Inclinometer
with two programmable switchpoints
B1N360V-Q20L60-2UP6X3-H1151/3GD
Edition • 2013-11-13T17:09:32+01:00
4 / 5 TURCK Inc. ñ 3000 Campus Drive Minneapolis, MN 55441-2656 ñ Phone: 763-553-7300 ñ Application Support: 1-800-544-7769 ñ Fax 763-553-0708 ñ www.turck.com
Operating manual
Intended use
This device fulfills the directive 94/9/EC and is suited for use in explosion hazardous areas acc. to EN60079-0:2009, EN60079-15:2010 and
EN60079-31:2009.
In order to ensure correct operation to the intended purpose it is required to observe the national regulations and directives.
For use in explosion hazardous areas conform to classification
II 3 G and II 3 D (Group II, Category 3 G, electrical equipment for gaseous atmospheres and category 3 D, electrical equipment for dust atmo-
spheres).
Marking (see device or technical data sheet)
Ex II 3 G Ex nA IIC T5 Gc acc .to EN 60079-0:2009 and EN 60079-15:2010 and Ex II 3 D Ex tc IIIC T85°C Dc acc. to EN 60079-0:2009 and EN
60079-31:2009
Local admissible ambient temperature
-30…+70 °C
Installation / Commissioning
These devices may only be installed, connected and operated by trained and qualified staff. Qualified staff must have knowledge of protection
classes, directives and regulations concerning electrical equipment designed for use in explosion hazardous areas.
Please verify that the classification and the marking on the device comply with the actual application conditions.
Installation and mounting instructions
Avoid static charging of cables and plastic devices. Please only clean the device with a damp cloth. Do not install the device in a dust flow and
avoid build-up of dust deposits on the device.
If the devices and the cable could be subject to mechanical damage, they must be protected accordingly. They must also be shielded against
strong electro-magnetic fields.
The pin configuration and the electrical specifications can be taken from the device marking or the technical data sheet.
In order to avoid contamination of the device, please remove possible blanking plugs of the cable glands or connectors only shortly before in-
serting the cable or opening the cable socket.
Special conditions for safe operation
For devices with M12 connectors please use the supplied safety clip SC-M12/3GD. The safety clips SC-M12/3GD are not required when using
the protective housing SG-Q20L60.
Do not disconnect the plug-in connection or cable when energised.
Please attach a warning label permanently in an appropriate fashion in close proximity to the plug-in connection with the following inscription:
Nicht unter Spannung trennen / Do not separate when energized.
The device must be protected against any kind of mechanical damage and degrading UV-radiation. On selecting the approval-relevant acces-
sories, always ensure that they are installed conform to the application.
Load voltage and operating voltage of this equipment must be provided by power supplies featuring safe isolation (IEC 60 364/ UL 508), which
ensures that the rated voltage (24 VDC +20% = 28.8 VDC) of the equipment is not exceeded by more than 40%.
service / maintenance
Repairs are not possible. The approval expires if the device is repaired or modified by a person other than the manufacturer. The most important
data from the approval are listed.
Switchpoint adjustable as NO contact counterclockwise or as NC contact clockwise
Press T1 (T2) for 5 sec.
Power LED flashing
Place the sensor in the wanted start position
Press T1 (T2) for 1 sec. to set the switch-on point
Power LED and Output 1 (2) LED flashing
Place the sensor in the wanted end position
Press T1 (T2) for 3 sec. to set the switch-off point
Power LED and Output 1 (2) LED flashing 3 sec. then steady
Teach process completed, sensor ready for operation.
Switchpoint adjustable as NO contact clockwise or as NC contact counterclockwise
Press T1 (T2) for 5 sec.
Power LED flashing
Place the sensor in the wanted start position
Press T1 (T2) for 3 sec. to set the switch-on point
Power LED and Output 1 (2) LED flashing fast
Place the sensor in the wanted end position