TFP510
Page 7 of 8
Replacement Escutcheons
Order replacement escutcheons
separately.
Note: Style 10 Recessed Escutcheons
are shipped as assemblies comprised
of closure ring and mounting plate. The
included mounting plate is not used
for Dry Type Sprinkler applications,
discard accordingly.
Specify: (specify type), (specify) finish,
P/N (specify):
Recessed (Style 10)
Brass Plated . . . . . . . . . . . . . . . . . 56-701-2-010
Signal White (RAL9003) 56-701-4-010
Chrome Plated . . . . . . . . . . . . . . . 56-701-9-010
Standard (Push-On)
White Color . . . . . . . . . . . . . . . . . . 91-106-0-007
Brass Plated . . . . . . . . . . . . . . . . . 91-106-2-007
Chrome Plated . . . . . . . . . . . . . . . 91-106-9 -007
Deep
Brass Plated . . . . . . . . . . . . . . . . . . 91-107-2-010
White ........................91-107-4-007
Chrome Plated . . . . . . . . . . . . . . . 91-107-9-007
Sprinkler Wrench
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
Sprinkler Boot
Specify: Model DSB-2 Dry Sprinkler
Boot, P/N 63-000-0-002
This Part Number includes one (1)
Boot, two (2) Strap Ties, and 1/3 oz
of Adhesive (a sufficient quantity for
installing one boot).
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
DS-1 Dry-Type Sprinklers
When ordering TYCO Series DS-1
Dry-Type Sprinklers, 5.6K Pendent,
Upright, and Horizontal Sidewall,
Quick Response (3 mm bulb) and Stan-
dard Coverage, specify the following
information:
• SIN:
Pendent – TY3935 or TY3235
Sidewall – TY3735 or TY3335
Upright – TY3135
• 5.6 K-factor
• Deector Style:
Upright, Pendent, or Horizontal
Sidewall
•
Quick Response, Standard Cover-
age, Dry-Type Sprinkler
• Order Length:
Dry-Type Sprinklers are furnished
based upon Order Length as
measured per Figures 3 through
10. After taking the measure-
ment, round it to the nearest 1/4 in.
increment.
• Inlet Connections:
3/4 in. NPT, 1 in. NPT, or ISO 7-R 1
• Temperature Rating
• Sprinkler Finish
•
Escutcheon Style and Finish, as
applicable
• Part Number (P/N) from Table D
The Upright Sprinkler without an
Escutcheon (TY3135) is available in
1 in. NPT only.
Part Numbers are for 3/4 in. and
1 in. NPT standard order sprin-
klers. Orders for all other sprinkler
assemblies must be accompanied
by a complete description. Refer to
the Price List for a complete listing
of Part Numbers.
Absence of the outer piece of an
escutcheon, which is used to cover a
clearance hole, can delay the time to
sprinkler operation in a fire situation.
A Vent Hole is provided in the Bulb
Seat (see Figures 1 and 2) to indicate
if the Dry-Type Sprinkler is remaining
dry. Evidence of leakage from the Vent
Hole indicates potential leakage past
the Inlet seal and the need to remove
the sprinkler to determine the cause
of leakage for example, an improper
installation or an ice plug. Close the
fire protection system control valve and
drain the system before removing the
sprinkler.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. See the Installation
Section.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION, such as NFPA 25, in
addition to the standards of any other
authorities having jurisdiction. Contact
the installing contractor or product
manufacturer with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.