Tyco ELO-231B Series User manual

http://www.tyco-reproducts.com
Page 1 of 6 MArch, 2007 TFP342_EN
General
Description
The 160 K-factor, Series ELO-231B, Standard
Response, Standard Coverage, Upright and
Pendent Sprinklers (Ref. Figure 1) are auto-
matic sprinklers of the frangible bulb type.
They are “standard response - spray sprin-
klers” that produce a hemispherical water
distribution pattern below the deector.
The K160, ELO-231B Sprinklers were sub-
jected to full scale, high-piled storage re
tests to qualify their use in lieu of 80 or 115
K-factor standard spray sprinklers for the
protection of high-piled storage.
Higher ow rates can be achieved at much
lower pressures with the K160, ELO-231B
Sprinklers — making their use highly ad-
vantageous in high density applications,
such as the protection of high-piled stor-
age.
Wax or lead coatings can be used to extend
the life of the copper alloy components
used in Series ELO-231B sprinklers beyond
that which would otherwise be obtained
when exposed to corrosive atmospheres.
Although wax, lead, and polyester coated
sprinklers have passed the standard cor-
rosion tests of the applicable approval
agencies, the testing is not representative
of all possible corrosive atmospheres. Con-
sequently, it is recommended that the end
user be consulted with respect to the suit-
ability of these corrosion resistant coatings
for any given corrosive environment. The
eects of ambient temperature, concentra-
tionofchemicals,andgas/chemicalvelocity,
should be considered, as a minimum, along
with the corrosive nature of the chemical to
which the sprinklers will be exposed.
An upright intermediate level version of the
Series ELO-231B Sprinklers for in-rack ap-
plications can be obtained by utilizing the
Series ELO-231B Upright Sprinkler with the
WSG-2 Guard & Shield, and a pendent in-
termediate level version of the Series ELO-
231B Sprinklers can be obtained by utiliz-
ing the Series ELO-231B Pendent Sprinkler
with the WS-2 Shield. If there is a possibility
of the pendent intermediate level version
being exposed to mechanical damage, a G-
2 Guard can be added.
WARNINGS
The K160, Series ELO-231B Upright and Pen-
dent Sprinklers described herein must be in-
stalled and maintained in compliance with
this document, as well as with the applicable
standards of the National Fire Protection As-
sociation, in addition to the standards of any
other authorities having jurisdiction. Failure
to do so may impair the performance of
these devices.
The owner is responsible for maintaining their
re protection system and devices in proper
operating condition. The installing contrac-
tor or manufacturer should be contacted with
any questions.
Installation of Series ELO-231B Pendent Sprin-
klers in recessed escutcheons will void all
sprinkler warranties, as well as possibly void
the sprinkler’s Approvals and/or Listings.
IMPORTANT
Always refer to Technical Data Sheet
TFP700 for the “INSTALLER WARNING”
that provides cautions with respect to
handling and installation of sprinkler
systems and components. Improper
handling and installation can perma-
nently damage a sprinkler system or
its components and cause the sprin-
kler to fail to operate in a re situa-
tion or cause it to operate prematurely.
Series ELO-231B — 160 K-factor
Upright and Pendent Sprinklers
Standard Response, Standard Coverage
General
Description
The 11.2 K-factor, Series ELO-231B,
Standard Response, Standard Cover-
age, Upright and Pendent Sprinklers
(Ref. Figure 1) are automatic sprin-
klers of the frangible bulb type. They
are “standard response - spray sprin-
klers” that produce a hemispherical
water distribution pattern below the de-
flector.
The 11.2 K-factor, ELO-231B Sprin-
klers were subjected to full scale, high-
piled storage, fire tests to qualify their
use in lieu of 5.6 or 8.0 K-factor stand-
ard spray sprinklers for the protection
of high-piled storage.
Higher flow rates can be achieved at
much lower pressures with the 11.2
K-factor, ELO-231B Sprinklers —
making their use highly advantageous
in high density applications, such as
the protection of high-piled storage.
Wax or lead coatings can be used to
extend the life of the copper alloy com-
ponents used in Series ELO-231B
sprinklers beyond that which would
otherwise be obtained when exposed
to corrosive atmospheres. Although
wax, lead, and polyester coated sprin-
klers have passed the standard corro-
sion tests of the applicable approval
agencies, the testing is not repre-
sentative of all possible corrosive at-
mospheres. Consequently, it is recom-
mended that the end user be consulted
with respect to the suitability of these
corrosion resistant coatings for any
given corrosive environment. The ef-
fects of ambient temperature, concen-
tration of chemicals, and gas/chemical
velocity, should be considered, as a
minimum, along with the corrosive na-
ture of the chemical to which the sprin-
klers will be exposed.
An upright intermediate level version
of the Series ELO-231B Sprinklers for
in-rack applications can be obtained
by utilizing the Series ELO-231B Up-
right Sprinkler with the WSG-2 Guard
& Shield, and a pendent intermediate
level version of the Series ELO-231B
Sprinklers can be obtained by utiliz-
ing the Series ELO-231B Pendent
Sprinkler with the WS-2 Shield. If there
is a possibility of the pendent interme-
diate level version being exposed to
mechanical damage, a G-2 Guard can
be added.
WARNINGS
The 11.2 K-factor, Series ELO-231B
Upright and Pendent Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction.
Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or manufac-
turer should be contacted with any
questions.
Installation of Series ELO-231B Pen-
dent Sprinklers in recessed escutch-
eons will void all sprinkler warranties,
as well as possibly void the sprinkler’s
Approvals and/or Listings.
Series ELO-231B — 11.2 K-factor
Upright and Pendent Sprinklers
Standard Response, Standard Coverage
Page 1 of 6 TFP342
JANUARY, 2005
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 2 of 6 TFP342_EN
Model/Sprinkler
Identication
Numbers
TY5151 - Upright K160, 3/4”NPT
TY5251 - Pendent K160, 3/4”NPT
TY5851 - Upright K160, 1/2”NPT
TY5151 is a redesignation for C5151.
TY5251 is a redesignation for C5251, G1871,
and S2531.
TY5851 is a redesignation for C5851.
Technical Data
Approvals
UL and C-UL Listed. FM and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resistant
status. The approvals apply to the service
conditions indicated in the Design Criteria
section.)
Maximum Working Pressure
12,1 bar (175 psi)
Discharge Coecient
161,4 l/min.bar0,5 (11.2 usgpm/psi0,5)
Temperature Ratings
Refer to Table A
Finish
Refer to Table A
Physical Characteristics
Frame...........................................................Bronze
Cap................................................................Bronze
Sealing Assembly .................................................
................................ Beryllium Nickel w/Teon*
Bulb (5mm dia.)...........................................Glass
Compression Screw................................Bronze
Deflector.....................................................Bronze
*Registered trademark of DuPont.
Design Criteria
UL and C-UL Listing Requirements
The K160, Model ELO-231B (TY5151, TY5251
& TY5851) Sprinklers are to be installed in
accordance with NFPA 13 standard sprin-
kler position and area/density ow calcula-
tion requirements for light, ordinary, or ex-
tra hazard occupancies as well as high piled
storage occupancies (solid piled, palletized,
rack storage, bin box, and shelf storage
including but not limited to Class I-IV and
Group A plastics) with a minimum residual
(owing) pressure of 0,5 bar (7 psi) for wet
or dry pipe systems.
FM Approval Requirements
The K160, Model ELO-231B (TY5151, TY5251
& TY5851) Sprinklers are to be installed in
accordance with the applicable “control
mode density/area” guidelines provided by
Factory Mutual. (FM guidelines may dier
from UL and C-UL Listing criteria.)
SPRINKLER FINISH
TYPE TEMPERATURE BULB
LIQUID
NATURAL
BRASS
CHROME-
PLATED
LEAD
COATED
WAX
COATED
WAX OVER
LEAD
UPRIGHT
(TY5151 &
TY5851)
68°C (155°F) Red
1,2,3,4 3
93°C (200°F) Green
141°C (286°F) Blue 3 3(a)
PENDENT
(TY5251)
68°C (155°F) Red
1,2,3,4 3
93°C (200°F) Green
141°C (286°F) Blue 3 3(a)
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL Listed).
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL Listed).
3. Approved by Factory Mutual Research Corporation (FM Approved).
4. Approved by the City of New York under MEA 291-04-E.
(a). FM Approved for a maximum ceiling temperature of 66°C (150°F).
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR K160 SERIES ELO-
231B UPRIGHT AND PENDENT SPRINKLERS
(Refer to the Design Criteria Section)

TFP342_EN Page 3 of 6
the need for in-rack sprinkler protec-
tion) of cartoned or uncartoned unex-
panded Group A or B plastics, or, car-
toned expanded Group A or B plastics,
with:
•
a storage height of up to 20 feet (6,1
m);
•
a maximum ceiling height of 27 feet
(8,2 m);
•
a minimum deflector to top of stor-
age clearance of 18 inches (457
mm);
•
a minimum design density of 0.60
gpm/ft2(24,4 mm/min);
•
a minimum residual (flowing) pres-
sure of 10 psi (0,7 bar);
•
a minimum design area of 2000 ft2
(186 m2) for wet systems or 2600 ft2
(242 m2) for dry pipe systems
FM Approval
Requirements
The 11.2 K-factor, Model ELO-231B
(TY5151, TY5251 & TY5851) Sprin-
klers are to be installed in accordance
with the applicable “control mode den-
sity/area” guidelines provided by Fac-
tory Mutual. (FM guidelines may differ
from UL and C-UL Listing criteria.)
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Installation
The Series ELO-231B Sprinklers must
be installed in accordance with the fol-
lowing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 155°F/68°C to 3/32
inch (2,4 mm) for the 286°F/141°C
temperature ratings.
A leak tight 3/4 inch NPT sprinkler joint
should be obtained with a torque of 10
to 20 ft.lbs. (13,4 to 26,8 Nm). A maxi-
mum of 30 ft.lbs. (40,7 Nm) of torque
is to be used to install sprinklers with
3/4 NPT connections. A leak tight 1/2
inch NPT sprinkler joint should be ob-
tained with a torque of 7 to 14 ft.lbs.
(9,5 to 19,0 Nm). A maximum of 21 ft.
lbs. (28,5 Nm) of torque may be used
to install sprinklers with 1/2 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series ELO-231B Upright and
Pendent Sprinklers must be installed
in accordance with the following in-
structions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
3 Sprinkler Wrench (Ref. Figure 2),
except that an 8 or 10 inch adjustable
Crescent wrench is to be used for wax
coated sprinklers. With reference to
TFP342 Page 3 of 6
FIGURE 1
11.2 K-FACTOR SERIES ELO-231B
UPRIGHT - 3/4" NPT (TY5151), UPRIGHT - 1/2" NPT (TY5851), AND PENDENT - 3/4" NPT (TY5251) SPRINKLERS
"FITTIN
G S
IDE"
FITTING
TOWARDS SPRINKLER
RECESS
WRENCH
(END "A")
FIGURE 2
W-TYPE 3 SPRINKLER
WRENCH
PENDENT
TY5251
1/2" (12,7 mm)
NOMINAL MAKE-IN
7/16" (11,1 mm)
NOMINAL MAKE-IN
Temperature rating is indicated on deflector.
Pipe thread connections per ISO 7/1 can be provided on
TYP.
2-13/16"
(71,4 mm)
UPRIGHT
TY5851
special request.
**
*
UPRIGHT
TY5151
NOMINAL MAKE-IN
1/2" (12,7 mm)
**
NPT
1/2"
WRENCH
FLATS
**
RELIEF
THREAD
3/4"
NPT
Deflector
Screw
Compression
Bulb
Components:
Seal
Cap
Frame
-
4
2
6
5
4
3
CROSS
SECTION
6
5
-
-
NPT
**
3/4" 1
2
3
1
-
-
-
*
Assembly
FIGURE 1
K160 SERIES ELO-231B UPRIGHT - 3/4” NPT (TY5151), UPRIGHT - 1/2” NPT (TY5851), AND PENDENT - 3/4” NPT
(TY5251) SPRINKLERS
UPRIGHT
TY5851
WRENCH
FLATS
71 mm
(2-13/16”)
TYP.
NOMINAL MAKE-IN
12,5 mm (1/2”)
Components
1 - Frame
2 - Sealing
Assembly
3 - Cap
4 - Bulb
5 - Compression
Screw
6 - Deector *
* Temperature rating is indicated on deector.
**Pipe thread connections per ISO 7/1 can be
provided on special request.
Operation
The glass bulb contains a uid that expands
when exposed to heat.When the rated tem-
perature is reached, the uid expands su-
ciently to shatter the glass bulb, activating
the sprinkler and allowing water to ow.
Installation
The Series ELO-231B Sprinklers must be
installed in accordance with the following
instructions:
NOTES
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of liquid from
the bulb. With the sprinkler held horizontally,
a small air bubble should be present. The di-
ameter of the air bubble is approximately 1,5
mm (1/16”) for the 57°C (135°F) to 2,5 mm
(3/32”) for the 141°C (286°F) temperature rat-
ings.
A leak tight 3/4” NPT sprinkler joint should be
obtained with a torque of 13 to 27 Nm (10 to
20 ft.lbs.). A maximum of 41 Nm (30 ft.lbs.) of
torque is to be used to install sprinklers with
3/4 NPT connections. A leak tight 1/2” NPT
sprinkler joint should be obtained with a
torque of 9,5 to 19 Nm (7 to 14 ft.lbs.). A maxi-
mum of 29 Nm (21 ft. lbs.) of torque may be
used to install sprinklers with 1/2 NPT connec-
tions. Higher levels of torque may distort the
sprinkler inlet and cause leakage or impair-
ment of the sprinkler.
sprinkler, loosen the wrench jaws before
removing the wrench.
After installation, the sprinkler wrench ats
and frame arms must be inspected and the
wax coating retouched (repaired) whenev-
er the coating has been damaged and bare
metal is exposed. The wax coating on the
wrench ats can be retouched by gently
applying a heated 1/8 inch diameter (M3)
steel rod to the areas of wax that have been
damaged, to smooth it back over areas
where bare metal is exposed.
NOTES
Only retouching of the wax coating applied to
the wrench ats and frame arms is permitted,
and the retouching is to be performed only at
the time of the initial sprinkler installation.
The steel rod should be heated only to the
point at which it can begin to melt the wax,
and appropriate precautions need to be tak-
UPRIGHT
TY5151
PENDENT
TY5251
CROSS
SECTION
NOMINAL MAKE-IN
12,5 mm (1/2”)
NOMINAL MAKE-IN
11,1 mm (7/16”)
THREAD
RELIEF
the need for in-rack sprinkler protec-
tion) of cartoned or uncartoned unex-
panded Group A or B plastics, or, car-
toned expanded Group A or B plastics,
with:
•
a storage height of up to 20 feet (6,1
m);
•
a maximum ceiling height of 27 feet
(8,2 m);
•
a minimum deflector to top of stor-
age clearance of 18 inches (457
mm);
•
a minimum design density of 0.60
gpm/ft2(24,4 mm/min);
•
a minimum residual (flowing) pres-
sure of 10 psi (0,7 bar);
•
a minimum design area of 2000 ft2
(186 m2) for wet systems or 2600 ft2
(242 m2) for dry pipe systems
FM Approval
Requirements
The 11.2 K-factor, Model ELO-231B
(TY5151, TY5251 & TY5851) Sprin-
klers are to be installed in accordance
with the applicable “control mode den-
sity/area” guidelines provided by Fac-
tory Mutual. (FM guidelines may differ
from UL and C-UL Listing criteria.)
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Installation
The Series ELO-231B Sprinklers must
be installed in accordance with the fol-
lowing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 155°F/68°C to 3/32
inch (2,4 mm) for the 286°F/141°C
temperature ratings.
A leak tight 3/4 inch NPT sprinkler joint
should be obtained with a torque of 10
to 20 ft.lbs. (13,4 to 26,8 Nm). A maxi-
mum of 30 ft.lbs. (40,7 Nm) of torque
is to be used to install sprinklers with
3/4 NPT connections. A leak tight 1/2
inch NPT sprinkler joint should be ob-
tained with a torque of 7 to 14 ft.lbs.
(9,5 to 19,0 Nm). A maximum of 21 ft.
lbs. (28,5 Nm) of torque may be used
to install sprinklers with 1/2 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series ELO-231B Upright and
Pendent Sprinklers must be installed
in accordance with the following in-
structions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
3 Sprinkler Wrench (Ref. Figure 2),
except that an 8 or 10 inch adjustable
Crescent wrench is to be used for wax
coated sprinklers. With reference to
TFP342 Page 3 of 6
FIGURE 1
11.2 K-FACTOR SERIES ELO-231B
UPRIGHT - 3/4" NPT (TY5151), UPRIGHT - 1/2" NPT (TY5851), AND PENDENT - 3/4" NPT (TY5251) SPRINKLERS
"FITTIN
G S
IDE"
FITTING
TOWARDS SPRINKLER
RECESS
WRENCH
(END "A")
FIGURE 2
W-TYPE 3 SPRINKLER
WRENCH
PENDENT
TY5251
1/2" (12,7 mm)
NOMINAL MAKE-IN
7/16" (11,1 mm)
NOMINAL MAKE-IN
Temperature rating is indicated on deflector.
Pipe thread connections per ISO 7/1 can be provided on
TYP.
2-13/16"
(71,4 mm)
UPRIGHT
TY5851
special request.
**
*
UPRIGHT
TY5151
NOMINAL MAKE-IN
1/2" (12,7 mm)
**
NPT
1/2"
WRENCH
FLATS
**
RELIEF
THREAD
3/4"
NPT
Deflector
Screw
Compression
Bulb
Components:
Seal
Cap
Frame
-
4
2
6
5
4
3
CROSS
SECTION
6
5
-
-
NPT
**
3/4" 1
2
3
1
-
-
-
*
Assembly
“FITTING SIDE”
TOWARDS SPRINKLER
FITTING
WRENCH
RECESS
(END “A”)
FIGURE 2
W-TYPE 3 SPRINKLER
WRENCH
Do not attempt to make-up for insucient
adjustment in the escutcheon plate by under-
or over-tightening the sprinkler. Readjust the
position of the sprinkler tting to suit.
The Series ELO-231B Upright and Pen-
dent Sprinklers must be installed in ac-
cordance with the following instructions.
Step 1. Pendent sprinklers are to be in-
stalled in the pendent position, and upright
sprinklers are to be installed in the upright
position.
Step 2. With pipe thread sealant applied to
the pipe threads, hand tighten the sprinkler
into the sprinkler tting.
Step 3. Tighten the sprinkler into the sprin-
kler tting using only the W-Type 3 Sprin-
kler Wrench (Ref. Figure 2), except that a
200 or 250 mm (8 or 10”) adjustable Cres-
cent wrench is to be used for wax coated
sprinklers. With reference to Figure 1, the
W-Type 3 Sprinkler Wrench or the adjust-
able Crescent wrench, as applicable is to be
applied to the wrench ats.
When installing wax coated sprinklers with
the adjustable Crescent wrench, additional
care needs to be exercised to prevent dam-
age to the wax coating on the sprinkler
wrench ats or frame arms and, conse-
quently, exposure of bare metal to the cor-
rosive environment. The jaws of the wrench
should be opened suciently wide to pass
over the wrench ats without damaging
the wax coating. Before wrench tightening
the sprinkler, the jaws of the wrench are to
be adjusted to just contact the sprinkler
wrench ats. After wrench tightening the

Page 4 of 6 TFP342_EN
en, when handling the heated rod, in order to
prevent the installer from being burned.
If attempts to retouch the wax coating with
complete coverage are unsuccessful, addi-
tional wax can be ordered in the form of a wax
stick (the end of which is color coded). Only
the correct color coded wax is to be used, and
retouching of wrench ats and frame arms is
only permitted at the time of initial sprinkler
installation. With the steel rod heated as pre-
viously described, touch the rod to the area
requiring additional wax with the rod angled
downward, and then touch the wax stick to
the rod approximately one-half inch away
from the area requiring retouching. The wax
will melt and run down onto the sprinkler.
Care and
Maintenance
Series ELO-231B Sprinklers must be main-
tained and serviced in accordance with the
following instructions:
NOTES
Before closing a re protection system control
valve for maintenance work on the re pro-
tection system that it controls, permission to
shut down the aected re protection system
must be obtained from the proper authorities
and all personnel who may be aected by this
action must be notied.
Sprinklers that are found to be leaking or
exhibiting visible signs of corrosion must
be replaced.
Automatic sprinklers must never be paint-
ed, plated, coated or otherwise altered af-
ter leaving the factory. Modied sprinklers
must be replaced. Sprinklers that have
been exposed to corrosive products of
combustion, but have not operated, should
be replaced if they cannot be completely
cleaned by wiping the sprinkler with a cloth
or by brushing it with a soft bristle brush.
Care must be exercised to avoid damage to
the sprinklers — before, during, and after
installation. Sprinklers damaged by drop-
ping, striking, wrench twist/slippage, or
the like, must be replaced. Also, replace any
sprinkler that has a cracked bulb or that has
lost liquid from its bulb (ref. Installation Sec-
tion Note).
Frequent visual inspections are recom-
mended to be initially performed for cor-
rosion resistant sprinklers, after the installa-
tion has been completed, to verify the long
term potential integrity of the sprinkler
coatings. Thereafter, annual inspections per
NFPA 25 should suce; however, instead of
inspecting from the oor level, a random
sampling of close-up visual inspections
should be made, so as to better determine
the exact sprinkler condition and the long
term integrity of the corrosion resistant
coating, as it may be aected by the corro-
sive conditions present.
The owner is responsible for the inspection,
testing, and maintenance of their re pro-
tection system and devices in compliance
with this document, as well as with the
applicable standards of the National Fire
Protection Association (e.g. NFPA 25), in ad-
dition to the standards of any other author-
ities having jurisdiction. The installing con-
tractor or sprinkler manufacturer should be
contacted relative to any questions.
It is recommended that automatic sprinkler
systems be inspected, tested, and main-
tained by a qualied Inspection Service in
accordance with local requirements and/or
national code.
Limited
Warranty
Products manufactured byTyco Fire & Build-
ing Products (TFBP) are warranted solely to
the original Buyer for ten (10) years against
defects in material and workmanship when
paid for and properly installed and main-
tained under normal use and service. This
warranty will expire ten (10) years from
date of shipment by TFBP. No warranty is
given for products or components manu-
factured by companies not aliated by
ownership with TFBP or for products and
components which have been subject to
misuse, improper installation, corrosion, or
which have not been installed, maintained,
modied or repaired in accordance with ap-
plicable Standards of the National Fire Pro-
tection Association, and/or the standards
of any other Authorities Having Jurisdic-
tion. Materials found by TFBP to be defec-
tive shall be either repaired or replaced, at
TFBP’ sole option. TFBP neither assumes,
nor authorizes any person to assume for it,
any other obligation in connection with the
sale of products or parts of products. TFBP
shall not be responsible for sprinkler system
design errors or inaccurate or incomplete
information supplied by Buyer or Buyer’s
representatives.
In no event shall TFBP be liable, in contract,
tort, strict liability or under any other le-
gal theory, for incidental, indirect, special
or consequential damages, including but
not limited to labor charges, regardless of
whether tyco re products was informed
about the possibility of such damages, and
in no event shall TFBP’ liability exceed an
amount equal to the sales price.
The foregoing warranty is made in lieu of
any and all other warranties express or
implied, including warranties of merchant-
ability and tness for a particular purpose.
This limited warranty sets forth the exclu-
sive remedy for claims based on failure of
or defect in products, materials or compo-
nents, whether the claim is made in con-
tract, tort, strict liability or any other legal
theory.
This warranty will apply to the full extent
permitted by law. The invalidity, in whole or
part, of any portion of this warranty will not
aect the remainder.

TFP342_EN Page 5 of 6
Ordering
Procedure
A Part Number (P/N) is not specied when
ordering sprinklers with thread connec-
tions per ISO 7/1.
Contact your local distributor for availabil-
ity.
Sprinkler Assemblies with NPT Thread
Connection:
Specify: (specify SIN), K160, (specify tem-
perature rating), Series ELO-231B Stand-
ard Response (specify Pendent or Upright)
Sprinkler with (specify nish), P/N (specify
from Table B).
Sprinkler Wrench:
Specify: W-Type 3 Sprinkler Wrench, P/N 56-
895-1-001.
Wax Sticks: (for retouching wrench dam-
aged wax coating)
Specify: (Specify color) color coded Wax
Stick for retouching (specify temperature
rating) temperature rated Series TY-B Sprin-
klers, P/N (specify).
Red for 68°C......................... P/N 56-065-1-155
Blue for 93°C & 141°C....... P/N 56-065-1-286
NOTES
Each wax stick is suitable for retouching up to
twenty-ve sprinklers.
The wax used for 141°C sprinklers is the same
as for 93°C sprinklers, and, therefore, the
141°C sprinkler is limited to the same maxi-
mum ceiling temperature as the 93°C sprin-
kler (i.e. 65°C).
TABLE B
PRODUCT SYMBOL NUMBER SELECTION K160 SERIES
ELO-231B STANDARD RESPONSE UPRIGHT AND PENDENT
SPRINKLERS
TYPE
510 UPRIGHT
3/4” NPT
(TY5151)
512 PENDENT
3/4” NPT
(TY5251)
501 UPRIGHT
1/2” NPT
(TY5851)
FINISH TEMPERATURE
RATING
1 NATURAL BRASS 155 68°C (155°F)
9 CHROME PLATED 200 79°C (200°F)
6 WAX COATED 286 141°C (286°F)
7 LEAD COATED
8 WAX OVER LEAD
P/N 50 — XXX — X — XXX

Page 6 of 6 TFP342_EN
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Note: This document is a translated document. Translations of any materials into languages other than English are intended
solely as a convenience to the non-English-reading public. Translation accuracy is neither guaranteed nor implied. If any
questions arise related to the accuracy of the information contained in the translation, please refer to the English version of
document TFP342 which is the ocial version of the document. Any discrepancies or dierences created in the translation are
not binding and have no legal eect for compliance, enforcement or any other purposes. www.quicksilvertranslate.com.
This manual suits for next models
3
Table of contents
Other Tyco Irrigation System manuals

Tyco
Tyco TY-B Series User manual

Tyco
Tyco Rapidresponse LFII Series User manual

Tyco
Tyco Rapidresponse LFII Series User manual

Tyco
Tyco AM11 User manual

Tyco
Tyco Style 60 User manual

Tyco
Tyco DS-1 Series User manual

Tyco
Tyco DS-2 Series User manual

Tyco
Tyco ESFR-1 User manual

Tyco
Tyco ESFR-17 User manual

Tyco
Tyco DS-3 Series User manual

Tyco
Tyco Grinnell F692 DESIGNER User manual

Tyco
Tyco ILLUSION User manual

Tyco
Tyco EC-11 Series User manual

Tyco
Tyco EC-5 Series User manual

Tyco
Tyco ESFR-22 User manual

Tyco
Tyco EC-11 Series User manual

Tyco
Tyco TY-FRFS User manual

Tyco
Tyco Rapidresponse LFII Series User manual

Tyco
Tyco EC-5 Series User manual

Tyco
Tyco ESFR-25 User manual