Tyco DSB-2 User manual

General
Description
The Tyco®Model DSB-2 Dry Sprin-
kler Boot (Ref. Figure 1) is designed
for use with TFP Dry Type Sprinklers.
When properly installed, it will help
close the air gap created by the clear-
ance hole through a wall or ceiling
through which the dry type sprinkler
has penetrated.
The DSB-2 is intended predominately
for use with clearance holes through
freezer ceiling structures. In these
types of installations, due to the great-
er temperature difference between the
inside and outside of the freezer than
found with other type installations, the
potential for the formation of conden-
sation in the sprinkler and subsequent
ice build-up is increased. If this con-
densation is not controlled, ice build-
up can occur that might damage the
dry type sprinkler and/or prevent
proper operation in a fire situation.
The DSB-2 is intended to help stop
the air exchange between the inside
and outside of the freezer (or any oth-
er type of similar construction) to help
prevent transfer of moist air into the
freezer space. The use of the DSB-2
provides a quick and efficient means
of closing the air gap created by the
dry type sprinkler clearance hole. The
DSB-2 provides the added feature of
eliminating the occurrence of crack-
ing of some commonly used sealants,
that subsequently allows the passage
of moist air.
WARNINGS
The Model DSB-2 Dry Sprinkler Boot
described herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these
devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Technical
Data
Approvals
The Tyco®Model DSB-2 Dry Sprinkler
Boot does not require laboratory ap-
proval to be installed in accordance
with the applicable standards of the
National Fire Protection Association.
The use of the DSB-2 does not alter
any of the applicable laboratory ap-
provals for TFP Dry Type Sprinklers.
The 2007 edition of NFPA 13, Section
8.4.10.2 requires that dry sprinklers
connected to wet pipe sprinkler
systems protecting insulated freezer
structures, the clearance space
around the sprinkler barrel shall be
sealed.
Dry Type Sprinkler Compatibility
and Technical Data Sheet
Reference
Series DS-1, Standard Response
Standard Coverage,
Pendent, Upright
andHSW...............TFP500
Series DS-1, Quick Response
Standard Coverage,
Pendent, Upright
andHSW...............TFP510
Series DS-C, Standard Coverage
Concealed Pendent . . . . . . . TFP515
Series DS-ECC, Extended Coverage
Concealed Pendent . . . . . . . TFP518
Series DS-1, Extended Coverage
Horizontal Sidewall . . . . . . . TFP520
Series DS-2, Standard
Coverage Pendent . . . . . . . . TFP530
Series DS-2, Extended
Coverage Pendent . . . . . . . . TFP540
Series DS-3, ECOH
Horizontal Sidewall . . . . . . . TFP550
NOTE
Use of the Model DSB-2 Dry Sprinkler
Boot with non-TFP Dry Type Sprinklers
will void the warranty. Failure may re-
sult due to dimensional differences in
the outside diameter of the barrel. The
DSB-2 has not been tested with any
non-TFP Dry Type Sprinklers with re-
gard to fit or performance.
Physical Characteristics
The Boot is EPDM, the Strap Ties
are nylon, and the Adhesive is ethyl
cyanoacrylate based. The adhesive
is formulated for instant bonding of
the Boot to metal, plastic, or rubber
surfaces.
Patents
U.S.A. 7,213,319
Model DSB-2
Dry Sprinkler Boot
For Use With TFP Dry Type Sprinklers
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Page 1 of 4 DECEMBER, 2007 TFP591
Design
Criteria
There are four items to be consid-
ered: Dry Type Sprinklers, Clearance
Hole, Exposure Length, and Sprinkler
Fitting.
Dry Type Sprinklers. This Techni-
cal Data section provides a list of all
of the compatible dry type sprinklers
and their associated technical data
sheets. Refer to the applicable tech-
nical data sheet for installation and
maintenance information for the sprin-
kler being utilized.
NOTE
The TFP Dry Type Sprinklers must be
installed and maintained in compli-
ance with the applicable technical data
sheet. Failure to do so may impair
the performance of these devices.
Clearance Hole. The Model DSB-
2 Dry Sprinkler Boot may be used
with a maximum 2-1/2 inch (63,5
mm) diameter clearance hole (i.e.,
the diameter of the hole in the ceiling
or wall being penetrated by the dry
type sprinkler, reference Figure 1
or 2). Based on the diameter of
the Dry Type Sprinkler Barrel, the
designated maximum clearance hole
will compensate for non-centering of
the Dry Type Sprinkler Barrel within
the clearance hole. Where centering
can be maintained, a clearance hole
as large as 3 inches (76,2 mm) in
diameter can be accommodated.
NOTES
The clearance hole adjacent to the
DSB-2 cannot be larger than 2-1/2
inch (63,5 mm) diameter for a non-
concentric installation or 3 inch (76,2
mm) diameter for a concentric instal-
lation. Otherwise, the DSB-2 cannot
perform as intended by closing the air
gap.
Clearance holes greater than specified
cannot be filled in with foam insula-
tion, etc. In order for the DSB-2 to be
effective in closing the air gap it must
seat and seal against the smooth ma-
terial of the ceiling or wall.
Exposure Length. When Dry Sprin-
klers are to be used in wet pipe sprin-
kler systems protecting areas subject
to freezing temperatures (e.g., sprin-
kler drops into freezers), consider-
ation must be given to the appropriate
length of the sprinkler that will prevent
freezing of the water in the connect-
ing pipes due to conduction. When
the temperature surrounding the wet
pipe sprinkler system is maintained at
a minimum temperature of 40°F/4°C,
INSULATED
FREEZER
STRUCTURE
TFP
DRY TYPE
SPRINKLER
(44,5 mm)
CLEARANCE
HOLE
1-3/4" DIA.
"BOOT"
"ADHESIVE" 3-3/4" DIA.
(95,3 mm) REF.
2" (50,8 mm)
REF.
(ENDS ON
OPPOSING
SIDES OF
"STRAP TIES"
BOOT)
TFP DS-C OR DS-ECC DRY
PENDENT CONCEALED SPRINKLER
CLEARANCE
HOLE
(63,5 mm)
2-1/2" DIA.
MODEL DSB-2
DRY SPRINKLER
BOOT
INSULATED
FREEZER CEILING
STRUCTURE
FIGURE 1
TYPICAL INSTALLATION OF MODEL DSB-2 DRY SPRINKLER BOOT
WITH SERIES DS-1 DRY PENDENT SPRINKLER
FIGURE 2
TYPICAL INSTALLATION OF MODEL DSB-2 DRY SPRINKLER BOOT
WITH SERIES DS-C DRY PENDENT CONCEALED SPRINKLER
Page 2 of 4 TFP591
the following are the minimum recom-
mended lengths between the face of
the sprinkler fitting and the outside sur-
face of the protected area (i.e., length
exposed to minimum ambient tem-
perature of 40°F/4°C — Ref. Figure 3):
• 12 inches (300 mm) when the tem-
perature within the protected area
is -20°F/-29°C
• 18 inches (450 mm) when the tem-
perature within the protected area
is -40°F/-40°C
• 24 inches (600 mm) when the tem-
perature within the protected area
is -60°F/-51°C
For protected area temperatures be-
tween those given above, the mini-
mum recommended length from the
face of the fitting to the outside of the
protected area may be determined by
interpolating between the indicated
values.
NOTE
The temperature within the protected
area must be based on the lowest ex-
pected temperature.
For example: a freezer may be rated
at -20°F/-29°C, yet the condenser is
emitting -30°F/-35°C. The dry sprinkler
length must be calculated based on
the lower temperature of -30°F/-35°C.
Sprinkler Fitting. TFP Dry Type Sprin-
klers must be installed in the 1 inch
NPT outlet or run of a malleable or
cast iron threaded tee as described in
the applicable Technical Data Sheets.
With reference to Figure 4 and in con-
junction with use in a wet pipe system,
the sprinkler drop may be installed as
shown. The information in Figure 4
may only be used where the sprinkler
fitting and water filled pipe above the
sprinkler fitting is not subject to freez-
ing. In areas subject to freezing, the
pipe connected to the dry type sprin-
kler must be configured to allow com-
plete drainage as shown in Figure 5.
Installation
The Tyco®Model DSB-2 must be in-
stalled in accordance with the follow-
ing instructions:
WARNING
The Adhesive contains cyanoacry-
late ester. Irritation will occur when
inhaled. This adhesive bonds skin in
seconds. Contact through clothing
may cause burns. EYE IRRITANT.
Always refer to the Material Safety
Data Sheet for additional adhesive
handling recommendations. The
Material Safety Data Sheet should
FREEZER
HEATED
AREA
AREA
TFP
DRY TYPE
SPRINKLER
EXPOSURE LENGTH
(SEE DESIGN CRITERIA
SECTION)
DSB-2
SPRINKLER
FITTING
HEATED
AREA
DSB-2
SIDE
OUTLET
PLUGGED
TO WET
SYSTEM
NPT TEE
(SEE DESIGN
CRITERIA
SECTION)
1 INCH
AREA
SUBJECT TO
FREEZING
DSB-2
DRY
SYSTEM
RUN
OUTLET
PLUGGED
1 INCH
NPT TEE
FIGURE 3, EXPOSURE LENGTH
FIGURE 4, SPRINKLER FITTING IN HEATED AREA
FIGURE 5, SPRINKLER FITTING IN UNHEATED AREA
TFP591 Page 3 of 4
be obtained from the adhesive man-
ufacturer via their web site noted on
the adhesive container label before
using the adhesive.
In case of skin contact, flush with
water, and for eye contact seek
medical attention.
Provide adequate ventilation in area
of usage. When possible ventilation
should be achieved by the use of
local exhaust ventilation and good
general ventilation. Vapors are
heavier than air, therefore, down-
ward ventilation should be used.
When handling cyanoacrylate ad-
hesives, goggles or safety glasses
should always be worn. Polyethyl-
ene gloves should be used to protect
the hands. WARNING: DO NOT USE
RUBBER OR CLOTH GLOVES. RUB-
BER GLOVES WILL BOND WHEN
BROUGHT IN CONTACT WITH THE
ADHESIVE AND POROUS COTTON
GLOVES WILL ABSORB THE ADHE-
SIVE AND BOND THE GLOVES TO
THE SKIN.
Step 1. Prepare the clearance hole
per the applicable TFP Dry Sprinkler
Technical Data Sheet.
Step 2. Insert the dry sprinkler
through the clearance hole and slide
the Boot over threaded inlet of the dry
sprinkler.
When installing on Series DS-2 Dry
Sprinklers, the Boot will require
stretching. The use of a grooved cou-
pling gasket lubricant will ease instal-
lation. Use only a petroleum free
silicone grooved coupling gasket lu-
bricant to avoid freezing of the Dry
Sprinkler Boot to the Dry Sprinkler.
When sliding the Boot over the length
of the Dry Sprinkler, sliding is easily
accomplished by slightly squeezing
the Boot around the cone area.
Step 3. Thread the dry sprinkler into
the sprinkler fitting per the applica-
ble TFP Dry Sprinkler Technical Data
Sheet.
Refer to the sprinkler technical data
sheet for tightening torque specifica-
tions. The use of higher levels of
torque then specified may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Step 4. Clean the contact surfaces
of the Boot and the building (ceiling
or wall) structure with a damp cloth.
Moist surfaces will aid in a quick
adhesion.
Use only a cloth that has been damp-
ened with water. The use of other
cleaning techniques, solvents, etc.
may render the adhesive incapable of
sealing.
Step 5. Apply the provided Adhesive
to the building structure in a zig-zag
pattern. Refer to Warning regarding
the adhesive.
Step 6. Slide the Boot so that it comes
in contact with the building structure,
and then press the Boot firmly against
the building structure to help ensure
that the Adhesive is fully applied to
both surfaces.
When sliding the Boot over the length
of the Dry Sprinkler, sliding is easily
accomplished by slightly squeezing
the Boot around the cone area.
Step 7. Wait two minutes to allow the
Adhesive to sufficiently cure and then
apply the two Strap Ties. The Strap
Ties are to be applied to the straight
section of the Boot as shown in Figure
1 and so that the ends are on oppos-
ing sides of the Boot.
The ties are to be pulled sufficient-
ly tight to the point that there is no
gap between Dry Sprinkler Boot and
the Dry Sprinkler. When properly in-
stalled a paper clip or wire of similar
dimension cannot be slipped between
the Dry Sprinkler Boot and the Dry
Sprinkler.
Care and
Maintenance
The owner is responsible for the in-
spection, testing, and maintenance
of their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in ad-
dition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
Automatic sprinkler systems should
be inspected, tested, and maintained
by a qualified Inspection Service in
accordance with local requirements
and/or national codes.
Limited
Warranty
Products manufactured by Tyco Fire
& Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years from
date of shipment by TFBP. No warran-
ty is given for products or components
manufactured by companies not affili-
ated by ownership with TFBP or for
products and components which have
been subject to misuse, improper in-
stallation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with
applicable Standards of the Nation-
al Fire Protection Association, and/or
the standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP’s sole
option. TFBP neither assumes, nor
authorizes any person to assume for
it, any other obligation in connection
with the sale of products or parts of
products. TFBP shall not be respon-
sible for sprinkler system design er-
rors or inaccurate or incomplete infor-
mation supplied by Buyer or Buyer’s
representatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP’s liability exceed an amount
equal to the sales price.
The foregoing warranty is made in
lieu of any and all other warranties,
express or implied, including warran-
ties of merchantability and fitness for
a particular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
Model DSB-2:
Specify: Model DSB-2 Dry Sprinkler
Boot*, P/N 63-000-0-002.
* Includes one Boot, two Strap Ties,
and 1/3 oz. of Adhesive (quantity of
adhesive is sufficient for installing one
Boot).
Page 4 of 4 TFP591
© 2007 TYCO FIRE & BUILDING PRODUCTS
, 451 North Cannon Avenue, Lansdale Pennsylvania 19446

Other Tyco Irrigation System manuals

Tyco rapidresponse RSV-1 User manual

Tyco

Tyco rapidresponse RSV-1 User manual

Tyco DS-C Series User manual

Tyco

Tyco DS-C Series User manual

Tyco ILLUSION User manual

Tyco

Tyco ILLUSION User manual

Tyco Mulsifyre F822 User manual

Tyco

Tyco Mulsifyre F822 User manual

Tyco RAVEN Institutional TY3281 User manual

Tyco

Tyco RAVEN Institutional TY3281 User manual

Tyco ESFR-25 User manual

Tyco

Tyco ESFR-25 User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco K17-231 User manual

Tyco

Tyco K17-231 User manual

Tyco G1 User manual

Tyco

Tyco G1 User manual

Tyco ESFR-25 User manual

Tyco

Tyco ESFR-25 User manual

Tyco TY-FRL Series User manual

Tyco

Tyco TY-FRL Series User manual

Tyco Grinnell F692 DESIGNER User manual

Tyco

Tyco Grinnell F692 DESIGNER User manual

Tyco rapid response LFII Series User manual

Tyco

Tyco rapid response LFII Series User manual

Tyco EC-HS User manual

Tyco

Tyco EC-HS User manual

Tyco DS-1 Series User manual

Tyco

Tyco DS-1 Series User manual

Tyco ILLUSION TY5521 User manual

Tyco

Tyco ILLUSION TY5521 User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco RFII Series User manual

Tyco

Tyco RFII Series User manual

Tyco rapid response LFII Series Operating and maintenance instructions

Tyco

Tyco rapid response LFII Series Operating and maintenance instructions

Tyco Rapidresponse LFII Series User manual

Tyco

Tyco Rapidresponse LFII Series User manual

Tyco TY3201 User manual

Tyco

Tyco TY3201 User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco DSB-1 User manual

Tyco

Tyco DSB-1 User manual

Tyco TY-L Series User manual

Tyco

Tyco TY-L Series User manual

Popular Irrigation System manuals by other brands

Lindsay GrowSmart Multi-Control Operation manual

Lindsay

Lindsay GrowSmart Multi-Control Operation manual

Gardena T 200 operating instructions

Gardena

Gardena T 200 operating instructions

Viking M Technical data

Viking

Viking M Technical data

Viking C-1 Window Sprinkler Technical data

Viking

Viking C-1 Window Sprinkler Technical data

Tyco Fire Product CENTRAL ESFR-25 instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESFR-25 instruction manual

Autopot easy2grow 80 Set-up guidelines

Autopot

Autopot easy2grow 80 Set-up guidelines

Reliable J112SS Series Bulletin

Reliable

Reliable J112SS Series Bulletin

Netafim EFLOW CNL XR installation guide

Netafim

Netafim EFLOW CNL XR installation guide

Rain S-Dial installation manual

Rain

Rain S-Dial installation manual

Fiskars 1023659 instructions

Fiskars

Fiskars 1023659 instructions

GW Sprinkler M5 manual

GW Sprinkler

GW Sprinkler M5 manual

Tyco Fire Product Star TFP1 instruction manual

Tyco Fire Product

Tyco Fire Product Star TFP1 instruction manual

Lux Tools A-EWSU-A Set Original instructions

Lux Tools

Lux Tools A-EWSU-A Set Original instructions

Hunter Institutional Series I-90 manual

Hunter

Hunter Institutional Series I-90 manual

Tyco Fire Product Star PH-2 instruction manual

Tyco Fire Product

Tyco Fire Product Star PH-2 instruction manual

Senju Sprinkler RC-RES quick start guide

Senju Sprinkler

Senju Sprinkler RC-RES quick start guide

Tyco Fire Product CENTRAL Ultra K17 instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL Ultra K17 instruction manual

Reliable N252 EC manual

Reliable

Reliable N252 EC manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.