Tyco DS-1 Series User manual

Series DS-1 Stainless Steel Dry-Type Sprinklers
5.6K Pendent, HSW, and Extended Coverage HSW
Standard and Quick Response
Page 1 of 10 SEPTEMBER 2014 TFP560
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cau-
tions with respect to handling
and installation of sprinkler sys-
tems and components. Improp-
er handling and installation can
permanently damage a sprin-
kler system or its components
and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
NOTICE
The Series DS-1 Stainless Steel Dry-
Type Sprinklers described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
of the National Fire Protection
Association (NFPA), in addition to
the standards of any authorities
having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condi-
tion. Contact the installing contrac-
tor or product manufacturer with any
questions.
The Series DS-1 Stainless Steel Dry-
Type Sprinklers must only be installed
in fittings that meet the requirements
of the Design Criteria section.
• in systems that are seasonably
drained to avoid freezing (e.g., va-
cation areas)
The stainless steel construction of
these sprinklers extends the life of a
sprinkler beyond that of traditional
copper alloy sprinklers exposed to
corrosive atmospheres. Although
corrosion-resistant sprinklers have
passed the standard corrosion tests
of the applicable approval agencies,
the testing is not representative of all
possible corrosive atmospheres.
Consequently, it is necessary that the
end user be consulted with respect to
the suitability of this alternate material
of construction for any given corrosive
environment. As a minimum, consider
the following criteria:
• ambient temperature
• concentration of chemicals
• humidity
• gas/chemical velocity
• corrosive nature of the chemical to
which the sprinklers are exposed
Stainless Steel Pendent
Dry-Type Sprinklers
The pendent sprinklers are provided
with stainless steel escutcheons that
allow vertical adjustment during in-
stallation. This adjustment provides
a measure of exibility in determining
the length of xed piping to cut for
sprinkler drops.
Stainless Steel Sidewall
Dry-Type Sprinklers
The horizontal sidewall sprinklers are
designed for installation along a wall
or side of a soft and just beneath a
smooth ceiling. Sidewall sprinklers
are commonly used instead of pen-
dent sprinklers due to aesthetics or
building construction considerations
where piping along the ceiling is not
desirable.
General
Description
TYCO Series DS-1 Stainless Steel
Dry-Type Sprinklers, 5.6K Pendent,
Horizontal Sidewall (HSW), and Ex-
tended Coverage HSW, Standard (5
mm bulb) and Quick (3 mm bulb) Re-
sponse are the rst stainless steel
dry-type sprinklers to be listed by
UL and C-UL. With a K-factor of 5.6,
these corrosion-resistant automatic
sprinklers can be used in wet-pipe,
dry-pipe, or preaction systems.
These pendent and horizontal side-
wall sprinklers are available in a vari-
ety of congurations to suit coverage
type and thermal sensitivity. Refer to
the Sprinkler Identication Numbers
(SINs) section for details.
Series DS-1 Stainless Steel Dry-Type
Sprinklers are typically used:
• where corrosive atmospheres exist
(e.g., salt-water areas, parking ga-
rages, chemical storage areas,
mechanical rooms, industrial manu-
facturing sites, and software chip
washing facilities)
• on dry-pipe systems exposed to
freezing temperatures (e.g., sprin-
kler drops from unheated portions
of buildings)
• with pipe connections exposed to
freezing temperatures (e.g., sprin-
kler drops from wet-pipe systems
into freezers or horizontal piping ex-
tensions to protect unheated areas)

TFP560
Page 2 of 10
APPLICATION(1)
Coverage(2)
W x L,
Ft. x Ft.
(m x m)
Minimum
Flow,
gpm
(lpm)
Minimum
Pressure,
psi
(bar)
Temperature
Rating
Top of
Deflector-to-Ceiling
Distance(2)
TY3339
(3 mm Bulb)
For Quick Response,
Light Hazard,
Extended Coverage
per NFPA 13
16 x 16
(4,9 x 4,9)
26
(98)
21.6
(1,49)
135°F (57°C)
and
155°F (68°C)
4 inches (100 mm)
to
12 inches (300 mm)
16 x 18
(4,9 x 5,5)
29
(110)
26.8
(1,85)
16 x 20
(4,9 x 6,1)
32
(121)
32.7
(2,25)
18 x 16
(5,5 x 4,9)
29
(110)
26.8
(1,85)
Notes:
1. These sprinklers are Listed by UL and C-UL. Stainless steel sprinklers noted to be UL and C-UL Listed are listed as Corrosion Resistant Sprinklers.
2. The minimum allowable spacing between sprinklers to prevent cold soldering is 14 feet (4,3 m).
Temperature
Rating Bulb
Color Code
Standard Coverage Extended Coverage
Horizontal Sidewall
Pendent Horizontal Sidewall
TY3230
(3 mm Bulb)
with Standard
Escutcheon
(Figure 10)
with Recessed
Escutcheon(a)
(Figure 11)
with Deep
Escutcheon
(Figure 12)
without
Escutcheon
(Figure 13)
TY3250
(5 mm Bulb)
with Standard*
Escutcheon
(Figure 10)
with Recessed
Escutcheon(a)
(Figure 11)
with Deep*
Escutcheon
(Figure 12)
without*
Escutcheon
(Figure 13)
TY3337
(3 mm Bulb)(b)
with Standard
Escutcheon
(Figure 14)
with Deep
Escutcheon
(Figure 15)
without
Escutcheon
(Figure 16)
TY3357
(5 mm Bulb)(b)
with Standard
Escutcheon
(Figure 14)
with Deep
Escutcheon
(Figure 15)
without
Escutcheon
(Figure 16)
TY3339
(3 mm Bulb)(c)
with Standard
Escutcheon
(Figure 17)
135°F (57°C) Orange 1, 2 1, 2 1**, 2** 1**, 2** 1***, 2***
155°F (68°C) Red 1, 2 1, 2, 3*1**, 2** 1**, 2** 1***, 2***
175°F (79°C) Yellow 1, 2 1, 2 1**, 2** 1**, 2** N/A
200°F (93°C) Green 1, 2 1, 2, 3* 1**, 2** 1**, 2** N/A
286°F (141°C) Blue 1, 2 1, 2, 3*1**, 2** 1**, 2** N/A
360°F (182°C) Mauve N/A 1, 2 N/A 1**, 2** N/A
Notes:
1. Listed by Underwriters Laboratories, Inc. (UL). Stainless steel sprinklers noted to be UL Listed are listed as Corrosion Resistant Sprinklers. Maximum order lengths are described
in Figures 10 through 17.
2. Listed by Underwriters Laboratories for use in Canada (C-UL). Stainless steel sprinklers noted to be C-UL Listed are listed as Corrosion Resistant Sprinklers. Maximum order
lengths are described in Figures 10 through 17.
3. Loss Prevention Certication Board (LPCB) approval and CE conformity apply to these temperature ratings only.
* LPCB approval and CE conformity apply to only these congurations for TY3250 with only these indicated temperatures.
** Light and Ordinary Hazard Occupancies only
*** Light Hazard Occupancies only
a. This conguration is applicable only up to 286°F (141°C).
b. To meet the deector-to-ceiling distance of 4 to 12 inches (100 to 300 mm) for the standard coverage horizontal sidewall, the centerline of the sprinkler waterway must be 4-5/16
to 12-5/16 inches below the ceiling.
c. To meet the deector-to-ceiling distance of 4 to 12 inches (100 to 300 mm) for the extended coverage horizontal sidewall, the centerline of the sprinkler waterway must be 4-7/16
to 12-7/16 inches below the ceiling.
N/A – Not Applicable
TABLE B
SERIES DS-1 STAINLESS STEEL DRY-TYPE
HORIZONTAL SIDEWALL EXTENDED COVERAGE SPRINKLERS
UL AND C-UL INSTALLATION CRITERIA
TABLE A
SERIES DS-1 STAINLESS STEEL DRY-TYPE
PENDENT AND HORIZONTAL SIDEWALL
STANDARD AND EXTENDED COVERAGE SPRINKLERS
LABORATORY LISTINGS AND APPROVALS

TFP560
Page 3 of 10
Operation
When TYCO Series DS-1 Stainless
Steel Dry-Type Sprinklers, 5.6K Pen-
dent, Horizontal Sidewall (HSW), and
Extended Coverage HSW, Standard
(5 mm bulb) and Quick (3 mm bulb)
Response are in service, water is pre-
vented from entering the assembly by
the Plug with Sealing Assembly in the
Inlet of the sprinkler. Refer to Figures 1
through 3.
The glass bulb contains a uid that
expands when exposed to heat. When
the rated temperature is reached, the
uid expands sufciently to shatter
the glass bulb then release the Bulb
Seat.
The compressed Spring is then able
to expand and push the Water Tube as
well as the Guide Tube outward. This
outward action simultaneously pulls
inward on the Yoke, withdrawing the
Plug with Sealing Assembly from the
Inlet and allowing the sprinkler to acti-
vate and ow water effectively.
Design
Criteria
TYCO Series DS-1 Stainless Steel Dry-
Type Sprinklers, 5.6K Pendent, Hori-
zontal Sidewall (HSW), and Extended
Coverage HSW, Standard (5 mm bulb)
and Quick (3 mm bulb) Response are
intended for use in re sprinkler sys-
tems designed in accordance with the
standard installation rules recognized
by the applicable Listing or Approval
agency (e.g., UL Listing is based on
NFPA 13 requirements).
For more information on LPCB Ap-
proval, contact Tyco Fire Protection
Products at the following ofce:
Kopersteden 1
7547 TJ Enschede
The Netherlands
Tel: +31-(0)53-428-4444
Fax: +31-(0)53-428-3377
The Series DS-1 Stainless Steel Ex-
tended Coverage Sprinklers are in-
tended for use in re sprinkler systems
designed in accordance with extend-
ed coverage installation guidelines
provided by NFPA 13 and the installa-
tion criteria provided by Table B.
Sprinkler Fittings
Install the 1 inch NPT Series DS-1
Stainless Steel Dry-Type Sprinkler in
the 1 inch NPT outlet or run of one of
the following ttings:
• malleable or ductile iron thread-
ed tee ttings that meet the dimen-
sional requirements of ANSI B16.3
(Class 150)
• cast iron threaded tee ttings that
meet the dimensional requirements
of ANSI B16.4 (Class 125)
Sprinkler
Identification
Numbers (SINs)
Standard Coverage Pendent
• TY3230 – 3 mm Bulb
• TY3250 – 5 mm Bulb
Standard Coverage
Horizontal Sidewall
• TY3337 – 3 mm Bulb
• TY3357 – 5 mm Bulb
Extended Coverage
Horizontal Sidewall
• TY3339 – 3 mm Bulb
Technical
Data
Approvals
UL and C-UL Listed
LPCB Approved: Ref. No. 094a/12
CE Certied: EN 12259-1
(Refer to Tables A and B for details.)
Maximum Working Pressure
175 psi (12,1 bar)
Inlet Thread Connections
1-Inch NPT or
ISO 7-R 1
Discharge Coefficient
K=5.6 gpm/psi1/2 (80,6 lpm/bar1/2)
Temperature Ratings
Refer to Tables A and B.
Finishes
Sprinkler: Stainless Steel
Escutcheon: Stainless Steel
Physical Characteristics
With the exceptions of the bulb, the
Insert, the Deector, and the Seal-
ing Assembly, all components of the
Series DS-1 Stainless Steel Dry-Type
Sprinkler are constructed with Type
316 Stainless Steel.
• The bulb is glass.
• The Insert is 300 Series Stainless
Steel.
• The Deector is Type 316L Stainless
Steel.
The Sealing Assembly consists of a
Disc Spring that is sealed on both its
inside and outside faces with a TEF-
LON gasket. The Disc Spring is 1/2
Hard Beryllium Nickel.
Refer to Figures 1 through 3 for com-
ponent assemblies.
• cast bronze threaded tee ttings
that meet the dimensional require-
ments of ANSI B16.15 (Class 125)
• stainless steel threaded tee ttings
that meet the dimensional require-
ments of MSS SP-114.
Do not install the Series DS-1 Stain-
less Steel Dry-Type Sprinklers into
elbow ttings. The inlet of the sprinkler
can contact the interior of the elbow,
potentially damaging the Inlet seal.
The unused outlet of the threaded tee is
plugged as shown in Figures 4 and 5.
You can also install the Series DS-1
Sprinklers in the 1 Inch NPT outlet of
a GRINNELL Figure 730 Mechanical
Tee. However, the use of the Figure
730 Tee for this arrangement is limited
to wet-pipe systems.
The conguration shown in Figure 4 is
only applicable for wet-pipe systems
where the sprinkler tting and water-
lled pipe above the sprinkler tting
are not subject to freezing and where
the length of the Stainless Steel Dry-
Type Sprinkler has the minimum
exposure length depicted in Figure 6.
Refer to the Exposure Length section.
For wet-pipe system installations of
the 1 Inch NPT Series DS-1 Stainless
Steel Dry-Type Sprinklers connected
to CPVC piping, use only the following
TYCO CPVC ttings:
• 1” x 1” NPT Female Adapter
(P/N 80145)
• 1” x 1” x 1” NPT Sprinkler Head
Adapter Tee (P/N 80249)
For dry-pipe system installations, use
only the side outlet of maximum 2-1/2
inch reducing tee when locating the
Series DS-1 Stainless Steel Dry-Type
Sprinklers directly below the branch
line. Otherwise, use the conguration
shown in Figure 5 to assure complete
water drainage from above the Series
DS-1 Stainless Steel Dry-Type Sprin-
klers and the branchline. Failure to
do so may result in pipe freezing and
water damage.
NOTICE
Do not install the Series DS-1
Stainless Steel Dry-Type Sprinklers
into any other type fitting without first
consulting the Technical Services
Department. Failure to use the
appropriate fitting can result in one of
the following:
• failure of the sprinkler to operate
properly due to formation of ice
over the Inlet Plug or binding of the
Inlet Plug
• insufficient engagement of the In-
let pipe threads with consequent
leakage

TFP560
Page 4 of 10
3 or 5 mm BULB
WATER
TUBE
VENT HOLE
GUIDE
TUBE
INSERT
YOKE
SCREW
INLET
SEALING
PLUG WITH
CASING
DEFLECTOR
BULB
SPRING
COMPRESSION
SEAT
ASSEMBLY
FRAME
INLET
BAND
WATER
TUBE
GUIDE
TUBE HOLEINLET
INSERT DEFLECTOR
3 or 5 mm
SCREW
COMPRESSION
SEALING
PLUG WITH
BULB
SEAT
YOKE
1" NPT
CASING
SPRING
VENT
FRAME
BULB
ASSEMBLY
BAND
INLET
WATER
TUBE
GUIDE
TUBE HOLEINLET
INSERT DEFLECTOR
3 mm
SCREW
COMPRESSION
SEALING
PLUG WITH
BULB
SEAT
YOKE
1" NPT
CASING
SPRING
VENT
FRAME
BULB
ASSEMBLY
BAND
INLET
FIGURE 3
SERIES DS-1 STAINLESS STEEL DRY-TYPE
EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER
TY3339 (3 mm Bulb)
FIGURE 1
SERIES DS-1 STAINLESS STEEL DRY-TYPE
STANDARD COVERAGE PENDENT SPRINKLERS
TY3230 (3 mm Bulb) and TY3250 (5 mm Bulb)
FIGURE 2
SERIES DS-1 STAINLESS STEEL DRY-TYPE
STANDARD COVERAGE HORIZONTAL SIDEWALL SPRINKLER
TY3337 (3 mm Bulb) and TY3357 (5 mm Bulb)

TFP560
Page 5 of 10
Drainage
In accordance with the minimum
requirements of the National Fire
Protection Association for dry-pipe
sprinkler systems, pitch branch, cross,
and feed main piping connected to
Stainless Steel Dry-Type Sprinklers
and subject to freezing temperatures
to allow proper drainage.
Exposure Length
When using Stainless Steel Dry-Type
Sprinklers in wet-pipe sprinkler sys-
tems protecting areas subject to
freezing temperatures, use Table C
to determine a sprinkler’s appropriate
exposed barrel length to prevent water
from freezing in the connecting pipes
due to conduction. The exposed bar-
rel length measurement must be taken
from the face of the sprinkler tting to
the surface of the structure or insu-
lation that is exposed to the heated
area. Refer to Figure 6 for an example.
Clearance Space
Section 8.4.9.2 of 2010 edition of
NFPA 13 requires a sealed clearance
space around the sprinkler barrel of
dry sprinklers that are connected to
wet-pipe sprinkler systems protect-
ing insulated freezer structures. The
use of the Model DSB-2 Dry Sprin-
kler Boot, described in technical
data sheet TFP591 and illustrated in
Figures 7 and 8, meets this NFPA 13
requirement.
HEATED
AREA (SEE DESIGN
CRITERIA
SECTION)
FACE OF
SPRINKLER
FITTING
LENGTH
EXPOSURE
DSB-2
BOOT
AREA
SUBJECT
TO
FREEZING
RUN
OUTLET
PLUGGED
TO DRY
SYSTEM
DSB-2
BOOT
FITTING
(SEE DESIGN
CRITERIA
SECTION)
SPRINKLER
(ENDS ON OPPOSING
SIDES OF BOOT)
STRAP TIES
ADHESIVE
SHOWN WITH
STANDARD
ESCUTCHEON
DS-1
1-3/4" DIA.
(44,5 mm)
CLEARANCE
HOLE
FREEZER
STRUCTURE
OR EXTERIOR
INSULATED
CEILING
EXPOSED
DSB-2
BOOT
TO FREEZING
SIDE
OUTLET
PLUGGED
TO WET
SYSTEM
FITTING
(SEE DESIGN
CRITERIA
SECTION)
SPRINKLER
DSB-2
BOOT
HEATED
AREA
(ENDS ON
OPPOSING
SIDES OF
STRAP TIES
BOOT)
ADHESIVE
SHOWN WITH
STANDARD
ESCUTCHEON
DS-1
1-3/4" DIA.
(44,5 mm)
CLEARANCE
HOLE
DSB-2
BOOT
FREEZER
STRUCTURE
OR EXTERIOR
INSULATED
WALL EXPOSED
TO FREEZING
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
SPRINKLER
WRENCHING
AREA
FIGURE 4
SPRINKLER FITTING
HEATED AREA
FIGURE 5
SPRINKLER FITTING
UNHEATED AREA
FIGURE 6
EXPOSURE LENGTH
FIGURE 8
MODEL DSB-2 SPRINKLER BOOT
HORIZONTAL SIDEWALL
APPLICATION
FIGURE 7
MODEL DSB-2 SPRINKLER BOOT
PENDENT APPLICATION
FIGURE 9
W-TYPE 7
SPRINKLER WRENCH

TFP560
Page 6 of 10
Installation
TYCO Series DS-1 Stainless Steel
Dry-Type Sprinklers, 5.6K Pendent,
Horizontal Sidewall (HSW), and Ex-
tended Coverage HSW, Standard (5
mm bulb) and Quick (3 mm bulb) Re-
sponse must be installed in accor-
dance with this section.
NOTICE
The Series DS-1 must only be installed
in fittings that meet the requirements
of the Design Criteria section. For
other important requirements regard-
ing piping design and sealing of the
clearance space around the Sprinkler
Casing, refer to the Design Criteria
section.
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of
the air bubble is approximately 1/16
inch (1,6 mm) for the 135°F (57°C) rat-
ing to 1/8 inch (3,2 mm) for the 286°F
(141°C) rating.
A leak-tight 1 inch NPT sprinkler joint
should be obtained by applying a min-
imum-to-maximum torque of 20 to 30
ft.-lbs. (26,8 to 40,2 Nm). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impair-
ment of the sprinkler.
Do not attempt to compensate for in-
sufcient adjustment in an Escutch-
eon Plate by under- or over-tightening
the Sprinkler. Re-adjust the position of
the sprinkler tting to suit.
Step 1. Install pendent sprinklers
only in the pendent position with the
deector parallel to the ceiling. Install
horizontal sidewall sprinklers in the
horizontal position with their center-
line of waterway perpendicular to the
back wall and parallel to the ceiling.
Ensure the word “TOP” on the Deec-
tor faces the ceiling.
Step 2. With a non-hardening pipe
thread sealant such as TEFLON ap-
plied to the Inlet threads, hand-tighten
the sprinkler into the sprinkler tting.
Step 3. Wrench-tighten the sprinkler
using a pipe wrench on the Inlet Band
or Casing (refer to Figures 1 to 3) or
using the W-Type 7 Sprinkler Wrench
on the Wrench Flat (refer to Figure 9).
Note: If sprinkler removal becomes
necessary, remove the sprinkler using
the same wrenching method noted
above. Sprinkler removal is easier
when a non-hardening sealant was
used and torque guidelines were fol-
lowed. After removal, inspect the
sprinkler for damage.
Step 4. After installing the ceiling or
wall and applying a ceiling nish, slide
on the outer piece of the Escutcheon
until it comes in contact with the ceil-
ing or wall. Do not lift the ceiling panel
out of its normal position.
When using the Deep Escutcheon,
hold the outer piece in contact with
the mounting surface (ceiling or wall).
Then rotate the inner piece approxi-
mately 1/4 turn, with respect to the
outer piece, to hold the Deep Escutch-
eon rmly together.
Ambient Temperature
Exposed to
Discharge End of Sprinkler
Temperatures for Heated Area(a)
40°F
(4°C)
50°F
(10°C)
60°F
(16°C)
Minimum Exposed Barrel Length(b),
Inches
(mm)
40°F
(4°C) 0 0 0
30°F
(-1°C) 0 0 0
20°F
(-7°C)
4
(100) 0 0
10°F
(-12°C)
8
(200)
1
(25) 0
0°F
(-18°C)
12
(305)
3
(75) 0
-10°F
(-23°C)
14
(355)
4
(100)
1
(25)
-20°F
(-29°C)
14
(355)
6
(150)
3
(75)
-30°F
(-34°C)
16
(405)
8
(200)
4
(100)
-40°F
(-40°C)
18
(455)
8
(200)
4
(100)
-50°F
(-46°C)
20
(510)
10
(255)
6
(150)
-60°F
(-51°C)
20
(510)
10
(255)
6
(150)
Notes:
1. For protected area temperatures that occur between values listed above, use the next cooler temperature.
2. These lengths are inclusive of wind velocities up to 30 mph (18,6 kph).
TABLE C
EXPOSED SPRINKLER BARRELS IN WET-PIPE SYSTEMS
MINIMUM RECOMMENDED LENGTHS

TFP560
Page 7 of 10
ORDER LENGTHS:
(69,9 to 1219,2 mm)
2-3/4" to 48"
IN 1/4" (6,4 mm)
INCREMENTS
FITTING
FACE OF
SPRINKLER
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
(76,2 mm)
3" DIA.
1-3/4" DIA.
(44,5 mm)
(55,6 ± 3,2 mm)
2-3/16" ± 1/8"
CEILING
FACE OF
SPRINKLER
FACE OF
FITTING
(127,0 to 1219,2 mm)
INCREMENTS
IN 1/4" (6,4 mm)
ORDER LENGTHS:
5" to 48"
DEFLECTOR
TO CEILING
1-3/4" (44,5 mm)
MINIMUM
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
2-1/4" DIA.
(57,2 mm)
1-3/8" ± 1/8"
(34,9 ± 3,2 mm)
2-7/8" DIA.
(73,0 mm)
IN 1/4" (6,4 mm)
3-3/4" to 48"
INCREMENTS
(95,3 to 1219,2 mm)
ORDER LENGTHS:
SPRINKLER
FACE OF
FITTING
CEILING
FACE OF
CRITERIA SECTION)
(REFER TO DESIGN
SPRINKLER FITTING
ORDER LENGTHS:
INCREMENTS
4-1/4" ± 1/8"
(108,0 ± 3,2 mm)
IN 1/4" (6,4 mm)
(12,7 to 1168,4 mm)
1/2" to 46"
FACE OF
CEILING
(88,9 mm)
3-1/2" DIA.
2-1/2" DIA.
(63,5 mm)
FITTING
FACE OF
SPRINKLER
CRITERIA SECTION)
(REFER TO DESIGN
SPRINKLER FITTING
FIGURE 13
PENDENT without ESCUTCHEON
TY3230 (3 mm Bulb) and TY3250 (5 mm Bulb)
FIGURE 12
PENDENT with DEEP ESCUTCHEON
TY3230 (3 mm Bulb) and TY3250 (5 mm Bulb)
FIGURE 10
PENDENT with STANDARD ESCUTCHEON
TY3230 (3 mm Bulb) and TY3250 (5 mm Bulb)
FIGURE 11
PENDENT with RECESSED ESCUTCHEON
TY3230 (3 mm Bulb) and TY3250 (5 mm Bulb)

TFP560
Page 8 of 10
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be
replaced. Also, replace any sprinkler
that has a cracked bulb or that has
lost liquid from its bulb. (Refer to In-
stallation Section.)
The owner is responsible for the in-
spection, testing, and maintenance of
their re protection system and devic-
es in compliance with this document,
as well as with the applicable stan-
dards of the National Fire Protection
Association (e.g., NFPA 25), in addition
to the standards of any other authori-
ties having jurisdiction. Contact the
installing contractor or product manu-
facturer with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualied Inspec-
tion Service in accordance with local
requirements and/or national codes.
A Vent Hole is provided in the Bulb
Seat to indicate if the Dry Sprinkler
is remaining dry. (Refer to Figures 1
through 3.) Evidence of leakage from
the Vent Hole indicates potential leak-
age past the Inlet seal and the need
to remove the sprinkler to determine
the cause of leakage; for example, an
improper installation or an ice plug.
Close the re protection system con-
trol valve and drain the system before
removing the sprinkler.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care and
Maintenance
TYCO Series DS-1 Stainless Steel
Dry-Type Sprinklers, 5.6K Pendent,
Horizontal Sidewall (HSW), and
Extended Coverage HSW, Standard
(5 mm bulb) and Quick (3 mm bulb)
Response must be maintained and
serviced in accordance with this
section.
Before closing a re protection system
main control valve for maintenance
work on the re protection system that
it controls, obtain permission to shut
down the affected re protection sys-
tems from the proper authorities and
notify all personnel who may be af-
fected by this action.
Absence of the outer piece of an es-
cutcheon, which is used to cover a
clearance hole, can delay sprinkler
operation in a re situation.
FACE OF
SPRINKLER
FITTING
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
CENTERLINE
OF WATERWAY
1-3/4" DIA.
(44,5 mm)
FACE OF
MOUNTING
SURFACE
ORDER LENGTHS:
2-3/4" to 48" (69,9 to 1219,2 mm)
IN 1/4" (6,4 mm) INCREMENTS
3" DIA.
(76,2 mm)
5/16"
(7,9 mm)
2-3/8" ± 1/8"
(60,3 ± 3,2 mm)
3.5°
FACE OF
SPRINKLER
FITTING
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
CENTERLINE
OF WATERWAY
FACE OF
MOUNTING
SURFACE
ORDER LENGTHS:
1/2" to 45-3/4" (12,7 to 1162,1 mm)
IN 1/4" (6,4 mm) INCREMENTS
5/16"
(7,9 mm)
3.5°
2-1/2" DIA.
(63,5 mm)
4-1/4" ± 1/8"
(108,0 ± 3,2 mm)
3-1/2" DIA.
(88,9 mm)
FIGURE 14
STANDARD COVERAGE HORIZONTAL SIDEWALL with STANDARD ESCUTCHEON
TY3337 (3 mm Bulb) and TY3357 (5 mm Bulb)
FIGURE 15
STANDARD COVERAGE HORIZONTAL SIDEWALL with DEEP ESCUTCHEON
TY3337 (3 mm Bulb) and TY3357 (5 mm Bulb)

TFP560
Page 9 of 10
Limited
Warranty
For warranty terms and conditions,
visit www.tyco-re.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product description and Part
Number (P/N).
Refer to the price list for a complete
listing of part numbers. Part numbers
are for 1 inch NPT standard order
sprinklers. Orders for all other sprin-
kler assemblies must be accompanied
by a complete description.
Stainless Steel Dry-Type Sprinkler
When ordering Series DS-1 Stain-
less Steel Dry-Type Sprinklers, 5.6K
Pendent, Horizontal Sidewall (HSW),
and Extended Coverage HSW, Stan-
dard (5 mm bulb) and Quick (3 mm
bulb) Response, specify the following
information:
• SIN
Standard Coverage Pendent
TY3230 – Quick Response
TY3250 – Standard Response
Standard Coverage
Horizontal Sidewall
TY3337 – Quick Response
TY3357 – Standard Response
Extended Coverage
Horizontal Sidewall
TY3339 – Quick Response
• Order Length:
Dry-Type Sprinklers are furnished
based upon Order Length as mea-
sured per Figures 10 through 17, as
applicable. Measure the required
length and then round the mea-
surement to the nearest 1/4 inch
increment.
• Inlet Connections:
1 Inch NPT
(Standard)
ISO 7-R 1
(For information on ISO Inlet Thread
Connections, contact your Tyco
Sales Representative.)
• Temperature Rating
(Temperature rating 360°F (182°C)
applies to non-recessed sprinkler
assemblies.)
• Escutcheon Type, as applicable
• Part Number from Table D
Sprinkler Wrench
Specify W-Type 7 Sprinkler Wrench
P/N 56-850-4-001
Sprinkler Boot
Specify Model DSB-2 Dry Sprinkler
Boot, P/N 63-000-0-002
This P/N includes one (1) Boot, two
(2) Strap Ties, and 1/3 oz. of Adhesive
(a sufcient quantity for installing one
boot).
3.5° 5/16"
(7,9 mm)
CENTERLINE
OF WATERWAY
FITTING
SPRINKLER
FACE OF
2-1/4" (57,2 mm)
DEFLECTOR TO
5-1/2" to 48" (139,7 to 1219,2 mm)
IN 1/4" (6,4 mm) INCREMENTS
ORDER LENGTHS:
MINIMUM
MOUNTING
SURFACE
SPRINKLER FITTING
CRITERIA SECTION)
(REFER TO DESIGN
FACE OF
SPRINKLER
FITTING
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
CENTERLINE
OF WATERWAY
1-3/4" DIA.
(44,5 mm)
FACE OF
MOUNTING
SURFACE
ORDER LENGTHS:
2-3/4" to 48"
(69,9 to 1219,2 mm)
IN 1/4" (6,4 mm)
INCREMENTS
3" DIA.
(76,2 mm)
2-3/8" ± 1/8"
(60,3 ± 3,2 mm)
7/16"
(11,1 mm)
FIGURE 16
STANDARD COVERAGE HORIZONTAL SIDEWALL without ESCUTCHEON
TY3337 (3 mm Bulb) and TY3357 (5 mm Bulb)
FIGURE 17
EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER with STANDARD ESCUTCHEON
TY3339 (3 mm Bulb)

TFP560
Page 10 of 10
P/ N*60 – XXX – X– XXX
SIN
11 SS Pendent Quick Response
with Standard Escutcheon (1” NPT)
TY3230
(Figure 10)
12 SS Pendent Quick Response
with Recessed Escutcheon (1” NPT)
TY3230
(Figure 11)
13 SS Pendent Quick Response
with Deep Escutcheon (1” NPT)
TY3230
(Figure 12)
14 SS Pendent Quick Response
without Escutcheon (1” NPT)
TY3230
(Figure 13)
21 SS Pendent Standard Response
with Standard Escutcheon (1” NPT)
TY3250
(Figure 10)
22 SS Pendent Standard Response
with Recessed Escutcheon (1” NPT)
TY3250
(Figure 11)
23 SS Pendent Standard Response
with Deep Escutcheon (1” NPT)
TY3250
(Figure 12)
24 SS Pendent Standard Response
without Escutcheon (1” NPT)
TY3250
(Figure 13)
15
SS HSW Quick Response
Standard Coverage
without Standard Escutcheon (1” NPT)
TY3337
(Figure 14)
16
SS HSW Quick Response
Standard Coverage
with Deep Escutcheon (1” NPT)
TY3337
(Figure 15)
17
SS HSW Quick Response
Standard Coverage
without Escutcheon (1” NPT)
TY3337
(Figure 16)
25 SS HSW Standard Response
Standard Coverage
with Standard Escutcheon (1” NPT)
TY3357
(Figure 14)
26 SS HSW Standard Response
Standard Coverage
with Deep Escutcheon (1” NPT)
TY3357
(Figure 15)
27 SS HSW Standard Response
Standard Coverage
without Escutcheon (1” NPT)
TY3357
(Figure 16)
18
SS HSW Quick Response
Extended Coverage
with Standard Escutcheon (1” NPT)
TY3339
(Figure 17)
ORDER
LENGTH
EXAMPLES(1)
055 5.50”
082 8.25”
180 18.00”
187 18.75”
372 37. 2 5”
480 48.00”
FINISH
6
Stainless Steel for
Sprinkler and
Escutcheon
TEMPERATURE
RATING(2)
0135°F (57°C)
1155°F (68°C)
2175°F (79°C)
3 200°F (93°C)
4286°F (141°C)
5360°F (182°C)
Notes:
1. Dry-Type Sprinklers are furnished based upon “Order Length” as
measured per Figures 10 through 17 and for each individual sprinkler
where it is to be installed. After taking the measurement, round it to
the nearest 1/4 inch increment.
2. Temperature rating 360°F (182°C) applies to non-recessed sprinkler
assemblies.
* Use Prex “I” for ISO 7-R 1 Connection (e.g., I-60-110-6-055).
TABLE D
SERIES DS-1 STAINLESS STEEL DRY-TYPE SPRINKLERS
PART NUMBER SELECTION
Other manuals for DS-1 Series
10
Table of contents
Other Tyco Irrigation System manuals

Tyco
Tyco ESFR-17 User manual

Tyco
Tyco EC-11 Series User manual

Tyco
Tyco Rapidresponse LFII Series User manual

Tyco
Tyco DS-1 Series User manual

Tyco
Tyco DSB-2 User manual

Tyco
Tyco EC-8C User manual

Tyco
Tyco K17-231 User manual

Tyco
Tyco Rapidresponse LFII Series User manual

Tyco
Tyco TY-FRL Series User manual

Tyco
Tyco ESFR-22 User manual

Tyco
Tyco ESFR-14 User manual

Tyco
Tyco TY-B Series User manual

Tyco
Tyco TY-B Series User manual

Tyco
Tyco ELOC User manual

Tyco
Tyco RAVEN Institutional TY3281 User manual

Tyco
Tyco BB Series User manual

Tyco
Tyco EC-5 Series Instruction Manual

Tyco
Tyco EC-HS User manual

Tyco
Tyco RAVEN 5.6K User manual

Tyco
Tyco ESFR-17 User manual