General
Description
TheSeriesTY-B,5.6K-factor,Hori-
zontal and Vertical Sidewall Sprinklers
described in this data sheet are stand-
ard response - standard coverage,
decorative 5 mm glass bulb type spray
sprinklers designed for use in light and
ordinaryhazard,commercialoccupan-
cies such as banks, hotels, shopping
malls, etc. They are designed for in-
stallation along a wall or the side of a
beam and just beneath a smooth ceil-
ing. Sidewall sprinklers are commonly
used instead of pendent or upright
sprinklers due to aesthetics or building
construction considerations, where
piping across the ceiling is not desir-
able.
The recessed version of the Series
TY-B Horizontal Sidewall Sprinkler is
intended for use in areas with a fin-
ished wall. Ituses a two-piece Style10
Recessed Escutcheon. The Recessed
Escutcheon provides 1/2 inch (12,7
mm) of recessed adjustment or up to
3/4 inch (19,1 mm) of total adjustment
from the flush sidewall position. The
adjustment provided by the Recessed
Escutcheon reduces the accuracy to
which the fixed pipe nipples to the
sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tantcoatedsprinklershave passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect tothe suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemicaltowhichthe sprinklerswill be
exposed.
WARNINGS
The Series TY-B Sprinklers described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the
standards ofany other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY3351 - Horizontal
TY3451 - Vertical
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A for complete ap-
proval information including corrosion
resistant status)
Maximum Working Pressure
RefertoTableB.
Discharge Coefficient
K=5.6GPM/psi
1/2 (80,6 LPM/bar1/2)
Temperature Ratings
RefertoTableA.
Finishes
Sprinkler: Refer to Table A.
Recessed Escutcheon: White Coated,
Chrome Plated, and Brass Plated.
Series TY-B — 5.6 K-factor
Horizontal and Vertical Sidewall Sprinklers
Standard Response, Standard Coverage
Page 1 of 6 TFP161
APRIL, 2006
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
tooperatein afire situationor cause
it to operate prematurely.