4.4 Specic
4.4.1 Parameters FM(X)-IM-3UP63FX
Name Index
(dec.)
Index
(hex.)
Ac-
cess
Bit-
count
Type Bit Value Description
Output type
Flow (SP1)
97 0x61 Read/
Write
8 Uint8 1 PNP 1 Switching characteristic “active
high”
2 PNP 1 Switching characteristic “active
low”
Output type
Temp (SP2)
98 0x62 Read/
Write
8 Uint8 1 PNP 2 Switching characteristic “active
high”
2 PNP 2 Switching characteristic “active
low”
Teach 100 0x64 Write 8 Uint8 1 Upper limit teach (MAX teach)
2 Lower limit teach (MIN teach)
3 Quick teach
Operating Mode 102 0x66 Read/
Write
8 Uint8 1 Quick teach mode
2 MAX/MIN trim
QuickTeach % 103 0x67 Read/
Write
8 Uint8 40 4.0 % above actual flow process value
35 3.5 % above actual flow process value
30 3.0 % above actual flow process value
25 2,5 % above actual flow process value
20 2.0 % above actual flow process value
15 1.5 % above actual flow process value
10 1.0 % above actual flow process value
5 0.5 % above actual flow process value
0 (Set current flow process value as
SP flow )
-5 0.5 % below actual flow process value
-10 1.0 % below actual flow process value
-15 1.5 % below actual flow process value
-20 2.0 % below actual flow process value
-25 2,5 % below actual flow process value
-30 3.0 % below actual flow process value
-35 3.5 % below actual flow process value
-40 4.0 % below actual flow process value
Flow rate 112 0x70 Read 16 Uint16 0…1023 Process value flow with regard to the
MAX/MIN Teach range 0 … 100 %
0 = 0 % … 1023 = 100 %
Media
temperature
113 0x71 Read 16 Int16 -50…200 Media temperature −50 … 200 °C
[1 °C steps]
Instantaneous
switchpoint (SP1)
[Bit]
128 0x80 Read 16 Uint16 0…1023 Current switchpoint flow process value
0…1023
Switchpoint
MAX/MIN Teach
(SP1) [%]
129 0x81 Read/
Write
8 Uint8 0…100 Switchpoint MAX/MIN Teach (Out 1)
0 … 100 % [1 % steps] for MAX/MIN
operation mode