Care and
Maintenance
The Type HV Nozzles must be main-
tained and serviced in accordance
with the following instructions:
NOTE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
itcontrols,permission toshutdownthe
affectedfire protectionsystemmustbe
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Type HV Nozzles must never be
painted, plated, coated or altered in
any way after leaving the factory; oth-
erwise, the spray performance may be
impaired.
Care must be exercised to avoid dam-
agetothenozzles-before,during,and
after installation. Nozzles damaged by
dropping, striking, wrench twist/slip-
page, or the like, must be replaced.
Frequent visual inspections are rec-
ommendedtobeinitiallyperformedfor
nozzles installed in potentially corro-
sive atmospheres to verify theintegrity
of the materials of constructionas they
may be affected by the corrosive con-
ditions present for a given installation.
Thereafter, annual inspections per
NFPA 25 are required.
Water spray fixed systems for fire pro-
tection service require regularly
scheduled care and maintenance by
trained personnel. In addition to in-
specting nozzles for proper spray per-
formanceduringwater flow triptestsof
the system, it is recommended that
nozzles be periodically inspected for
broken or missing parts or evidence of
impaired protection. The inspections
should be scheduled weekly or as fre-
quently as may be necessary, andcor-
rective action must be taken to ensure
that the nozzles will perform as in-
tended in the event of a fire.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
It is recommended that water spray
fixed systems be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
havebeensubject to misuse,improper
installation,corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP’s sole
option. TFBP neither assumes, nor
authorizesanypersontoassumeforit,
any other obligation in connection with
the sale of products or parts of prod-
ucts.TFBP shall not be responsiblefor
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer’s repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect,special or consequentialdam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP’s liability exceed an amount
equal to the sales price.
Theforegoingwarrantyismadeinlieu
of any and all other warranties, ex-
press or implied, including warranties
ofmerchantabilityandfitnessforapar-
ticular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name and P/N.
Contact your local distributor for avail-
ability.
HV Nozzles:
Specify: Type (number), (specify
brass or stainless steel) Nozzle with
(specify NPT or ISO 7/1) thread con-
nection, P/N (specify).
Brass Assemblies, NPT
HV-14 . . . . . . . . . . . . . . . . . . . P/N 49-014-1-001
HV-17 . . . . . . . . . . . . . . . . . . . P/N 49-016-1-001
HV-26 . . . . . . . . . . . . . . . . . . . P/N 49-026-1-001
HV-37 . . . . . . . . . . . . . . . . . . . P/N 49-037-1-001
HV-45 . . . . . . . . . . . . . . . . . . . P/N 49-045-1-001
HV-60 . . . . . . . . . . . . . . . . . . . P/N 49-060-1-001
Stainless Steel Assemblies, NPT
HV-14 . . . . . . . . . . . . . . . . . . . P/N 49-014-0-001
HV-17 . . . . . . . . . . . . . . . . . . . P/N 49-016-0-001
HV-26 . . . . . . . . . . . . . . . . . . . P/N 49-026-0-001
HV-37 . . . . . . . . . . . . . . . . . . . P/N 49-037-0-001
HV-45 . . . . . . . . . . . . . . . . . . . P/N 49-045-0-001
HV-60 . . . . . . . . . . . . . . . . . . . P/N 49-060-0-001
Brass Assemblies, ISO 7/1
HV-14 . . . . . . . . . . . . . . . . . . . P/N PBP55062
HV-17 . . . . . . . . . . . . . . . . . . . P/N PBP55071
HV-26 . . . . . . . . . . . . . . . . . . . P/N PBP55080
HV-37 . . . . . . . . . . . . . . . . . . . P/N PBP55099
HV-45 . . . . . . . . . . . . . . . . . . . P/N PBP55101
HV-60 . . . . . . . . . . . . . . . . . . . P/N AEC00236
Stainless Steel Assemblies, ISO 7/1
HV-14 . . . . . . . . . . . . . . . . . . . P/N AEC00012
HV-17 . . . . . . . . . . . . . . . . . . . P/N AEC00021
HV-26 . . . . . . . . . . . . . . . . . . . P/N AEC00030
HV-37 . . . . . . . . . . . . . . . . . . . P/N AEC00049
HV-45 . . . . . . . . . . . . . . . . . . . P/N AEC00058
HV-60 . . . . . . . . . . . . . . . . . . . P/N AEC00263
Page6of6 TFP815
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446