
TFP330
Page 2 of 4
Design
Criteria
UL and C-UL Listing Requirements
The TYCO 16.8 K-factor, Ultra K17,
Standard Response, Upright Control
Mode Specific Application Sprin-
kler may be installed in accordance
with NFPA 13 “Control Mode Spe-
cific Application Sprinkler (for Storage
Use)” requirements to provide ceiling
only protection (that is, no in-rack
sprinklers) for high piled storage occu-
pancies (Solid-piled, palletized and
rack storage including but not limited to
Class I-IV and Group A plastics) using
the criteria from NFPA 13.
FM Approval Requirements
The TYCO 16.8 K-factor, Ultra K17
(TY7153) Sprinklers may be installed
with the applicable “storage sprinkler”
guidelines provided by Factory Mutual.
(FM guidelines may differ from UL and
C-UL Listing criteria.)
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and flow water.
Installation
The TYCO 16.8 K-factor, Ultra K17,
Standard Response, Upright Control
Mode Specific Application Sprinkler
must be installed in accordance with
this section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontal, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm).
NOTICE
Obtain a 3/4 inch NPT sprinkler joint
by applying a minimum to maximum
torque of 7 to 14 ft.-lbs. (9,5 to 19,0
Nm). Higher levels of torque can distort
the sprinkler Inlet with consequent
leakage or impairment of the sprinkler.
Step 1. With pipe thread sealant
applied to the pipe threads, hand
tighten the Ultra K17 Sprinkler into the
sprinkler fitting.
Step 2. Using the W-Type 8 Sprinkler
Wrench (Ref. Figure 2) applied to the
sprinkler Wrench Flats (Ref. Figure 1),
tighten the Ultra K17 Sprinkler into the
sprinkler fitting.
Care and
Maintenance
The TYCO 16.8 K-factor, Ultra K17,
Standard Response, Upright Control
Mode Specific Application Sprinkler
must be maintained and serviced in
accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection systems must
be obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers - before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section).
SPRINKLER FINISH
TYPE TEMPERATURE BULB
LIQUID NATURAL BRASS WITH
CHROME DEFLECTOR
UPRIGHT K = 16.8 (TY7153)
155°F (68°C) Red 3, 4
200°F (93°C) Green 1, 2, 3, 4
NOTES:
a. Listed by Underwriters Laboratories, Inc. (UL Listed)
b. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL Listed)
c. Approved by Factory Mutual Research Corporation (FM Approved)
d. Approved by the City of New York under MEA 177-03-E
TABLE A
LABORATORY LISTINGS AND APPROVALS
(REFER TO THE DESIGN CRITERIA SECTION)