Page 1 of 4 JANUARY 2013 TFP152
Series TY-B, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Standard Response, Standard Coverage
Worldwide
Contacts
www.tyco-fire.com
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and
installation of sprinkler systems and
components. Improper handling and
installation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
General
Description
The TYCO Series TY-B, 5.6 K-factor,
Upright (TY315) and Pendent (TY325)
Sprinklers described in this data sheet
are standard response, standard cover-
age, decorative 5 mm glass bulb type
spray sprinklers designed for use in
light, ordinary, or extra hazard, com-
mercial occupancies such as banks,
hotels, shopping malls, factories,
reneries, and chemical plants.
The recessed version of the Series
TY-B Pendent Sprinkler, where appli-
cable, is intended for use in areas with a
nished ceiling. This recessed pendent
sprinkler uses one of the following:
•
A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 inch (15,9 mm) from
the ush pendent position.
•
A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 inch (12,7 mm) from
the ush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the xed pipe drops
to the sprinklers must be cut.
Intermediate level versions of Series
TY-B Sprinklers are described in
Technical Data Sheet TFP352. Sprinkler
guards and shields are described in
Technical Data Sheet TFP780.
NOTICE
The TYCO Series TY-B Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the
applicable standards of the National
Fire Protection Association, in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
Sprinkler
Identification
Numbers (SINs)
TY315 ......Upright 5.6K, 1/2˝ NPT
TY325 .....Pendent 5.6K, 1/2˝ NPT
Technical
Data
Approvals
UL and C-UL Listed
FM and VdS Approved
CE Certied
Maximum Working Pressure
175 psi (12.1 bar)
250 psi (17.2 bar)*
* The maximum working pressure of 250 psi
(17.2 bar) only applies to the listing by Un-
derwriters Laboratories, Inc. (UL).
Discharge Coefficient
K = 5.6 GPM/psi1/2 (80,6 LPM/bar1/2
Temperature Ratings
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
360°F (182°C)†
†UL, C-UL, and VdS Approved only
Finishes
Sprinkler: Natural Brass, Chrome
Plated, Pure White (RAL 9010) and
Signal White (RAL 9003).
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
Frame ................... Bronze
Button..............Brass/Copper
Sealing Assembly .........Stainless
Steel w/TEFLON
Bulb ......................Glass
Compression Screw. . . . . . . . Bronze
Deector................. Bronze

TFP152
Page 2 of 4
Operation
The glass bulb contains a uid which
expands when exposed to heat. When
the rated temperature is reached, the
uid expands sufciently to shatter the
glass bulb, allowing the sprinkler to
activate and water to ow.
Design
Criteria
The TYCO Series TY-B, 5.6 K-factor,
Upright (TY315) and Pendent (TY325)
Sprinklers are intended for re protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable Listing
or Approval agency (e.g., UL Listing
is based on the requirements of NFPA
13, and FM Approval is based on the
requirements of the FM Loss Preven-
tion Data Sheets). Only the Style 15
or Style 20 Recessed Escutcheon, as
applicable, is to be used for recessed
pendent installations.
Installation
The TYCO Series TY-B, 5.6 K-factor,
Upright (TY315) and Pendent (TY325)
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F (57°C) to 3/32
inch (2,4 mm) for the 360°F (182°C)
temperature ratings.
A leak-tight 1/2 inch NPT sprinkler
joint should be obtained by applying a
minimum-to-maximum torque of 7 to 14
ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque may distort the sprinkler inlet
and cause leakage or impairment of the
sprinkler.
Do not attempt to compensate for
insufcient adjustment in the escutch-
eon plate by under- or over-tightening
the sprinkler. Readjust the position of
the sprinkler tting to suit.
Upright and Pendent Sprinklers
The Series TY-B Upright and Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step 1. Install pendent sprinklers in
the pendent position; install upright
sprinklers in the upright position.
Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
tting.
Components:
1/2" NPT
1
5
2
3
4
2"
(50,8 mm)
Frame
Button
Sealing
Assembly
*
6
2-
-
3
-
1
*
-
6 Deector
Compression
Screw
-
5
4-Bulb
2-7/8" (73,0 mm) DIA.
1-3/8"
(34,9 mm)
2"
(50,8 mm)
WRENCH
FLATS
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
STYLE 15 or 20
RECESSED
ESCUTCHEON
7/16" (11,1 mm)
NOMINAL MAKE-IN
Pipe thread connections per ISO 7-1
can be provided on special request.
** DEFLECTOR *
Temperature rating is
indicated on Deector.
DEFLECTOR *
*
ESCUTCHEON PLATE
SEATING SURFACE
**
**
1/2"
NPT
UPRIGHTCROSS SECTION PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-B UPRIGHT (TY315) AND PENDENT (TY325) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, STANDARD RESPONSE
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 3
W-TYPE 7 RECESSED
SPRINKLER WRENCH
WRENCH RECESS
(USE ONLY
END "A")
FIGURE 2
W-TYPE 6
SPRINKLER WRENCH

TFP152
Page 3 of 4
MOUNTING
SURFACE
SERIES
TY-B
CLOSURE MOUNTING
PLATE
2-7/8" DIA.
(73,0 mm)
2-1/4" DIA.
(57,2 mm)
FACE OF
SPRINKLER
FITTING
1/8"
(3,2 mm)
5/16±1/4"
(7,9±6,4 mm) 1/2" (12,7 mm)
1-3/8" (34,9 mm)
FLUSH
7/8" (22,2 mm)
FIGURE 5
SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY (TY325)
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
RECESSED ESCUTCHEON
Step 3. Tighten the sprinkler into the
sprinkler tting using only the W-Type
6 Sprinkler Wrench (Figure 2). With
reference to Figure 1, apply the W-Type
6 Sprinkler Wrench to the wrench ats.
Torque sprinklers 7 to 14 ft.-lbs. (9,5 to
19,0 Nm).
Recessed Pendent Sprinklers
The Series TY-B Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. After installing the Style 15 or
Style 20 Mounting Plate, as applicable,
over the sprinkler threads and with
pipe-thread sealant applied to the pipe
threads, hand-tighten the sprinkler into
the sprinkler tting.
Step B. Tighten the sprinkler into the
sprinkler tting using only the W-Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench ats. Torque
sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0
Nm).
Step C. After the ceiling is installed or
the nish coat is applied, slide on the
Style 15 or Style 20 Closure over the
Series TY-B Sprinkler and push the
Closure over the Mounting Plate until
its ange contacts the ceiling.
Care and
Maintenance
The TYCO Series TY-B, 5.6 K-factor,
Upright (TY315) and Pendent (TY325)
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a re protection system
main control valve for maintenance
work on the re protection system
that it controls, obtain permission to
shut down the affected re protection
system from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a re situation.
The owner must assure that the
sprinklers are not used for hanging
any objects and that the sprinklers are
only cleaned by means of gently dust-
ing with a feather duster; otherwise,
non-operation in the event of a re or
inadvertent operation may result.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory.
Modied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be
replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section.)
Thereafter, annual inspections per
NFPA 25 are required; however, instead
of inspecting from the oor level, a
random sampling of close-up visual
inspections should be made.
The owner is responsible for the
inspection, testing, and maintenance of
their re protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associa-
tion (e.g., NFPA 25), in addition to the
standards of any other authorities hav-
ing jurisdiction. Contact the installing
contractor or sprinkler manufacturer
regarding any questions.
Automatic sprinklers are recommended
to be inspected, tested, and maintained
by a qualied Inspection Service in
accordance with local requirements
and/or national codes.
MOUNTING
PLATE
MOUNTING
SURFACE
SERIES
TY-B
2-7/8" DIA.
(73,0 mm)
FACE OF
SPRINKLER
FITTING
2-1/4" DIA.
(57,2 mm)
1/8"
(3,2 mm)
CLOSURE
3/8±5/16"
(9,5±7,9 mm)
1-3/8" (34,9 mm)
5/8" (15,9 mm)
3/4" (19,1 mm)
FLUSH
FIGURE 4
SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY (TY325)
WITH TWO-PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON

TFP152
Page 4 of 4
Copyright © 2013 Tyco Fire Products, LP. All rights reserved.
TEFLON is trademark of The DuPont Corporation.
GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-B (SIN), K=5.6,
(Upright or Pendent) Sprinkler Standard
Response, (specify) temperature rating,
(specify) nish, P/N (Table A)
Recessed Escutcheon
Specify: Style 15 Recessed Escutcheon
with (specify*) nish, P/N (specify*)
Specify: Style 20 Recessed Escutcheon
with (specify*) nish, P/N (specify*)
* Refer to Technical Data Sheet TFP770.
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
P/N* 77 – XXX – X – XXX
SIN
570 5.6K UPRIGHT (1/2˝ NPT) TY315
571 5.6K PENDENT (1/2˝ NPT) TY325
** Eastern Hemisphere sales only
* Use sufx “I” for ISO 7-1 connection;
for example, 77-570-4-175-I
TABLE A
SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS
— PART NUMBER SELECTION —
SPRINKLER
FINISH
1NATURAL BRASS
4SIGNAL WHITE (RAL 9003)
3PURE WHITE (RAL 9010)**
9CHROME PLATED
TEMPERATURE
RATINGS
135 135°F (57°C)
155 155°F (68°C)
175 175°F ( 79°C)
200 200°F (93°C)
286 286°F (141°C)
360 360°F (182°C)
Other manuals for TY-B Series
22
This manual suits for next models
4
Other Tyco Irrigation System manuals

Tyco
Tyco TFP PH2 Instruction Manual

Tyco
Tyco ELO-231B Series User manual

Tyco
Tyco ESFR-14 User manual

Tyco
Tyco K17-231 User manual

Tyco
Tyco ELO-231FRB Series User manual

Tyco
Tyco TY-FRL Series User manual

Tyco
Tyco FASTFLEX FB User manual

Tyco
Tyco TY-B Series User manual

Tyco
Tyco LD User manual

Tyco
Tyco WS TY3388 User manual

Tyco
Tyco TY-B Series User manual

Tyco
Tyco ESFR-17 User manual

Tyco
Tyco Ultra K17 User manual

Tyco
Tyco TY-B Series User manual

Tyco
Tyco TY-FRL Series User manual

Tyco
Tyco ESFR-25 User manual

Tyco
Tyco TY-FRFS User manual

Tyco
Tyco Rapidresponse LFII Series User manual

Tyco
Tyco Rapidresponse LFII Series User manual

Tyco
Tyco EC-HS User manual