Installation
The TYCO RAPID RESPONSE Series
LFII Residential Pendent Sprinklers
(TY1234) must be installed in accor-
dance with this section:
General Instructions
Do not install any bulb-type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bub-
ble should be present. The diameter
of the air bubble is approximately 1/16
inch (1,6 mm).
A leak-tight 1/2 inch NPT sprinkler
joint should be obtained by applying a
minimum-to-maximum torque of 7 to
14 ft.-lbs. (9,5 to 19,0 Nm). Higher lev-
els of torque can distort the sprinkler
inlet with consequent leakage or im-
pairment of the sprinkler.
Do not attempt to compensate for in-
sufcient adjustment in an Escutch-
eon Plate by under-or over-tightening
the Sprinkler. Re-adjust the position of
the sprinkler tting to suit.
Series LFII Residential Pendent
Sprinklers
The Series LFII Residential Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step 1. Install pendent sprinklers in
the pendent position with the deec-
tor parallel to the ceiling.
Step 2. With pipe-thread sealant ap-
plied to the pipe threads, hand-tighten
the sprinkler into the sprinkler tting.
Step 3. Wrench-tighten the sprinkler
into the sprinkler tting using only the
W-Type 6 Sprinkler Wrench (Figure
3). With reference to Figure 1, apply
the W-Type 6 Sprinkler Wrench to the
wrench ats.
Series LFII Residential Recessed
Pendent Sprinklers
The Series LFII Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. Install recessed pendent
sprinklers in the pendent position with
the deector parallel to the ceiling.
Step B. After installing the Style 20
Mounting Plate over the sprinkler
threads and with pipe thread seal-
ant applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
tting.
Step C. Wrench-tighten the sprinkler
into the sprinkler tting using only the
W-Type 7 Recessed Sprinkler Wrench
(Figure 4). With reference to Figure 1,
apply the W-Type 7 Recessed Sprin-
kler Wrench to the sprinkler wrench
ats.
Step D. After installing the ceiling ap-
plying the nish coat, slide on the
Style 20 Closure over the Series LFII
Sprinkler and push the Closure over
the Mounting Plate until the ange
comes in contact with the ceiling.
Care and
Maintenance
The TYCO RAPID RESPONSE Series
LFII Residential Pendent Sprinklers
(TY1234) must be maintained and ser-
viced in accordance with this section:
Before closing a re protection system
main control valve for maintenance
work on the re protection system that
it controls, obtain permission to shut
down the affected re protection sys-
tem from the proper authorities and
notify all personnel who may be af-
fected by this decision.
Absence of the outer piece of an
escutcheon,which is used to cover
a clearance hole, can delay sprinkler
operation in a re situation.
The owner must assure that the sprin-
klers are not used for hanging any ob-
jects and that the sprinklers are only
cleaned by means of gently dusting
with a feather-duster. Otherwise, non-
operation in the event of a re or inad-
vertent operation may result.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be
replaced. Also, replace any sprinkler
that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section.)
The owner is responsible for the in-
spection, testing, and maintenance of
their re protection system and devic-
es in compliance with this document,
as well as with the applicable stan-
dards of the National Fire Protection
Association (e.g., NFPA 25), in addition
to the standards of any other authori-
ties having jurisdiction. Contact the in-
stalling contractor or sprinkler manu-
facturer regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualied Inspec-
tion Service in accordance with local
requirements and/or national codes.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indi-
cate the full product name and Part
Number (P/N).
Sprinkler Assembly
Specify: Series LFII (TY1234), K=3.0,
Residential Pendent Sprinkler, (speci-
fy) temperature rating, (specify) nish,
and P/N (specify).
155°F (68°C)
Natural Brass ..............P/N 51- 010 -1-155
Signal White (RAL 9003)......P/N 51-010-4-155
Chrome Plated .............P/ N 51- 0 10 - 9 -15 5
175°F (79°C)
Natural Brass ..............P/N 51- 010 -1-175
Signal White (RAL 9003)......P/N 51- 010-4-175
Chrome Plated .............P/N 51-010-9-175
Recessed Escutcheon
Specify: Style 20 Recessed Escutch-
eon with (specify*) nish, and P/N
(specify*).
*Refer to Technical Data Sheet
TFP770.
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench
for use with Series LFII Pendent Sprin-
klers, P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench
for use with Series LFII Recessed Pen-
dent Sprinklers, P/N 56-850-4-001.
TFP402
Page 4 of 4