manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco Fire Product
  6. •
  7. Irrigation System
  8. •
  9. Tyco Fire Product CENTRAL BVR User manual

Tyco Fire Product CENTRAL BVR User manual

fully sprinklered in accordance with the
recomendations of NFPA 13, NFPA
13D, or NFPA 13R. In the event of this
condition, consult the authorities
having jurisdiction for guidance and
approval.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
Tyco Fire Products --- www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446 --- USA
Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Model BVR
No. 4-4.0
5.4 K-factor -
Fast Response Residential
Horizontal Sidewall & Recessed Horizontal Sidewall
Glass Bulb Automatic Sprinkler
General
Description
The Central Model BVR, 5.4 K-factor
Residential Horizontal Sidewall &
Recessed Horizontal Sidewall Sprinklers
are decorative glass bulb sprinklers
designed for use in residential occupan-
cies such as homes, apartments,
dormitories, and hotels.
They are to be used in wet pipe residential
sprinkler systems for one- and two-family
dwellings and mobile homes per NFPA
13D; wet pipe residential sprinkler
systems for residential occupancies up to
and including four stories in height per
NFPA 13R; or, wet pipe sprinkler systems
for the residential portions of any occu-
pancy per NFPA 13.
The recessed version of the Model BVR
Residential Horizontal Sidewall Sprinkler is
obtained by utilizing the Model BVR
Horizontal Sidewall Sprinkler in combina-
tion with the Model BV Res./QR Re-
cessed Escutcheon Assembly. The
recessed version of the Central Model
BVR using a Model BV Res./QR Re-
cessed Escutcheon provides up to 3/8
inch (9,5 mm) of total adjustment from the
flush Horizontal Sidewall position.
Operation: The glass bulb contains a fluid
which expands when exposed to heat.
When the rated temperature is reached,
the fluid expands sufficiently to shatter the
glass bulb, which then allows the sprinkler
to activate and flow water.
WARNING
The BVR Residential Horizontal
Sidewall Sprinklers described herein
must be installed and maintained in
compliance with this document, as well
as with the applicable standards of the
National Fire Protection Association, in
addition to the standards of any other
authorities having jurisdiction. Failure
to do so may impair the integrity of
these devices.
Because of the above cited stipulations
and the varied nature of residential
type architecture, there will be some
compartment designs which cannot be
Technical
Data
CENTRAL BVR Sidewall 7-02
Residential
Horiz. Sidewall
Sprinklers
Design
Criteria
The Model BVR Horizontal Sidewall and
Recessed Horizontal Sidewall Sprinklers
are UL, ULC Listed and MEA Approved
for use in accordance with current NFPA
standards for use on wet pipe sprinkler
systems. These sprinklers have been
investigated for use under smooth flat
horizontal ceilings with slopes up to 2
inches per foot, at spacings up to 16 feet
by 20 feet, using the design requirements
found in Table 1. These sprinklers have
also been investigated for use under
smooth flat sloping ceilings with slopes up
to 8 inches per foot, at spacings up to 16
feet by 20 feet, using the design
requirements found in Table 2 & 3 as well
as the sloped ceiling "Specific Application
Design Criteria" found in Figure 1.
The Recessed Horizontal Sidewall
Sprinklers are only listed with the Series
BV Res./QR Recessed Escutcheon
Assembly.
The minimum required single and multiple
sprinkler flow rates for systems designed
to NFPA 13D or NFPA 13R occupancies
are given in Table 1, Table 2, and Table 3.
The single sprinkler flow rate is the
minimum required discharge from the
most hydraulically demanding single
sprinkler and, the multiple sprinkler flow
rate is the minimum required discharge
from each of the total number of "design
sprinklers" as specified in NFPA 13D or
NFPA 13R.
(Continued on page 2)
Sprinkler Identification Number
SIN - C3396
Approvals
UL & ULC Listed. MEA (323-98-E)
(Refer to the Design Criteria Section)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection - 1/2 inch NPT
Discharge Coefficient
K = 5.4 GPM/psi1/2 (77,9 LPM/bar1/2)
Temperature Ratings - 155°F/68°C
Finishes
Sprinkler: White Polyester, Chrome
Plated, or Natural Brass
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
The Model BVR Residential Horizontal
Sidewall Sprinkler utilizes a dezincification
resistant (DZR) bronze frame and a 3 mm
bulb. The sprinkler frame orifice is sealed
with a gasketed spring plate (Belleville
Seal) consisting of a beryllium nickel disc
spring that is sealed on both its inside and
outside edges with a TeflonTM gasket. The
compression screw is bronze, and the
deflector is brass.
SPRINKLERS FOR REPLACEMENT USE ONLY IN EXISTING SPRINKLER SYSTEMS
OBSOLETE
Design
Criteria (Cont.) Installation
The Central Model BVR Horizontal
Sidewall Sprinklers must be installed in
accordance with the following instructions:
NOTES
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of liquid
from the bulb. With the sprinkler held
horizontally, a small air bubble with an
approximate diameter of 1/16 inch should
be present.
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7 to 14
ft.lbs. (9,5 to 19,0 Nm). A maximum of 21
ft.lbs. (28,5 Nm) of torque is to be used to
install 1/2 inch NPT sprinklers. Higher
levels of torque may distort the sprinkler
inlet with consequent leakage or impair-
ment of the sprinkler.
Step 1. The sprinkler must only be
installed in the sidewall position with the
centerline of the sprinkler parallel to the
ceiling and perpendicular to the wall. The
top of the deflector is to be positioned
towards the ceiling.
Step 2. After installing the BV Res./QR
Recessed Support Cup (or other accept-
able escutcheon, as applicable) over the
sprinkler pipe threads and with pipe thread
sealant applied to the pipe threads, hand
TIA 99-1 (Tentative Interim Ammendment)
with an effective date of May 22, 2000
states that the minimum required
discharge from each of the "design
sprinklers" for systems designed to NFPA
13 must be calculated based on delivering
a minimum design density of 0.1 gpm/sq.
ft. for each of the listed coverage areas
shown in Table 1, Table 2, or Table 3.
Consult the authority having jurisdiction
regarding the application of this TIA to the
currently adopted NFPA 13.
Model BVR Residential Horizontal
Sidewall and Recessed Horizontal
Sidewall Sprinklers must be installed using
the obstruction and minimum distance
between sprinkler criteria for extended
coverage sidewall sprinklers found the
current edition of NFPA 13.
NOTES
Residential Fire Sprinkler Systems
should only be designed and installed
by those competent and completely
familiar with automatic sprinkler
system design, installation procedures,
and techniques.
The sprinkler must be secured in
position by firmly fastening the
sprinkler system piping to the
structure. If the sprinkler is not
properly secured in position, reaction
forces resulting from sprinkler
operation could alter its orientation and
its water distribution pattern. The
sprinkler escutcheon cannot be used
to hold the sprinkler in position.
Several criteria may apply to the
installation and usage of each
sprinkler. Consequently, it is
recommended that the sprinkler
system designer review and develop a
working understanding of the
complete list of criteria prior to
initiating the design of the sprinkler
system.
Questions concerning sprinkler
installation and usage criteria, which
are not covered by the following
instructions, should be submitted to
Central Sprinkler. Include sketches and
technical details as appropriate.
In some instances, the requirements of
this document may concern
specifications which are more
stringent and which take precedence
over those specified in NFPA 13, NFPA
13D, NFPA 13R, or by the authority
having jurisdiction.
tighten the sprinkler into the sprinkler
fitting.
Step 3. Wrench tighten the sprinkler using
only a BV Sprinkler Wrench (1099). The
wrench recess of the BV Sprinkler Wrench
is to be applied to the sprinkler wrench
flats (Ref Figure 3).
Step 4. For Recessed Sidewall Sprinkler
Applications, a Protective Cap is available
which helps to prevent damage to the
sprinkler during ceiling/wall installation
and/or during application of the finish
coating of the ceiling/wall. Place the
Protective Cap over the Recessed
Support Cup and push it sideways until it
bottoms out against the sprinkler deflector.
NOTE
As long as the Protective Cap remains in
place, the system is considered to be "Out
of Service"
Step 5. After the ceiling/wall has been
completed , remove and discard the
Protective Cap. If the Sprinkler has been
damaged, replace the entire Sprinkler
assembly. Do not attempt to modify or
repair a damaged sprinkler.
Step 6. Push the outer ring of the
Recessed Escutcheon over the Re-
cessed Support Cup. If the Recessed
Escutcheon cannot be engaged with the
Support Cup or the Recessed Escutcheon
cannot be engaged sufficiently to contact
the wall, the Sprinkler Fitting must be
repositioned.
Coverage Area Minimum Design Flow (Pressure)
Two or More
Width Throw One Sprinkler Sprinklers
12'
(or less)
12'
(or less)
20 GPM (13.7 psi) 18 GPM (11.1 psi)
(3,7m) (3,7m) 75,8 LPM (0,94 bar) 68,2 LPM (0,77 bar)
16' 18' 22 GPM (16.6 psi) 20 GPM (13.7 psi)
(4,9m) (5,5m) 83,4 LPM (1,14 bar) 75,8 LPM (0,94 bar)
16' 20' 30 GPM (30.9 psi) 25 GPM (21.4 psi)
(4,9m) (6,1m) 113,7 LPM (2,13 bar) 94,8 LPM (1,48 bar)
Table 1 - BVR S/W 1/2" Residential Sidewall Sprinkler Design Requirements
Smooth, Flat, Ceiling with a Max. 2:12 Slope
4"
(101.6 mm)
to 6"
(152.4 mm)
below the ceiling.
Coverage Area Minimum Design Flow (Pressure)
Two or More
Width Throw One Sprinkler Sprinklers
16'
(or less)
16'
(or less)
22 GPM (16.6 psi) 20 GPM (13.7 psi)
(4,9m) (4,9m) 83,4 LPM (1,14 bar) 75,8 LPM (0,94 bar)
16' 18' 22 GPM (16.6 psi) 20 GPM (13.7 psi)
(4,9m) (5,5m) 83,4 LPM (1,14 bar) 75,8 LPM (0,94 bar)
16' 20' 30 GPM (30.9 psi) 25 GPM (21.4 psi)
(4,9m) (6,1m) 113,7 LPM (2,13 bar) 94,8 LPM (1,48 bar)
4"
(101.6 mm)
to 6"
(152.4 mm)
below the ceiling.
Table 2 - BVR S/W 1/2" Residential Sidewall Sprinkler Design Requirements
Smooth, Flat, Ceiling with a Max. 8:12 Slope with Sprinkler Located at Peak
Table 3 - BVR S/W 1/2" Residential Sidewall Sprinkler Design Requirements
Smooth, Flat, Ceiling with a Max. 8:12 Slope with Sprinkler Located Along
Sloping Wall
Coverage Area Minimum Design Flow (Pressure)
Two or More
Width Throw One Sprinkler Sprinklers
16'
(or less)
18'
(or less)
22 GPM (16.6 psi) 20 GPM (13.7 psi)
(4,9m) (5,5m) 83,4 LPM (1,14 bar) 75,8 LPM (0,94 bar)
4"
(101.6 mm)
to 6"
(152.4 mm)
below the ceiling.
OBSOLETE
Figure 1 - BVR Sidewall Sloped Ceiling Design Guidelines
Sidewall Located at the Peak
• Locate sidewalls at the peak with their deflectors parallel to
the slope.
• Number of heads to be calculated shall conform to the
appropriate NFPA standard being used for design.
• Maximum number of sidewalls at the peak is unlimited.
• Cathedral ceiling applications: An 8" minimum beam or
lintel is required at the peak.
• a: minimum: 4"
(101,6 mm)
maximum: one-half the maximum calculated spacing
• b: minimum: 8'-0"
(2,4 m)
maximum: 16'-0"
(4,9 m)
Sidewalls Located Along the Slope
• Up to three sidewalls along each side of the slope can be located with their deflectors parallel to the slope.
• All hydraulic criteria per the appropriate NFPA standard applies.
Note: If three sidewalls are present along one wall of one slope, all three must be calculated regardless of the NFPA
standard being used for design.
• Maximum number of sprinklers per compartment is six.
• For cathedral ceiling applications, an 8" minimum beam or lintel is required at the peak.
• a: minimum: 4"
(101,6 mm)
maximum: one-half the maximum calculated spacing
36' MAX.
a
a
bb
20' MAX.
MEASURED
ALONG SLOPE
48' MAX.
8'-0"
MIN.
D = MAXIMUM
SLOPE
8:12 (33.7O)
D
D
MAXIMUM 8'-0" OPENING
ALLOWED IN PERIMETER WALLS
D = MAXIMUM
SLOPE
8:12 (33.7O)
abb
MEASURED
ALONG SLOPE
18' MAX.
48' MAX.
MAXIMUM 8'-0" OPENING
ALLOWED IN PERIMETER WALLS
ab
a
b
MEASURED
ALONG SLOPE
D
MAXIMUM 8'-0" OPENING
ALLOWED IN PERIMETER WALLS
a
• b: minimum: 8'-0"
(2,4 m)
maximum: 16'-0"
(4,9 m)
Figure 2 - Model BVR Recessed Sidewall
(bottom view)
2-1/2" (63,5mm)
3/4" Max.
(19,1mm)
3/8" Min.
(9,5mm)
Face of
Reducing
Coupling
1-13/16" (46,0mm) Max.
Model BV Res./QR
Recessed Escutcheon
2-7/8" (73,0mm)
Support
Cup
Face of Wall
1-7/16" (36,5mm) Min.
1-1/2" (38,1mm)
Minimum Hole
in Wall is
2" (50,8mm),
Maximum is
2-1/2" (63,5mm)
1-13/16" (46,0mm)
Note: Central's Model 65 or 401 escutcheons may be used. When
using Central's Model 65 ceiling escutcheon, the face of the
reducing coupling should be 1/8"(3,2mm) ±1/16"(1,6mm)
beyond wall line.
Figure 3 - Model BVR Sidewall
WRENCH
FLAT
ELEVATION VIEW
TOP OF DEFLECTOR
7/16"
(11,1 mm)
2-1/2 (63,5 mm)
1/2" NPT
7/16" (11,1 mm) MAKE-IN
OBSOLETE
replaced. Sprinklers that have been
exposed to corrosive products of
combustion, but have not operated,
should be completely cleaned by
wiping the sprinkler with a cloth or by
brushing it with a soft bristle brush.
Care must be exercised to avoid
damage - before, during, and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/
slippage, or the like, must be re-
placed. Also, replace any sprinkler
that has a cracked bulb or that has
lost liquid from its bulb (Ref. Installa-
tion Section).
The Central Model BVR Horizontal
Sidewall Sprinklers must only be
replaced with sidewall sprinklers which
are listed for residential fire protection
service and which have the same
nominal K-factor, the same coverage
area, and the same or lower flow ratings
(as indicated under "Design Criteria").
When remodeling, such as by adding
false beams or light fixtures or changing
the location of compartment walls, first
verify that the new construction will not
violate the installation requirements
stated under WARNINGS. Alter the new
construction and/or the sprinkler system
to suit the requirements of this docu-
ment.
The owner is responsible for the
inspection, testing, and maintenance
of their fire protection system and
devices in compliance with this
document, as well as with the appli-
cable standards of the National Fire
Protection Association (e.g., NFPA
25), in addition to the standards of any
other authorities having jurisdiction.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.
Printed in U.S.A. 7-02
Flow Control
Tyco Fire

Products
The Central Model BVR Horizontal
Sidewall Sprinklers must be maintained
and serviced in accordance with the
following instructions:
NOTES
Wet pipe sprinkler systems must be
maintained at a minimum tempera-
ture of 40
°
F/4
°
C to prevent freezing
and bursting of the pipe and/or
sprinklers.
Automatic sprinklers are not to be
tested with a heat source. Operation
of the heat responsive element (bulb)
can result.
Absence of an Escutcheon Plate may
delay the time to sprinkler operation
in a fire situation.
Before closing a fire protection
system main control valve for
maintenance work on the fire
protection system which it controls,
permission to shut down the affected
fire protection system must be
obtained from the proper authorities
and all personnel who may be
affected by this action must be
notified.
Do NOT enclose sprinklers within
drapes, curtains, or valances.
Do NOT hang anything from the
sprinklers.
Do NOT cleanse the sprinklers with
soap and water, detergents, ammo-
nia, cleaning fluids, or other chemi-
cals. Remove dust, lint, cobwebs,
cocoons, insects, and larvae by
gently brushing with a feather duster
or gently vacuuming with a soft
bristle (i.e., dusting) brush attach-
ment.
Exercise suitable safety precautions
in the use and storage of highly
flammable materials. The rapid rate
of fire development and spread of
which can be caused by such
materials can reduce the ability of
the sprinkler system to aid in the
control of a fire in which they are
involved.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
shipped or stored where its tempera-
ture will exceed 100°F/38°C and they
must never be painted, plated, coated,
or otherwise altered after leaving the
factory. Modified sprinklers must be
Care &
Maintenance
Ordering Information: When placing
an order, indicate the full product
name. Please specify the quantity,
model, style, orifice size, temperature
rating, type of finish or coating, and
sprinkler wrench. Refer to price list for
complete listing of Part Numbers.
Teflon is a trademark of the DuPont Corp.
Ordering
Information
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and
workmanship when paid for and
properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by Tyco Fire
Products. No warranty is given for
products or components manufac-
tured by companies not affiliated by
Limited
Warranty
ownership with Tyco Fire Products or
for products and components which
have been subject to misuse, im-
proper installation, corrosion, or which
have not been installed, maintained,
modified or repaired in accordance
with applicable Standards of the
National Fire Protection Association,
and/or the standards of any other
Authorities Having Jurisdiction.
Materials found by Tyco Fire Products
to be defective shall be either repaired
or replaced, at Tyco Fire Products'
sole option. Tyco Fire Products
neither assumes, nor authorizes any
person to assume for it, any other
obligation in connection with the sale
of products or parts of products. Tyco
Fire Products shall not be responsible
for sprinkler system design errors or
inaccurate or incomplete information
supplied by Buyer or Buyer's repre-
sentatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY
OR UNDER ANY OTHER LEGAL
THEORY, FOR INCIDENTAL,
INDIRECT, SPECIAL OR CONSE-
QUENTIAL DAMAGES, INCLUDING
BUT NOT LIMITED TO LABOR
CHARGES, REGARDLESS OF
WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE
POSSIBILITY OF SUCH DAMAGES,
AND IN NO EVENT SHALL TYCO
FIRE PRODUCTS' LIABILITY
EXCEED AN AMOUNT EQUAL TO
THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS
OR IMPLIED, INCLUDING WARRAN-
TIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR
PURPOSE.
OBSOLETE

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product CENTRAL ELO SW-24 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO SW-24 User manual

Tyco Fire Product STAR SIN S3400 SR User manual

Tyco Fire Product

Tyco Fire Product STAR SIN S3400 SR User manual

Tyco Fire Product D3 PROTECTOSPRAY User manual

Tyco Fire Product

Tyco Fire Product D3 PROTECTOSPRAY User manual

Tyco Fire Product Gem F685 User manual

Tyco Fire Product

Tyco Fire Product Gem F685 User manual

Tyco Fire Product Gem F892QR User manual

Tyco Fire Product

Tyco Fire Product Gem F892QR User manual

Tyco Fire Product CENTRAL 3 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL 3 User manual

Tyco Fire Product CENTRAL WS User manual

Tyco Fire Product

Tyco Fire Product CENTRAL WS User manual

Tyco Fire Product Star Luminous S170 User manual

Tyco Fire Product

Tyco Fire Product Star Luminous S170 User manual

Tyco Fire Product Star SG S180 User manual

Tyco Fire Product

Tyco Fire Product Star SG S180 User manual

Tyco Fire Product Star Celeste S140 User manual

Tyco Fire Product

Tyco Fire Product Star Celeste S140 User manual

Tyco Fire Product TY-B Series User manual

Tyco Fire Product

Tyco Fire Product TY-B Series User manual

Tyco Fire Product CENTRAL ELO-231 BVQR User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-231 BVQR User manual

Tyco Fire Product CENTRAL ESFR-25 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESFR-25 User manual

Tyco Fire Product Star DS-1 Series User manual

Tyco Fire Product

Tyco Fire Product Star DS-1 Series User manual

Tyco Fire Product DS-2 Series User manual

Tyco Fire Product

Tyco Fire Product DS-2 Series User manual

Tyco Fire Product Star SuperNova S126 User manual

Tyco Fire Product

Tyco Fire Product Star SuperNova S126 User manual

Tyco Fire Product CENTRAL BV-R1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV-R1 User manual

Tyco Fire Product Star SG300 User manual

Tyco Fire Product

Tyco Fire Product Star SG300 User manual

Tyco Fire Product Star LD-2 User manual

Tyco Fire Product

Tyco Fire Product Star LD-2 User manual

Tyco Fire Product CENTRAL ESFR-17 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESFR-17 User manual

Tyco Fire Product CENTRAL S176 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL S176 User manual

Tyco Fire Product TFR MAX User manual

Tyco Fire Product

Tyco Fire Product TFR MAX User manual

Tyco Fire Product TY-QRF User manual

Tyco Fire Product

Tyco Fire Product TY-QRF User manual

Tyco Fire Product EC-HS User manual

Tyco Fire Product

Tyco Fire Product EC-HS User manual

Popular Irrigation System manuals by other brands

Rain Bird LNDDRIPKIT installation instructions

Rain Bird

Rain Bird LNDDRIPKIT installation instructions

Reliable N252 EC manual

Reliable

Reliable N252 EC manual

Tyco Power Pro Series user manual

Tyco

Tyco Power Pro Series user manual

Toro T5 Series quick start guide

Toro

Toro T5 Series quick start guide

Autopot SmartPot 24 XL Set-up guidelines

Autopot

Autopot SmartPot 24 XL Set-up guidelines

Viking FREEDOM VK460 Technical data

Viking

Viking FREEDOM VK460 Technical data

Viking VK192 Technical data

Viking

Viking VK192 Technical data

Gardena OS 140 operating instructions

Gardena

Gardena OS 140 operating instructions

Johnson Controls tyco EC-8C Series manual

Johnson Controls

Johnson Controls tyco EC-8C Series manual

Autopot easy2grow 16 Set-up guidelines

Autopot

Autopot easy2grow 16 Set-up guidelines

Tyco ESFR-17 quick start guide

Tyco

Tyco ESFR-17 quick start guide

Tyco TY-FRB Series quick start guide

Tyco

Tyco TY-FRB Series quick start guide

Reliable G6-80 Bulletin

Reliable

Reliable G6-80 Bulletin

Rain Bird Traveler TR Series Operation guide

Rain Bird

Rain Bird Traveler TR Series Operation guide

CENTRAL GB manual

CENTRAL

CENTRAL GB manual

G-Tools G-kit Bonanza 1m2 manual

G-Tools

G-Tools G-kit Bonanza 1m2 manual

Reliable GFR VELO–ECOH Bulletin

Reliable

Reliable GFR VELO–ECOH Bulletin

Tyco Grinnell F692 DESIGNER manual

Tyco

Tyco Grinnell F692 DESIGNER manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.