General
Description
The TYCO RAPID RESPONSE Se-
ries LFII Residential Pendent Sprin-
klers (TY1234) are decorative, fast
response, frangible bulb sprinklers
designed for use in residential occu-
pancies such as homes, apartments,
dormitories, and hotels. When aes-
thetics and optimized ow character-
istics are key considerations, the Se-
ries LFII (TY1234) should be the rst
choice.
The 3.0 K-factor of the Series LFII
Residential Pendent Sprinkler has
been designed to optimize ows (that
is, to avoid over discharging) speci-
cally for small coverage areas up to
14 ft. x 14 ft. (4,3 m x 4,3 m). The re-
quired residential ow rates can then
be delivered with the use of smaller
pipe sizes and reduced water supply
requirements.
The Series LFII Residential Sprinklers
are intended for use in the following
scenarios:
• wet pipe residential sprinkler sys-
tems for one-and two-family dwell-
ings and mobile homes per NFPA
13D
• wet pipe residential sprinkler sys-
tems for residential occupancies
up to and including four stories in
height per NFPA 13R
• wet pipe sprinkler systems for the
residential portions of any occupan-
cy per NFPA 13
The recessed version of the Series
LFII Residential Pendent Sprinkler is
intended for use in areas with nished
ceilings. It employs a two-piece Style
20 Recessed Escutcheon.
The Recessed Escutcheon provides
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of to-
tal adjustment from the ush ceiling
position. The adjustment provided by
the Recessed Escutcheon reduces
the accuracy to which the pipe drops
to the sprinklers must be cut.
The Series LFII Residential Pendent
Sprinkler has been designed with heat
sensitivity and water distribution char-
acteristics proven to help in the con-
trol of residential res and to improve
the chance for occupants to escape
or be evacuated.
NOTICE
The Series LFII Residential Pendent
Sprinklers (TY1234) described herein
must be installed and maintained in
compliance with this document and
with the applicable standards of the
National Fire Protection Association,
in addition to the standards of any au-
thorities having jurisdiction. Failure to
do so may impair the performance of
these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
Sprinkler
Identification
Number (SIN)
TY1234
RAPID RESPONSE Series LFII Residential Sprinklers
3.0 K-factor Pendent
Wet Pipe Systems
Page 1 of 4 APRIL 2013 REV A TFP402
Worldwide
Contacts
SURFACE
ESCUTCHEON
PLATE SEATING
1-9/16"
(39,7 mm)
-
2
Button
Temperature
rating is
indicated on
Deector.
Deector
Compression
Screw
Bulb
Sealing Assembly
-
6
*
-
4
5
-
3
-
*
*
6
4
5
1
3
2
Components:
Frame
1
-
1/2"
NPT
7/16" (11,1 mm)
MAKE-IN
NOMINAL
ESCUTCHEON
STYLE 20
RECESSED
WRENCH
(55,6 mm)
2-3/16"
FLATS
(73,0 mm)
2-7/8" DIA.
Insert
7
-
7
CROSS SECTION PENDENT RECESSED PENDENT
FIGURE 1
RAPID RESPONSE SERIES LFII RESIDENTIAL
PENDENT AND RECESSED PENDENT SPRINKLERS (TY1234)
Technical
Data
Approvals
UL and C-UL Listed
NSF Certied to NSF/ANSI 61
For details on these approvals, refer
to the Design Criteria section.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=3.0 GPM/psi1/2 (43,2 LPM/bar1/2)
Temperature Rating
155°F (68°C) or 175°F (79°C)
Finishes
Natural Brass
Signal White
Chrome Plated
Physical Characteristics
Frame ....................Brass
Button ...................Copper
Sealing Assembly . . . . . . . . Beryllium
Nickel w/TEFLON
Bulb .................3 mm Glass
Compression Screw . . . . . . . . Bronze
Deector .................Bronze
TY1234
2-7/8" DIA.
(73,0 mm)
(57,2 mm)
2-1/4" DIA.
MOUNTING
SPRINKLER
CLOSURE
SURFACE
FITTING
FACE OF
(11,1±3,2 mm)
7/16±1/8"
MOUNTING
PLATE
1-3/8" (34,9 mm)
1-1/8" (28,6 mm)
(3,2 mm)
1/8"
1/2" (12,7 mm)
1/4" (6,4 mm)
FIGURE 2
STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE
RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT SPRINKLER
(TY1234)
WRENCH RECESS
(END "A" USED
FOR TY1234)
FIGURE 3
W-T YPE 6
SPRINKLER WRENCH
RECESS
WRENCH
WITH SPRINKLER
ENGAGEMENT
IN TO ENSURE
WRENCHING AREA
PUSH WRENCH
FIGURE 4
W-TYPE 7 RECESSED
SPRINKLER WRENCH
TFP402
Page 2 of 4
Operation
The glass bulb contains a uid that ex-
pands when exposed to heat. When
the rated temperature is reached, the
uid expands sufciently to shatter
the glass bulb, allowing the sprinkler
to activate and ow water.
Design
Criteria
The TYCO RAPID RESPONSE Series
LFII Residential Pendent Sprinklers
(TY1234) are UL and C-UL Listed for
installation in accordance with the fol-
lowing criteria.
Residential Sprinkler Design Guide
When conditions exist that are out-
side the scope of the provided crite-
ria, refer to the Residential Pendent
Sprinkler Design Guide TFP490 for the
manufacturer’s recommendations that
may be acceptable to the local author-
ity having jurisdiction.
System Type
Only wet pipe systems may be utilized.
Ceiling Types
Smooth at horizontal, or beamed, or
sloped, in accordance with the 2013
Edition of NFPA 13D, 13R, or 13 as
applicable.
Hydraulic Design
(NFPA 13D and 13R)
The minimum required sprinkler
ow rate for systems designed to
NFPA 13D or NFPA 13R are given in
Table A as a function of tempera-
ture rating and the maximum allow-
able coverage areas. The sprinkler
ow rate is the minimum required dis-
charge from each of the total number
of design sprinklers as specied in
NFPA 13D or NFPA 13R.
Hydraulic Design
(NFPA 13)
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is to be the greater of the following:
• The ow rates given in Table A for
NFPA 13D and 13R as a function of
TFP402 temperature rating and the
maximum allowable coverage area.
• A minimum discharge of 0.1
gpm/ft.2over the “design area”
comprised of the four most hydrau-
lically demanding sprinklers for ac-
tual coverage areas protected by
the four sprinklers.
Obstruction to Water Distribution
Sprinklers are to be located in accor-
dance with the obstruction rules of
NFPA 13D, 13R, and 13 as applica-
ble for residential sprinklers as well as
with the obstruction criteria described
within the TYCO technical data sheet
TFP490.
Operational Sensitivity
Sprinklers are to be installed with a
deector-to-ceiling distance of 1-1/4
to 4 inches.
Sprinkler Spacing
The minimum spacing between sprin-
klers is 8 feet (2,4 m). The maximum
spacing between sprinklers can-
not exceed the length of the cover-
age area being hydraulically calculat-
ed (e.g., a maximum of 12 feet for a
12 ft. x 12 ft. coverage area, or 16 feet
for a 16 ft. x 16 ft. coverage area.) Re-
fer to Table A.
TABLE A
WET PIPE SYSTEM
SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY1234)
NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA
Max.
Coverage
Area (a)
Ft. x Ft.
(m x m)
WET PIPE SYSTEM
Minimum Flow and Residual Pressure (b, c)
Ordinary Temp. Rating
155°F (68°C) Intermediate Temp. Rating
175°F (79°C) Deflector to
Ceiling Installation
Type
Minimum
Spacing
Ft.
(m)
Flow
GPM
(L/min)
Pressure
PSI
(bar)
Flow
GPM
(L/min)
Pressure
PSI
(bar)
12 x 12
(3,7 x 3,7)
8
(30,3)
7.1
(0,49)
8
(30,3)
7.1
(0,49)
Smooth
Ceilings
1-1/4 to
4 inches
Beamed
Ceilings per
NFPA 13D
or 13R
1-1/4 to 1-3/4
inches below
bottom of
beam.
Recessed
using Style 20
Escutcheon or
non-recessed
per NFPA 13D,
13R, or 13
8
(2,4)
14 x 14
(4,3 x 4,3)
11
(41,6)
13.4
(0,92)
11
(41,6)
13.4
(0,92)
16 x 16
(4,9 x 4,9)
13
(49,2)
18.8
(1,29)
13
(49,2)
18.8
(1,29)
18 x 18
(5,5 x 5,5)
17
(64,3)
32,1
(2,21)
18
(68,1)
36.0
(2,48)
(a) For coverage area dimensions less than or between those indicated, use the minimum required ow for the next highest coverage
area for which hydraulic design criteria are stated.
(b) Requirement is based on minimum ow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using
the nominal K-factor. Refer to Hydraulic Design under the Design Criteria section.
(c) For NFPA 13 residential applications, the greater of 0.1 gpm/ft2over the design area or the ow in accordance with the criteria in
this table must be used.
TFP402
Page 3 of 4
Installation
The TYCO RAPID RESPONSE Series
LFII Residential Pendent Sprinklers
(TY1234) must be installed in accor-
dance with this section:
General Instructions
Do not install any bulb-type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bub-
ble should be present. The diameter
of the air bubble is approximately 1/16
inch (1,6 mm).
A leak-tight 1/2 inch NPT sprinkler
joint should be obtained by applying a
minimum-to-maximum torque of 7 to
14 ft.-lbs. (9,5 to 19,0 Nm). Higher lev-
els of torque can distort the sprinkler
inlet with consequent leakage or im-
pairment of the sprinkler.
Do not attempt to compensate for in-
sufcient adjustment in an Escutch-
eon Plate by under-or over-tightening
the Sprinkler. Re-adjust the position of
the sprinkler tting to suit.
Series LFII Residential Pendent
Sprinklers
The Series LFII Residential Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step 1. Install pendent sprinklers in
the pendent position with the deec-
tor parallel to the ceiling.
Step 2. With pipe-thread sealant ap-
plied to the pipe threads, hand-tighten
the sprinkler into the sprinkler tting.
Step 3. Wrench-tighten the sprinkler
into the sprinkler tting using only the
W-Type 6 Sprinkler Wrench (Figure
3). With reference to Figure 1, apply
the W-Type 6 Sprinkler Wrench to the
wrench ats.
Series LFII Residential Recessed
Pendent Sprinklers
The Series LFII Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. Install recessed pendent
sprinklers in the pendent position with
the deector parallel to the ceiling.
Step B. After installing the Style 20
Mounting Plate over the sprinkler
threads and with pipe thread seal-
ant applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
tting.
Step C. Wrench-tighten the sprinkler
into the sprinkler tting using only the
W-Type 7 Recessed Sprinkler Wrench
(Figure 4). With reference to Figure 1,
apply the W-Type 7 Recessed Sprin-
kler Wrench to the sprinkler wrench
ats.
Step D. After installing the ceiling ap-
plying the nish coat, slide on the
Style 20 Closure over the Series LFII
Sprinkler and push the Closure over
the Mounting Plate until the ange
comes in contact with the ceiling.
Care and
Maintenance
The TYCO RAPID RESPONSE Series
LFII Residential Pendent Sprinklers
(TY1234) must be maintained and ser-
viced in accordance with this section:
Before closing a re protection system
main control valve for maintenance
work on the re protection system that
it controls, obtain permission to shut
down the affected re protection sys-
tem from the proper authorities and
notify all personnel who may be af-
fected by this decision.
Absence of the outer piece of an
escutcheon,which is used to cover
a clearance hole, can delay sprinkler
operation in a re situation.
The owner must assure that the sprin-
klers are not used for hanging any ob-
jects and that the sprinklers are only
cleaned by means of gently dusting
with a feather-duster. Otherwise, non-
operation in the event of a re or inad-
vertent operation may result.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be
replaced. Also, replace any sprinkler
that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section.)
The owner is responsible for the in-
spection, testing, and maintenance of
their re protection system and devic-
es in compliance with this document,
as well as with the applicable stan-
dards of the National Fire Protection
Association (e.g., NFPA 25), in addition
to the standards of any other authori-
ties having jurisdiction. Contact the in-
stalling contractor or sprinkler manu-
facturer regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualied Inspec-
tion Service in accordance with local
requirements and/or national codes.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indi-
cate the full product name and Part
Number (P/N).
Sprinkler Assembly
Specify: Series LFII (TY1234), K=3.0,
Residential Pendent Sprinkler, (speci-
fy) temperature rating, (specify) nish,
and P/N (specify).
155°F (68°C)
Natural Brass ..............P/N 51- 010 -1-155
Signal White (RAL 9003)......P/N 51-010-4-155
Chrome Plated .............P/ N 51- 0 10 - 9 -15 5
175°F (79°C)
Natural Brass ..............P/N 51- 010 -1-175
Signal White (RAL 9003)......P/N 51- 010-4-175
Chrome Plated .............P/N 51-010-9-175
Recessed Escutcheon
Specify: Style 20 Recessed Escutch-
eon with (specify*) nish, and P/N
(specify*).
*Refer to Technical Data Sheet
TFP770.
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench
for use with Series LFII Pendent Sprin-
klers, P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench
for use with Series LFII Recessed Pen-
dent Sprinklers, P/N 56-850-4-001.
TFP402
Page 4 of 4

Other manuals for Rapidresponse LFII Series

18

Other Tyco Irrigation System manuals

Tyco CCU Rack Installation guide

Tyco

Tyco CCU Rack Installation guide

Tyco ESFR-25 User manual

Tyco

Tyco ESFR-25 User manual

Tyco DS-1 Series User manual

Tyco

Tyco DS-1 Series User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco TFP PH2 Instruction Manual

Tyco

Tyco TFP PH2 Instruction Manual

Tyco SW-20 User manual

Tyco

Tyco SW-20 User manual

Tyco RFII Series User manual

Tyco

Tyco RFII Series User manual

Tyco TY7158 User manual

Tyco

Tyco TY7158 User manual

Tyco Rapidresponse LFII Series User manual

Tyco

Tyco Rapidresponse LFII Series User manual

Tyco AquaMist AM4 User manual

Tyco

Tyco AquaMist AM4 User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco Power Pro Series User manual

Tyco

Tyco Power Pro Series User manual

Tyco Rapidresponse LFII Series Operating and maintenance instructions

Tyco

Tyco Rapidresponse LFII Series Operating and maintenance instructions

Tyco 3002B User manual

Tyco

Tyco 3002B User manual

Tyco RFII-MRI Series User manual

Tyco

Tyco RFII-MRI Series User manual

Tyco TY-FRL Series User manual

Tyco

Tyco TY-FRL Series User manual

Tyco Ultra K17 User manual

Tyco

Tyco Ultra K17 User manual

Tyco RFII User manual

Tyco

Tyco RFII User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco G2 User manual

Tyco

Tyco G2 User manual

Tyco LFII Series User manual

Tyco

Tyco LFII Series User manual

Tyco CC3 User manual

Tyco

Tyco CC3 User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco Rapidresponse LFII Series User manual

Tyco

Tyco Rapidresponse LFII Series User manual

Popular Irrigation System manuals by other brands

Tyco Fire Product CENTRAL BV4-QREC instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV4-QREC instruction manual

Rain Bird 552 Series Operation & maintenance manual

Rain Bird

Rain Bird 552 Series Operation & maintenance manual

Uponor MLC-S Mounting instructions

Uponor

Uponor MLC-S Mounting instructions

Tyco Fire Product CENTRAL BV instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV instruction manual

Autopot easy2grow 48 Set-up guidelines

Autopot

Autopot easy2grow 48 Set-up guidelines

Task Force Tips Masterstream Series INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

Task Force Tips

Task Force Tips Masterstream Series INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

Duramaxx Sprizzz manual

Duramaxx

Duramaxx Sprizzz manual

Kompernass KH4083-10 operating instructions

Kompernass

Kompernass KH4083-10 operating instructions

DIG 400A Series instruction manual

DIG

DIG 400A Series instruction manual

Ebinger LEADER 50 Instruction booklet

Ebinger

Ebinger LEADER 50 Instruction booklet

Eden 96122EDAMZ quick start guide

Eden

Eden 96122EDAMZ quick start guide

Kärcher WU 60/2 sun instructions

Kärcher

Kärcher WU 60/2 sun instructions

Reliable F1 Res 30 LL Bulletin

Reliable

Reliable F1 Res 30 LL Bulletin

Reliable F3QR56 manual

Reliable

Reliable F3QR56 manual

Galcon 9001D Operation and installation instructions

Galcon

Galcon 9001D Operation and installation instructions

Toro FLX35-6 Series Installation and service instructions

Toro

Toro FLX35-6 Series Installation and service instructions

Johnson Controls DS-2 Series manual

Johnson Controls

Johnson Controls DS-2 Series manual

CENTRAL ELO-231 manual

CENTRAL

CENTRAL ELO-231 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.