Tyco Fire Product Star Galaxy SG User manual

Std. Response - Std. Coverage
Upright, Pendent, and
Recessed Pendent Sprinklers
Star Galaxy™ SG, K=8.0, 3/4" NPT
GENERAL DESCRIPTION
The Star Galaxy SG, 8.0 K-Factor, Upright, Pendent, and
Recessed Pendent Sprinklers are standard response -
standard coverage, decorative glass bulb type spray
sprinklers designed for use in light, ordinary, or extra haz-
ard, commercial occupancies such as banks, hotels,
shopping malls, factories, refineries, chemical plants, etc.
The recessed version of the Star Galaxy SG, intended for
use in areas with a finished ceiling, uses a two-piece
#2086 Recessed Escutcheon. The #2086 provides 1/2
inch (12,7 mm) of recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the flush pendent posi-
tion. The adjustment provided by the Recessed Escutch-
eon reduces the accuracy to which the fixed pipe drops to
the sprinklers must be cut.
Wax and lead coatings are utilized to extend the life of
copper alloy sprinklers beyond that which would other-
wise be obtained when exposed to corrosive atmos-
pheres. Although wax and lead coated sprinklers have
passed the standard corrosion tests of the applicable ap-
proval agencies, the testing is not representative of all
possible corrosive atmospheres. Consequently, it is rec-
ommended that the end user be consulted with respect to
the suitability of these corrosion resistant coatings for any
given corrosive environment. The effects of ambient tem-
perature, concentration of chemicals, and gas/chemical
velocity, should be considered, as a minimum, along with
the corrosive nature of the chemical to which the sprin-
klers will be exposed.
An intermediate level version of the Star Galaxy SG Pen-
dent Sprinkler can be obtained by utilizing the Star Gal-
axy SG Pendent Sprinkler (SIN S2811) in combination
with the Model S11 Shield described in Product Data
Sheet 1-4.2.40.
WARNINGS
The Star Galaxy SG Sprinklers described herein must be
installed and maintained in compliance with this docu-
ment, as well as with the applicable standards of the Na-
tional Fire Protection Association, in addition to the stand-
ards of any other authorities having jurisdiction. Failure to
do so may impair the integrity of these devices.
The owner is responsible for maintaining their fire protec-
tion system and devices in proper operating condition.
The installing contractor or sprinkler manufacturer should
be contacted relative to any questions.
OPERATION
The glass bulb contains a fluid which expands when ex-
posed to heat. When the rated temperature is reached,
the fluid expands sufficiently to shatter the glass bulb,
which then allows the sprinkler to activate and flow water.
TECHNICAL DATA
Approvals
UL and ULC Listed. FM, LPC, NYC Approved.
(Refer to Table A. The approvals apply only to the service
conditions indicated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
1/2 inch NPT
Discharge Coefficient
K=8.0GPM/psi
1/2 (115,2 LPM/bar1/2)
Temperature Ratings
135°F/57°C, 155°F/68°C, 175°F/79°C,
200°F/93°C, 286°F/141°C, or 360°F/182°C
(Refer to Table A)
Finishes
Sprinkler: White Polyester, Black Polyester,
Chrome Plated, Natural Brass, Wax Coated, Lead Coated,
Wax over Lead Coated (Refer to Table A)
Recessed Escutcheon: White Coated, Black Coated,
Chrome Plated, Bright Brass Plated
(Other colors are available on request.)
Physical Characteristics (Ref. Figure 1)
The Star Galaxy SG utilizes a dezincification resistant
(DZR) bronze frame, and a 5 mm diameter glass bulb.
The two-piece button assembly is brass and copper. The
gasketed spring plate consists of a beryllium nickel disc
spring that is sealed on both its inside and outside edges
with a Teflon

gasket. The compression screw is bronze,
and the deflector is brass.
DESIGN CRITERIA
The 8.0 K-Factor, Star Galaxy SG Upright, Pendent, and
Recessed Pendent Sprinklers are intended for fire protec-
tion systems designed in accordance with the standard in-
stallation rules recognized by the applicable Listing or Ap-
proval agency (e.g., UL Listing is based on NFPA 13
requirements). Only the #2086 Recessed Escutcheon de-
scribed herein is to be used for recessed installations.
SIN S2810
Upright
SIN S2811
Pendent
Shown With
#2086 Recessed
Escutcheon
† DuPont Registered Trademark
Customer Service/Sales: Tel: (800) 558-5236 • Fax: (414) 570-5010
Technical Services: Tel: (800) 381-9312 • Fax: (800) 791-5500 3-01
1-1.2.50
TYCO FIRE PRODUCTS
OBSOLETE
INSTALLATION
The 8.0 K-Factor, Star Galaxy Sprinklers must be in-
stalled in accordance with the following instructions:
NOTES
Do not install any bulb type sprinkler if the bulb is
cracked or there is a loss of liquid from the bulb. With the
sprinkler held horizontally, a small air bubble should be
present. The diameter of the air bubble is approximately
1/16 inch (1,6 mm) for the 135°F/57°C to 3/32 inch
(2,4 mm) for the 360°F/182°C temperature ratings.
A leak tight 3/4 inch NPT sprinkler joint should be ob-
tainedwithatorqueof10to20ft.lbs.(13,4to20,4Nm).
A maximum of 30 ft. lbs. (40,7 Nm) of torque may be
used to install sprinklers with 3/4 NPT connections.
Higher levels of torque may distort the sprinkler inlet with
consequent leakage or impairment of the sprinkler.
Do not attempt to make-up for insufficient adjustment in
the escutcheon plate by under- or over-tightening the
sprinkler. Readjust the position of the sprinkler fitting to
suit.
The Star Galaxy SG Pendent and Upright Sprinklers
must be installed in accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be installed on the pen-
dent position, and upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant applied to the pipe
threads, hand tighten the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the sprinkler fitting us-
ing only the W-Type 9 Sprinkler Wrench (Ref. Figure 3),
except that an 8 or 10 inch adjustable Crescent wrench is
to be used for wax coated sprinklers. With reference to
Figure 1, the W-Type 9 Sprinkler Wrench is to be applied
to the sprinkler wrenching area, and the adjustable Cres-
cent wrench is to be applied to the wrenching flanges.
When installing wax coated sprinklers with the adjustable
Crescent wrench, additional care needs to be exercised
to prevent damage to the wax coating on the sprinkler
wrenching flanges or frame arms and, consequently, ex-
posure of bare metal to the corrosive environment. The
jaws of the wrench should be opened sufficiently wide to
pass over the wrenching flanges without damaging the
wax coating. Before wrench tightening the sprinkler, the
jaws of the wrench are to be adjusted to just contact the
sprinkler wrenching flanges. After wrench tightening the
sprinkler, loosen the wrench jaws before removing the
wrench.
After installation, the sprinkler wrenching flanges and
frame arms must be inspected and the wax coating re-
touched (repaired) whenever the coating has been dam-
aged and bare metal is exposed. The wax coating on the
wrenching flanges can be retouched by gently applying a
heated 1/8 inch diameter steel rod to the areas of wax
that have been damaged, to smooth it back over areas
where bare metal is exposed.
NOTES
Only retouching of the wax coating applied to the wrench-
ing flanges and frame arms is permitted, and the retouch-
STAR SPRINKLER
Page 2 1-1.2.50
FIGURE 2
8.0 K-FACTOR, STAR GALAXY SG PENDENT
SPRINKLER WITH #2086 RECESSED ESCUTCHEON
FIGURE 1
8.0 K-FACTOR, STAR GALAXY SG
STANDARD RESPONSE
PENDENT AND UPRIGHT SPRINKLERS
SPRINKLER
FACE OF
FITTING
SURFACE
MOUNTING
1/8"
(3.2 mm)
7/8" (22.2 mm)
1-3/8" (34.9 mm)
1/4" (6.4 mm)
3/4" (19.1 mm)
5/8±1/4"
(15.9±6.4 mm)
CLOSURE
PLATE
MOUNTING
SG
(57.2 mm)
2-1/4" DIA.
(73.0 mm)
2-7
/
8" DIA.
2-3/8"
(60.3 mm)
(41.3 mm)
1-5/8"
AREA
WRENCHING
WRENCHING
FLANGES
3/4" NPT
1/2" (12.7 mm)
NOMINAL MAKE-IN
ESCUTCHEON PLATE
SEATING SURFACE
WREN
C
H
RECESS
WRENCH
RECESS
FIGURE 3
W-TYPE 9 (#1849) SPRINKLER WRENCH
AND
W-TYPE 10 (#1948) RECESSED SPRINKLER WRENCH
#1849
#1948
OBSOLETE
ing is to be performed only at the time of the initial sprin-
kler installation.
The steel rod should be heated only to the point at which
it can begin to melt the wax, and appropriate precautions
need to be taken, when handling the heated rod, in order
to prevent the installer from being burned.
If attempts to retouch the wax coating with complete cov-
erage are unsuccessful, additional wax can be ordered in
the form of a wax stick (the end of which is color coded).
Only the correct color coded wax is to be used, and re-
touching of wrenching flanges and frame arms is only per-
mitted at the time of initial sprinkler installation. With the
steel rod heated as previously described, touch the rod to
the area requiring additional wax with the rod angled
downward, and then touch the wax stick to the rod ap-
proximately one-half inch away from the area requiring re-
touching. The wax will melt and run down onto the sprin-
kler.
The Star Galaxy SG Recessed Pendent Sprinklers
must be installed in accordance with the following instruc-
tions.
Step A. After installing the #2086 Mounting Plate over
the sprinkler threads and with pipe thread sealant applied
to the pipe threads, hand tighten the sprinkler into the
sprinkler fitting.
Step B. Tighten the sprinkler into the sprinkler fitting us-
ing only the W-Type 10 Recessed Sprinkler Wrench (Ref.
Figure 3). With reference to Figure 1, the W-Type 10 Re-
cessed Sprinkler Wrench is to be applied to the sprinkler
wrenching flanges.
Step C. After the ceiling has been installed or the finish
coat has been applied, slide on the #2086 Closure over
the Star Galaxy SG Sprinkler and push the Closure over
the Mounting Plate until its flange comes in contact with
the ceiling.
STAR SPRINKLER
1-1.2.50 Page 3
SPRINKLER FINISH
Temperature
Rating
Bulb
Liquid Code
Natural
Brass
Chrome
Plated
Wax
Coated
135°F/57°C
155°F/68°C
175°F/79°C
Red
Yellow
Orange
Pendent (S2811) and Upright (S2810)
Notes:
1. Listed by Underwriters Laboratories, Inc.
2. Listed by Underwriters’ Laboratories of Canada.
3. Approved by Factory Mutual Research Corporation.
4. Approved by Factory Mutual Research Corporation. (FM limits recessed sprinklers to light and ordinary hazards, and recessed
sprinklers used for ordinary hazards are limited to wet pipe systems or preaction systems qualifying as wet pipe systems.)
5. Approved by the Loss Prevention Council (United Kingdom)
6. Approved by the City of New York under MEA 395-91-M.
** 150°F/66°C Maximum Ceiling Temperature.
TABLE A
LABORATORY LISTINGS AND APPROVALS
Wax Over
Lead Coated
200°F/93°C Green
286°F/141°C Blue
Lead
Coated
Polyester
Coated
(All Colors)
SPRINKLER FINISH
Recessed (S2811) With #2086 Escutcheon
Temperature
Rating
Bulb
Liquid Code
Natural
Brass
Chrome
Plated
Polyester
Coated
(All Colors)
1, 2, 4, 5, 6
1, 2, 3, 5, 6
N/A
1, 2, 3
1, 2, 3
1**, 2**1**, 2**, 3**
1, 2, 3
360°F/182°C Mauve
135°F/57°C Orange
155°F/68°C
175°F/79°C
Red
Yellow
200°F/93°C Green
1, 2, 6
OBSOLETE
CARE AND MAINTENANCE
The Star Galaxy SG Sprinklers must be maintained and
serviced in accordance with the following instructions:
NOTE
Before closing a fire protection system main control valve
for maintenance work on the fire protection system which
it controls, permission to shut down the affected fire pro-
tection systems must be obtained from the proper authori-
ties and all personnel who may be affected by this action
must be notified.
Absence of an escutcheon, which is used to cover a clear-
ance hole, may delay the time to sprinkler operation in a
fire situation.
Sprinklers which are found to be leaking or exhibiting vis-
ible signs of corrosion must be replaced.
Automatic sprinklers must never be shipped or stored
where their temperature will exceed 100°F/38°C and they
must never be painted, plated, coated, or otherwise al-
tered after leaving the factory. Modified sprinklers must
be replaced. Sprinklers that have been exposed to corro-
sive products of combustion, but have not operated,
should be replaced if they cannot be completely cleaned
by wiping the sprinkler with a cloth or by brushing it with a
soft bristle brush.
Care must be exercised to avoid damage to the sprinklers
— before, during, and after installation. Sprinklers dam-
aged by dropping, striking, wrench twist/slippage or the
like, must be replaced. Also, replace any sprinkler that
has a cracked bulb or that has lost liquid from its bulb
(ref. Installation Section Note).
Frequent visual inspections are recommended to be in-
itially performed for wax and/or lead coated sprinklers, af-
ter the installation has been completed, to verify the integ-
rity of the wax and/or lead coating. Thereafter, annual
inspections per NFPA 25 should suffice; however, instead
of inspecting from the floor level, a random sampling of
close-up visual inspections should be made, so as to bet-
ter determine the exact sprinkler condition and the long
term integrity of the wax and/or lead coating, as it may be
affected by the corrosive conditions present.
The owner is responsible for the inspection, testing, and
maintenance of their fire protection system and devices in
compliance with this document, as well as with the appli-
cable standards of the National Fire Protection Associa-
tion (e.g., NFPA 25), in addition to the standards of any
other authorities having jurisdiction. The installing contrac-
tor or sprinkler manufacturer should be contacted relative
to any questions.
It is recommended that automatic sprinkler systems be in-
spected, tested, and maintained by a qualified Inspection
Service.
LIMITED WARRANTY
Products manufactured by Tyco Fire Products are war-
ranted solely to the original Buyer for ten (10) years
against defects in material and workmanship when paid
for and properly installed and maintained under normal
use and service. This warranty will expire ten (10) years
from date of shipment by Tyco Fire Products. No warranty
is given for products or components manufactured by
companies not affiliated by ownership with Tyco Fire Prod-
ucts or for products and components which have been
subject to misuse, improper installation, corrosion, or
which have not been installed, maintained, modified or re-
paired in accordance with applicable Standards of the Na-
tional Fire Protection Association, and/or the standards of
any other Authorities Having Jurisdiction. Materials found
by Tyco Fire Products to be defective shall be either re-
paired or replaced, at Tyco Fire Products’ sole option.
Tyco Fire Products neither assumes, nor authorizes any
person to assume for it, any other obligation in connec-
tion with the sale of products or parts of products. Tyco
Fire Products shall not be responsible for sprinkler sys-
tem design errors or inaccurate or incomplete information
supplied by Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LI-
ABLE, IN CONTRACT, TORT, STRICT LIABILITY OR UN-
DER ANY OTHER LEGAL THEORY, FOR INCIDENTAL,
INDIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES,
INCLUDING BUT NOT LIMITED TO LABOR CHARGES,
REGARDLESS OF WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT SHALL TYCO FIRE
PRODUCTS’ LIABILITY EXCEED AN AMOUNT EQUAL
TO THE SALES PRICE.
THE FOREGOING WARRANTY IS MADE IN LIEU OF
ANY AND ALL OTHER WARRANTIES EXPRESS OR IM-
PLIED, INCLUDING WARRANTIES OF MERCHANT-
ABILITY AND FITNESS FOR A PARTICULAR PUR-
POSE.
ORDERING PROCEDURE
Please Specify:
8.0 K-Factor, Star Galaxy SG
Standard Response Upright Sprinkler (#2810)
8.0 K-Factor, Star Galaxy SG
Standard Response Pendent Sprinkler (#2811)
Recessed Escutcheon (#2086)
W-Type 9 Sprinkler Wrench (#1849)
W-Type 10 Recessed Sprinkler Wrench (#1948)
Wax Sticks (for retouching wrench damaged wax coating)
Black for 135°F (560651135)
Red for 155°F (#560651155)
Yellow for 175°F (#560651175
Blue for 200°F and 286°F (#560651286)
Each wax stick is suitable for retouching up to twenty-five
sprinklers. The wax used for 286°F sprinklers is the same
as for 200°F sprinklers, and, therefore, the 286°F sprin-
kler is limited to the same maximum ceiling temperature
as the 200°F sprinkler (i.e., 150°F).
Refer to Price List for for complete listing of Part Num-
bers with respect to temperature ratings, sprinkler fin-
ishes, recessed escutcheon finishes, etc.
STAR SPRINKLER
Page 4 1-1.2.50
7071 S. 13th Street • Suite 103
Oak Creek, WI 53154
www.starsprinkler.com
PRINTED IN U.S.A. 3-01
OBSOLETE

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product CENTRAL ELO-231 GB User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-231 GB User manual

Tyco Fire Product CENTRAL CC1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL CC1 User manual

Tyco Fire Product Star E User manual

Tyco Fire Product

Tyco Fire Product Star E User manual

Tyco Fire Product Gem F892X User manual

Tyco Fire Product

Tyco Fire Product Gem F892X User manual

Tyco Fire Product CENTRAL Royal Flush A User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Royal Flush A User manual

Tyco Fire Product DS-2 Series User manual

Tyco Fire Product

Tyco Fire Product DS-2 Series User manual

Tyco Fire Product CENTRAL LF User manual

Tyco Fire Product

Tyco Fire Product CENTRAL LF User manual

Tyco Fire Product CENTRAL S170 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL S170 User manual

Tyco Fire Product CENTRAL A-1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL A-1 User manual

Tyco Fire Product CENTRAL RFII Series User manual

Tyco Fire Product

Tyco Fire Product CENTRAL RFII Series User manual

Tyco Fire Product Star StarMax S102 User manual

Tyco Fire Product

Tyco Fire Product Star StarMax S102 User manual

Tyco Fire Product CENTRAL H-1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL H-1 User manual

Tyco Fire Product CC1 User manual

Tyco Fire Product

Tyco Fire Product CC1 User manual

Tyco Fire Product Star I-LD-2 User manual

Tyco Fire Product

Tyco Fire Product Star I-LD-2 User manual

Tyco Fire Product Star Pulsar S195 User manual

Tyco Fire Product

Tyco Fire Product Star Pulsar S195 User manual

Tyco Fire Product CENTRAL BV-EC User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV-EC User manual

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product TY-B Series User manual

Tyco Fire Product

Tyco Fire Product TY-B Series User manual

Tyco Fire Product Gem F892 User manual

Tyco Fire Product

Tyco Fire Product Gem F892 User manual

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product CENTRAL BVR-2 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BVR-2 User manual

Tyco Fire Product CENTRAL Attic BB1-17/32 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Attic BB1-17/32 User manual

Tyco Fire Product CENTRAL LD User manual

Tyco Fire Product

Tyco Fire Product CENTRAL LD User manual

Tyco Fire Product CENTRAL H User manual

Tyco Fire Product

Tyco Fire Product CENTRAL H User manual

Popular Irrigation System manuals by other brands

Tyco TY-B Series manual

Tyco

Tyco TY-B Series manual

Toro ZSERIES 570Z brochure

Toro

Toro ZSERIES 570Z brochure

OpenSprinkler OSPi user manual

OpenSprinkler

OpenSprinkler OSPi user manual

EINHELL GE-WW 5537 E Original operating instructions

EINHELL

EINHELL GE-WW 5537 E Original operating instructions

Hunter Institutional Series instructions

Hunter

Hunter Institutional Series instructions

Cellfast 52-305 user manual

Cellfast

Cellfast 52-305 user manual

Oral Care Technologies Hydro Floss Instructions for use

Oral Care Technologies

Oral Care Technologies Hydro Floss Instructions for use

Reliable F1-300 quick start guide

Reliable

Reliable F1-300 quick start guide

Irrigation-Mart KIT-GK100-RV-B quick start guide

Irrigation-Mart

Irrigation-Mart KIT-GK100-RV-B quick start guide

Tyco CC3 manual

Tyco

Tyco CC3 manual

Reliable F4FR quick start guide

Reliable

Reliable F4FR quick start guide

Valley Bender160 owner's manual

Valley

Valley Bender160 owner's manual

Reliable F1FR42 Series manual

Reliable

Reliable F1FR42 Series manual

Toro 730 Series Installation and service instructions

Toro

Toro 730 Series Installation and service instructions

Eden 97063-EDAMZ quick start guide

Eden

Eden 97063-EDAMZ quick start guide

Netafim NETBEAT user manual

Netafim

Netafim NETBEAT user manual

Johnson Controls tyco ESFR-17 manual

Johnson Controls

Johnson Controls tyco ESFR-17 manual

Reliable RFC30 LL manual

Reliable

Reliable RFC30 LL manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.