON/OFF button to switch off the unit and press
low-pressure switch protection occurs 2 times successively, the indicator flickers and E3 is displayed ,and the unit cannot
minutes later.
2.Under defrosting mode, low-pressure switch signal can not be detected,which should be done after defrosting finished 10
can resume detection by pressing ON/OFF button to switch off the unit and pressing it again to start the unit.
of low pressure switch signal for purpose of air collection. Detection will be resumed automatically after 6 minutes,or you
3.From the controller, you can press down SWING button and FAN SPEED button simultaneously to shield the detection
Indoor ultra-high temp. protection
Under heating mode, if it is detected that the temp. of evaporator pipe is too high,the outdoor fan will stop runing(defrosting
won't be detected),if temp. gets right, outdoor fan will start running(defrosting will be detected).
E1 Compressor High-pressure Protection
E2 Indoor Antifreeze Protection
E3 Compressor Low-pressure Protection
E4 Exhaust Pipe High-temp. Protection
E5 Low-voltage Protection
(6) ON/OFF button
This button is controlling ON/OFF of the controller. After each pressing, the ON/OFF will be switched once.
Low-voltage Protection
When the compressor is running,and it is detected that the current exceeds specified value,the unit will stop running when
original running status. It needs to press the ON/OFF button to stop the unit and repress the button to resume operation.
6mins, the times of protection will be cleared),their indicator light flickers and displays E5,and the unit can not resume its
resume its original running status. If there are more than 6 times protection (If the compressor has stopped for more than
indoor ambient temperature reaches preset temp. After the compressor has stopped for 3 mins, the unit will automatically
If turn on the unit in heating mode or turn to heating mode from other modes, the air discharge temperature will shield
1min for protection when turning on the unit or the compressor is started up for the first time.
Malfunction and Protection Code