Trotec BA16 User manual

TRT-BA-BA16-TC2019-39-002-EN
BA16
EN
OPERATING MANUAL
VANE ANEMOMETER

2 EN
vane anemometer BA16
Table of contents
Notes regarding the operating manual.................................2
Safety .....................................................................................2
Information about the device................................................3
Transport and storage...........................................................5
Operation ...............................................................................5
Maintenance and repair ........................................................6
Errors and faults....................................................................6
Disposal .................................................................................7
Notes regarding the operating manual
Symbols
Warning of electrical voltage
This symbol indicates dangers to the life and health of
persons due to electrical voltage.
Warning
This signal word indicates a hazard with an average
risk level which, if not avoided, can result in serious
injury or death.
Caution
This signal word indicates a hazard with a low risk
level which, if not avoided, can result in minor or
moderate injury.
Note
This signal word indicates important information (e.g.
material damage), but does not indicate hazards.
Info
Information marked with this symbol helps you to carry
out your tasks quickly and safely.
Follow the manual
Information marked with this symbol indicates that the
operating manual must be observed.
You can download the current version of the operating manual
and the EU declaration of conformity via the following link:
BA16
https://hub.trotec.com/?id=40844
Safety
Read this manual carefully before starting or using the
device. Always store the manual in the immediate vicinity
of the device or its site of use!
Warning
Read all safety warnings and all instructions.
Failure to follow the warnings and instructions may
result in electric shock, fire and/ or serious injury.
Save all warnings and instructions for future
reference.
This appliance can be used by children aged from
8years and above and persons with reduced physical,
sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or
instruction concerning use of the appliance in a safe
way and understand the hazards involved.
Children shall not play with the appliance. Cleaning and
user maintenance shall not be made by children
without supervision.
• Do not use the device in potentially explosive rooms.
• Do not use the device in aggressive atmosphere.
• Do not immerse the device in water. Do not allow liquids to
penetrate into the device.
• The device may only be used in dry surroundings and must
not be used in the rain or at a relative humidity exceeding
the operating conditions.
• Protect the device from permanent direct sunlight.
• Do not expose the device to strong vibrations.
• Do not remove any safety signs, stickers or labels from the
device. Keep all safety signs, stickers and labels in legible
condition.
• Do not open the device.
• Observe the storage and operating conditions as given in
the Technical data chapter.

EN 3
vane anemometer BA16
Intended use
Only use the device for measurements of air velocity, air
temperature and volumetric flow within the measuring range
specified in the technical data. Observe and comply with the
technical data.
To use the device for its intended use, only use accessories and
spare parts which have been approved by Trotec.
Improper use
Do not use the device in potentially explosive atmospheres, for
measurements in liquids or at live parts.
Any unauthorised changes, modifications or alterations to the
device are forbidden.
Personnel qualifications
People who use this device must:
• have read and understood the operating manual, especially
the Safety chapter.
Residual risks
Warning of electrical voltage
There is a risk of a short-circuit due to liquids
penetrating the housing!
Do not immerse the device and the accessories in
water. Make sure that no water or other liquids can
enter the housing.
Warning of electrical voltage
Work on the electrical components must only be
carried out by an authorised specialist company!
Warning
Risk of suffocation!
Do not leave the packaging lying around. Children may
use it as a dangerous toy.
Warning
The device is not a toy and does not belong in the
hands of children.
Warning
Dangers can occur at the device when it is used by
untrained people in an unprofessional or improper way!
Observe the personnel qualifications!
Caution
Keep a sufficient distance from heat sources.
Note
To prevent damages to the device, do not expose it to
extreme temperatures, extreme humidity or moisture.
Note
Do not use abrasive cleaners or solvents to clean the
device.
Information about the device
Device description
The anemometer BA16 can simultaneously measure the
temperature and air velocity.
Temperature measuring is effected by means of an integrated
thermistor in °C or °F.
The air velocity can be indicated in the following units:
• m/s
• km/h
• ft/min
• mph
• knots
• m3/min (CMM)
The sensor is located at a so-called gooseneck probe, with that
it is able to measure even in poorly accessible locations.
Further available for the assessment of the measurements are a
Hold and a Max/Min function.
The display illumination can be switched on as needed.
When not in use, an automatic switch-off saves the battery.
Device depiction
1
2
3
4
No. Designation
1 Measuring sensor with flexible holder
2 Display
3 Operating elements
4 Battery compartment with cover

4 EN
vane anemometer BA16
Operating elements
8
5
6
7
No. Designation
5HOLD/light button
6UNITSbutton
7MAX/MINbutton
8 Power button
Display
10
23
11
12
9
15
16
17
18
22
21
20
19
14
13
No. Designation
9 Indication of the measured temperature value
10 Temperature unit indication
11 AREA indication
12 Indication of the units for velocity and volumetric flow
13 Indication of the measured value x 100
14 Indication of the measured value x 10
15 HOLD indication
16 AVG indication
17 MIN indication
18 MAX indication
19 Indication of the measured velocity value
20 Battery status indication
21 VEL indication
22 RECORD indication
23 RECALL indication
Technical data
Parameter Value
Model BA16
Temperature
Measuring range -10°C to 60°C
(14°F to 140°F)
Accuracy ±1.5°C (3.0°F)
Measuring range
resolution
±0.1°C (±0.1°F)
Air velocity
Measuring range 1.00 m/s to 30.00m/s
196 ft/min to 5900ft/min
3.6 km/h to 108.0km/h
2.2mph to 67.0mph
1.9kn to 58.0kn
Accuracy ±3% ±0.20 m/s
±3% ±40ft/min
±3% ±0.8 km/h
±3% ±0.4mph
±3% ±0.4kn
Measuring range
resolution
0.01m/s
1ft/min
0.1km/h
0.1mph
0.1kn
General technical data
Storage temperature -20 °C to 60°C (-4°F to 140°F)
with <80%RH
(non-condensing)
Operating temperature 0°C to 50°C (32°F to 122°F) with
<80%RH
(non-condensing)
Power supply 1 x 9 V battery
Device switch-off after approx. 15minutes of non-use
Type of protection IP40
Weight approx. 263 g (incl. battery)
Dimensions (Hx Wx D)
Length of the gooseneck
probe
162mmx 54mmx 32mm
360mm
Scope of delivery
• 1x Device BA16
• 1 x 9V battery
• 1 x Transport case
• 1 x Quick guide

EN 5
vane anemometer BA16
Transport and storage
Note
If you store or transport the device improperly, the
device may be damaged.
Note the information regarding transport and storage of
the device.
Transport
For transporting the device, use the transport case included in
the scope of delivery in order to protect the device from external
influences.
Storage
When the device is not being used, observe the following
storage conditions:
• dry and protected from frost and heat
• protected from dust and direct sunlight
• For storing the device, use the transport case included in
the scope of delivery in order to protect the device from
external influences.
• The storage temperature is the same as the range given in
the Technical data chapter.
Operation
Inserting the battery
Note
Make sure that the surface of the device is dry and the
device is switched off.
24
25
1. Remove the cover(24) from the device.
2. Use the battery clip(25) to connect the new battery with
correct polarity.
3. Slide the cover(24) back on the device.
Switch-on and measurements
1. Press the Power button(8) for approx. 3seconds.
ðThe display will be switched on and the device ready for
operation.
2. Hold the measuring sensor(1) into the area where the
measurement is to be performed. Ideally, the vane is
aligned precisely to the flow direction.
ðThe measured values for temperature and air velocity
are displayed in real time.
Note:
Note that moving from a cold area to a warm area can lead to
condensation forming on the device's circuit board. This
physical and unavoidable effect can falsify the measurement. In
this case, the display shows either no measured values or they
are incorrect. Wait a few minutes until the device has become
adjusted to the changed conditions before carrying out a
measurement.
Switching the display illumination on and off
1. Press the HOLD/lampbutton(5) for approx. 2seconds.
ðThe display illumination goes on.
2. Press the HOLD/lampbutton(5) again for approx.
2seconds.
ðThe display illumination switches off.
Setting the temperature unit
1. Press the UNITS button(6) for approx. 3seconds.
ðDepending on the setting the temperature
indication(10) changes to °C or °F.
Setting the air velocity unit
1. Press the UNITS button(6) until the desired unit is
displayed.
Entering the cross-sectional area for volumetric flow
measurement
In order to obtain a precise indication of the volumetric flow
measurement (CMM), the cross-sectional area of the opening to
be tested must be entered prior to measuring. To do so, use the
function AREA. The unit of the cross-sectional area is to be
specified in m². For entering the value of the cross-sectional
area please proceed as follows:
1. Switch the device off.
2. Press and hold the HOLD/lampbutton(5) while switching
the device back on.
ðThe indication SET AREA will be appear on the display.
3. Press the MAX/ MINbutton(7).
ðThe decimal point will move.
4. Press the HOLD/lampbutton(5).
ðYou can alternate between the digits, the selected
number flashes.
5. Press the UNITS button(6).
ðThe value of the selected digit changes.
6. Repeat the steps 4. and 5. until the value is set as desired.

6 EN
vane anemometer BA16
7. Switch the device off.
ðThe set value of the cross-sectional area will be used
for the calculation of the volumetric flow after the next
switch-on.
Indication of minimum and maximum values
1. Press the MAX/ MINbutton(7).
ðThe RECORD indication(22) appears on the display.
2. Press the MAX/MIN button(7) to switch between the
maximum and minimum value.
ðMAX(18) appears on the display.
ðActuating the MAX/ MINbutton(7) starts a new
measurement. The value now appearing on the display
is the reference value.
ðMAXfunction: The maximum value of the newly started
measurement interval is displayed. Values smaller than
the one displayed will not be indicated.
3. Press the MAX/MIN button(7) again.
ðMIN(17) appears on the display.
ðActuating the MAX/ MINbutton(7) starts a new
measurement. The value now appearing on the display
is the reference value.
ðMINfunction: The minimum value of the newly started
measurement interval is displayed. Values exceeding
the one displayed will not be indicated.
4. Press the MAX/ MINbutton(7) for approx. 3seconds to
terminate the function.
ðThe values will be deleted from the buffer memory.
Using the HOLDfunction
1. Press the HOLD/lampbutton(5).
ðThe current value will be indicated on the display.
2. Press the HOLD/lampbutton(5). again.
ðThe display again indicates the current measured value.
Disabling automatic switch-off
As standard, the automatic switch-off function is activated. This
results in the device switching off automatically after
15minutes of non-use. Please proceed as follows to deactivate
the automatic switch-off function:
üThe device is switched off.
1. Additionally press the UNITSbutton(6) when switching the
device on.
ðThe indication disAPO appears on the display.
ðAutomatic switch-off is deactivated.
Info
Note that the automatic switch-off function is activated
upon the next switch-on. If you do not like to use the
function, deactivate the automatic switch-off function
as described.
Switching the device off
1. Briefly press the Power button(8).
ðThe device will be switched off.
ðThe saved measured maximum and minimum values
are reset.
Maintenance and repair
Battery change
A battery change is required when the battery status
indication(20) lights up or the device can no longer be switched
on (see chapter Inserting the battery).
Cleaning
Clean the device with a soft, damp and lint-free cloth. Make
sure that no moisture enters the housing. Do not use any
sprays, solvents, alcohol-based cleaning agents or abrasive
cleaners, but only clean water to moisten the cloth.
Repair
Do not modify the device or install any spare parts. For repairs
or device testing, contact the manufacturer.
Errors and faults
The device has been checked for proper functioning several
times during production. If malfunctions occur nonetheless,
check the device according to the following list.
Fault Cause Remedy
The device can no
longer be switched
on.
The battery is dead. Insert a new battery
(see chapter
Operation).
The device indicates
implausible values
of the volumetric
flow measurement.
The cross-sectional
area of the opening
has not been
entered (correctly).
Determine and enter
the cross-sectional
area of the opening
(inm²) (see chapter
Operation).

EN 7
vane anemometer BA16
Disposal
The icon with the crossed-out waste bin on waste
electrical or electronic equipment stipulates that this equipment
must not be disposed of with the household waste at the end of
its life. You will find collection points for free return of waste
electrical and electronic equipment in your vicinity. The
addresses can be obtained from your municipality or local
administration. For further return options provided by us please
refer to our website www.trotec24.com.
The separate collection of waste electrical and electronic
equipment aims to enable the re-use, recycling and other forms
of recovery of waste equipment as well as to prevent negative
effects for the environment and human health caused by the
disposal of hazardous substances potentially contained in the
equipment.
In the European Union, batteries and accumulators must not be
treated as domestic waste, but must be disposed of
professionally in accordance with Directive 2006/66/EC of the
European Parliament and of the Council of 6September 2006
on batteries and accumulators. Please dispose of batteries and
accumulators according to the relevant legal requirements.

Trotec GmbH
Grebbener Str. 7
D-52525 Heinsberg
+49 2452 962-400
+49 2452 962-200
www.trotec.com
Table of contents
Other Trotec Measuring Instrument manuals

Trotec
Trotec PDR 908 HP User manual

Trotec
Trotec BE 38 User manual

Trotec
Trotec BP17 User manual

Trotec
Trotec BE42 User manual

Trotec
Trotec IC085LV User manual

Trotec
Trotec TD120 User manual

Trotec
Trotec BC21 User manual

Trotec
Trotec BI15 User manual

Trotec
Trotec B1DL User manual

Trotec
Trotec BP21WP User manual

Trotec
Trotec BE40 User manual

Trotec
Trotec BB30 User manual

Trotec
Trotec BE20 User manual

Trotec
Trotec BP17 User manual

Trotec
Trotec BM21 User manual

Trotec
Trotec MultiMeasure BASIC User manual

Trotec
Trotec SL3000 User manual

Trotec
Trotec BZ15M User manual

Trotec
Trotec BX50 MID User manual

Trotec
Trotec ProMarker OEM User manual