manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco
  6. •
  7. Irrigation System
  8. •
  9. Tyco Style 60 User manual

Tyco Style 60 User manual

Style 60
Two-Piece Flush Escutcheon
3/4 Inch NPT
Page 1 of 2 AUGUST 2018 TFP778
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
Technical
Data
Approvals
UL Listed for use with Series EC-11 and
EC-14 Pendent Sprinklers.
Finishes
Chrome, Signal White, or Brass
Material
Carbon Steel
Installation
The TYCO Style 60 Two-Piece Flush
Escutcheon must be installed in accor-
dance with this section.
General Instructions
A leak tight 3/4 inch NPT sprinkler joint
should be obtained with a torque of
10 to 20 ft.-lbs. Higher levels of torque
may distort the sprinkler orifice seat
with consequent leakage.
The face of the sprinkler fitting must
be positioned from 3/8 inch (9,5 mm)
above to 1/8 inch (3,2 mm) below the
level of the finished ceiling mounting
surface. This will ensure that when
installed the sprinkler escutcheon plate
seating surface is located within the
nominal range to allow proper installa-
tion of the escutcheon closure.
Do not attempt to correct for insuffi-
cient installation and adjustment of the
escutcheon closure by under- or over-
tightening the sprinkler. Readjust the
position of the sprinkler fitting to suit.
Step 1. Orient flat face of escutcheon
mounting plate parallel with open end
of sprinkler threads.
Step 2. Engage sprinkler threads with
mounting plate threads and rotate until
mounting plate is flush with sprinkler
frame arms.
General
Description
The TYCO Style 60 Two-Piece Flush
Escutcheon illustrated in Figure 1 is
designed for use with TYCO Series
EC-11 and EC-14 Pendent Sprinklers
(described in Technical Data Sheet
TFP220) where the piping is installed
above a ceiling. They are used to
improve the overall appearance of the
installation by concealing the clear-
ance holes required for the connecting
piping and fittings to the sprinkler.
The separable two-piece design of
the Style 60 allows installation of the
sprinklers and pressure testing of the
fire protection system/evaluation of
leak tightness, prior to installation of
a suspended ceiling or application of
the finish coating to a fixed ceiling. It
also permits the removal of suspended
ceiling panels, for access to build-
ing service equipment, without having
to first shut down the fire protection
system and remove sprinklers.
NOTICE
The Style 60 Escutcheon described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the stan-
dards of any other authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
Step 3. With thread sealant applied
to sprinkler pipe threads, hand tighten
sprinkler into sprinkler fitting.
Step 4. Using appropriate sprinkler
wrench, apply wrench to designated
sprinkler wrenching area and tighten
sprinkler into sprinkler fitting. (Refer to
Technical Data Sheet TFP220).
Step 5. After suspended ceiling panel
has been installed or finish coat has
been applied to fixed ceiling, slide
escutcheon closure over sprinkler and
mounting plate, pushing until flush
against mounting surface. If installed
beneath suspended ceiling do not
push escutcheon closure beyond point
of contact with mounting surface and
lift ceiling panel above normal position.
Care and
Maintenance
The following inspection procedure
must be performed as indicated, in
addition to any specific requirements
of the NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA). Any impair-
ments must be immediately corrected.
The owner is responsible for the inspec-
tion, testing, and maintenance of their
fire protection system and devices in
compliance with this document, as well
as with the applicable standards of the
NFPA (for example, NFPA 25), in addi-
tion to the standards of any authority
having jurisdiction. The installing con-
tractor or product manufacturer should
be contacted relative to any questions.
It is recommended that automatic sprin-
kler systems be inspected, tested,
and
maintained by a qualified Inspec-
TFP778
Page 2 of 2
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
tion Service in accordance with local
requirements and/or national codes.
After placing a fire protection system
in service, notify the proper authori-
ties and advise those responsible for
monitoring proprietary and/or central
station alarms.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Style 60 Two-Piece Flush
Escutcheon:
Specify: Style 60 Two-Piece Flush
Escutcheon with 3/4 NPT, (specify)
Finish, P/N (specify):
Chrome .......................P/N 208102
Signal White (RAL9003) . . . . . . . . . . P/N 208104
Brass ......................... P/N 208107
MOUNTING
SURFACE
1/8"
(3,2 mm)
1-13/16" (46,0 mm)
2-5/16" (58,7 mm)
CLOSURE
ESCUTCHEON PLATE
SEATING SURFACE:
1/4" (6,4 mm) ABOVE
TO 1/2" (12,7 mm) BELOW
MOUNTING SURFACE;
3/4" (19,1 mm) TOTAL
ADJUSTMENT
2-1/4" DIA.
(57,2 mm)
2-7/8" DIA.
(73,0 mm)
FACE OF
SPRINKLER FITTING:
3/8" (9,5 mm) ABOVE
TO 1/8" (3,2 mm) BELOW
MOUNTING SURFACE 3/4" NPT
MOUNTING
PLATE
INTERNAL
DIMENSIONS OF
STYLE 60 ESCUTCHEON
ACCOMMODATE
CLASS 150 MALLEABLE
IRON REDUCING
SPRINKLER FITTING
FIGURE 1
SERIES EC-11 AND EC-14 PENDENT SPRINKLER ASSEMBLY WITH
3/4 INCH TOTAL ADJUSTMENT STYLE 60 TWO-PIECE FLUSH ESCUTCHEON

Other Tyco Irrigation System manuals

Tyco Rapidresponse LFII Series Operating and maintenance instructions

Tyco

Tyco Rapidresponse LFII Series Operating and maintenance instructions

Tyco ESFR-17 User manual

Tyco

Tyco ESFR-17 User manual

Tyco rapid response LFII Series User manual

Tyco

Tyco rapid response LFII Series User manual

Tyco Integra Ci1 User manual

Tyco

Tyco Integra Ci1 User manual

Tyco ESFR-17 User manual

Tyco

Tyco ESFR-17 User manual

Tyco ESFR-22 User manual

Tyco

Tyco ESFR-22 User manual

Tyco EC-HS User manual

Tyco

Tyco EC-HS User manual

Tyco LFII Series User manual

Tyco

Tyco LFII Series User manual

Tyco TFP485 User manual

Tyco

Tyco TFP485 User manual

Tyco RFII Series User manual

Tyco

Tyco RFII Series User manual

Tyco ESFR-17 User manual

Tyco

Tyco ESFR-17 User manual

Tyco BB Series User manual

Tyco

Tyco BB Series User manual

Tyco TY-QRF-5.6 User manual

Tyco

Tyco TY-QRF-5.6 User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco DS-1 Series User manual

Tyco

Tyco DS-1 Series User manual

Tyco EC-HS User manual

Tyco

Tyco EC-HS User manual

Tyco EC-11 Series User manual

Tyco

Tyco EC-11 Series User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco ESFR-14 User manual

Tyco

Tyco ESFR-14 User manual

Tyco FASTFLEX FB User manual

Tyco

Tyco FASTFLEX FB User manual

Tyco TY-FRL Series User manual

Tyco

Tyco TY-FRL Series User manual

Tyco Rapidresponse LFII Series User manual

Tyco

Tyco Rapidresponse LFII Series User manual

Tyco AM11 User manual

Tyco

Tyco AM11 User manual

Tyco RAVEN 5.6K User manual

Tyco

Tyco RAVEN 5.6K User manual

Popular Irrigation System manuals by other brands

Reliable F1 56 quick start guide

Reliable

Reliable F1 56 quick start guide

Reliable F1FR quick start guide

Reliable

Reliable F1FR quick start guide

FarmTek Growers Supply HydroCycle manual

FarmTek

FarmTek Growers Supply HydroCycle manual

Reliable N252 EC quick start guide

Reliable

Reliable N252 EC quick start guide

Reliable N25 manual

Reliable

Reliable N25 manual

EINHELL GE-WW 5537 E Original operating instructions

EINHELL

EINHELL GE-WW 5537 E Original operating instructions

Tyco Fire Product Gem F892 instruction manual

Tyco Fire Product

Tyco Fire Product Gem F892 instruction manual

Hunter Hydrawise Ready manual

Hunter

Hunter Hydrawise Ready manual

Viking MICROFAST VK332 Technical data

Viking

Viking MICROFAST VK332 Technical data

Viking 12080 Technical bulletin

Viking

Viking 12080 Technical bulletin

K-Rain RPS 75 Setting instructions

K-Rain

K-Rain RPS 75 Setting instructions

greenPRO GPI-66 manual

greenPRO

greenPRO GPI-66 manual

Rehau Firepex Design and installation guide

Rehau

Rehau Firepex Design and installation guide

Pope MASTER DIY GUIDE

Pope

Pope MASTER DIY GUIDE

Reliable DH56 HSW-PL manual

Reliable

Reliable DH56 HSW-PL manual

K-Rain KRC 9 user manual

K-Rain

K-Rain KRC 9 user manual

Toro 53707 installation guide

Toro

Toro 53707 installation guide

Senju Sprinkler RC-QR manual

Senju Sprinkler

Senju Sprinkler RC-QR manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.