The Model A Intermediate Level Sprin-
klers
must be maintained and serviced in
accordance with the following instructions.
NOTES
Before closing a fire protection system
main control valve for maintenance work
on the fire protection system it controls,
permission to shut down the affected fire
protection systems must be obtained from
the proper authorities. All personnel who
may be affected by this action must be
notified.
Automatic sprinklers must never be
shipped or stored where their tempera-
tures will exceed 100°F/38°C and they
must never be painted, plated, coated or
otherwise altered after leaving the factory.
Modified or overheated sprinklers must be
replaced.
Care must be exercised to avoid damage
- before, during, and after installation.
Sprinklers damaged by dropping, striking,
wrench twist/slippage, or the like, must be
replaced.
Frequent visual inspections are recom-
mended to be initially performed for wax
and/or lead coated sprinklers, after the
installation has been completed, to verify
the integrity of the wax and/or lead
coating. Thereafter, annual inspections
per NFPA 25 should suffice; however,
instead of inspecting from the floor level, a
random sampling of close-up visual
inspections should be made, so as to
better determine the exact sprinkler
condition and the long term integrity of the
wax and/or lead coating, as it may be
affected by the corrosive conditions
present.
The owner is responsible for the inspec-
tion, testing, and maintenance of their fire
protection system and devices in
compliance with this document, as well as
with the applicable standards of the
National Fire Protection Association (e.g.,
NFPA 25), in addition to the standards of
any other authorities having jurisdiction.
The installing contractor or sprinkler
manufacturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspection
Service.
Care &
Maintenance
Installation
(Cont.)
Pendent Sprinklers
Step 1. Pendent sprinklers must be
installed only in the pendent position. The
deflector is to be parallel to the ceiling,
roof, or mounting surface, as applicable.
Step 2. With pipe thread sealant applied
to the pipe threads, hand tighten the
sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the Universal
Sprinkler Wrench (Ref. Fig. 6). The
Universal Sprinkler Wrench is to be
applied to the wrench flats only.
Pendent Sprinkler Created using the
WS-2 Water Shield
Step 1. Pendent sprinklers must be
installed only in the pendent position. The
deflector is to be parallel to the ceiling,
roof, or mounting surface, as applicable.
Step 2. Thread the WS-2 Water Shield
onto the sprinkler threads with the
stamped marking toward the deflector and
just to the end of the threads. There
should be an 1/8" gap between the plate
and the Sprinkler Wrench Flat.
Step 3. With pipe thread sealant applied
to the pipe threads, hand tighten the
sprinkler into the sprinkler fitting.
Step 4. Tighten the sprinkler into the
sprinkler fitting using only the Combination
Wrench (Ref. Fig. 5), except that an 8 or
10 inch adjustable Crescent wrench is to
be used for wax coated sprinklers. Both
the Combination Wrench and the
adjustable Crescent wrench are to be
applied to the wrench flats only.
Step 5. Rotate the WS-2 Water Shield
clockwise (looking up) so that it engages
with the sprinkler threads.
Head Guards
Step 1. After the sprinkler has been
installed, gently spread the two base
sections of the G-2 or WSG-2 Head
Guard and slide the guard around the
sprinkler head so the base of the guard is
located between the sprinkler threads and
the wrench flats of the sprinkler.
Step 2. Fasten the two horizontal retaining
clips in place, over the proper vertical rib of
the guard. Make sure this action results in
a tight fit between the clip and the rib. If
not, bend the clip slightly and repeat the
procedure until a tight fit is obtained.
Step 3. If installing the G-2 Head Guard
on a pendent sprinkler with the WS-2
Water Shield, turn the water shield
clockwise on the sprinkler thread until it
"bottoms out" against the base of the wire
guard.
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years against
defects in material and workmanship
when paid for and properly installed and
maintained under normal use and service.
This warranty will expire ten (10) years
from date of shipment by Tyco Fire
Products. No warranty is given for
products or components manufactured by
companies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject to
misuse, improper installation, corrosion, or
which have not been installed, maintained,
modified or repaired in accordance with
applicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities Having
Jurisdiction. Materials found by Tyco Fire
Products to be defective shall be either
repaired or replaced, at Tyco Fire
Products' sole option. Tyco Fire Products
neither assumes, nor authorizes any
person to assume for it, any other
obligation in connection with the sale of
products or parts of products. Tyco Fire
Products shall not be responsible for
sprinkler system design errors or inaccu-
rate or incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THEORY,
FOR INCIDENTAL, INDIRECT, SPECIAL
OR CONSEQUENTIAL DAMAGES,
INCLUDING BUT NOT LIMITED TO
LABOR CHARGES, REGARDLESS OF
WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE POSSI-
BILITY OF SUCH DAMAGES, AND IN
NO EVENT SHALL TYCO FIRE PROD-
UCTS' LIABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR PURPOSE.
Limited
Warranty
Ordering Information: When placing an
order, indicate the full product name.
Please specify the quantity, model, style,
orifice size, temperature rating, type of
finish or coating, and sprinkler wrench.
Refer to price list for complete listing of
Part Numbers.