
TFP450
Page 5 of 6
Step 4. Replace the Protective Cap
by pushing it upwards until it bottoms
out against the Support Cup. The Pro-
tective Cap helps prevent damage to
the Deflector and Arms during ceiling
installation and/or during application of
the finish coating of the ceiling. It may
also be used to locate the center of the
clearance hole by gently pushing the
ceiling material against the center point
of the Cap.
As long as the Sprinkler Strap (Figure 1)
or the Protective Cap (Figure 2) remains
in place, the system is considered to be
“Out Of Service.”
Step 5. After the ceiling has been com-
pleted with the 2-1/2 in. (63 mm) diam-
eter clearance hole and in preparation
for installing the Cover Plate/Retainer
Assembly, remove and discard the Pro-
tective Cap and the Sprinkler Strap.
NOTE: Refer to Technical Data Sheet
TFP700 regarding instructions for the
removal of the Sprinkler Strap.
Step 6. Push the Cover Plate/Retainer
Assembly into the Support Cup, and
as necessary, make the final adjust-
ment of the Cover Plate with respect to
the ceiling by turning the Cover Plate/
Retainer Assembly clockwise until its
flange just comes in contact with the
ceiling.
If it becomes necessary to remove
the Cover Plate, it can be removed
by unscrewing in a counter-clockwise
direction.
If the Cover Plate/Retainer Assembly
cannot be engaged with the Support
Cup or the Cover Plate/Retainer
Assembly cannot be engaged suffi-
ciently to contact the ceiling, the Sprin-
kler Fitting must be repositioned.
Care and
Maintenance
The TYCO Series LFII Residential
Domed-Plate Concealed Pendent 4.9
K-factor Sprinklers (TY2234) must be
maintained and serviced in accordance
with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of a Cover Plate may delay
sprinkler operation in a fire situation.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
When properly installed, there is a
nominal 3/32 in. (2,4 mm) air gap
between the lip of the Cover Plate and
the ceiling, as shown in Figure 2. This
air gap is necessary for proper oper-
ation of the sprinkler by allowing heat
flow from a fire to pass below and
above the Cover Plate to help assure
appropriate release of the Cover Plate
in a fire situation. If the ceiling needs
repainting after sprinkler installation,
exercise care to ensure that the new
paint does not seal off any of the air
gap. Failure to do so may impair sprin-
kler operation.
Factory painted Cover Plates must not
be repainted. They should be replaced,
if necessary, by factory painted
units. Non-factory applied paint may
adversely delay or prevent sprinkler
operation in the event of a fire.
Do not pull the Cover Plate relative to
the Retainer. Separation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied or overheated sprinklers must be
replaced.
Care must be exercised to avoid
damage to the sprinklers - before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. Refer to the Instal-
lation section for additional information.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION (e.g., NFPA 25), in addi-
tion to the standards of any authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and
Part Number (P/N).
Sprinkler Assembly
Specify: Series LFII (TY2234), K = 4.9,
Residential Domed-Plate Concealed
Pendent Sprinkler without Cover Plate
Assembly, P/N 51-873-1-155
Cover Plate Assembly
Specify: Series LFII (TY2234), K = 4.9,
Residential Domed-Plate Concealed
Pendent Sprinkler Cover Plate Assem-
bly with (specify) finish, P/N (specify):
Pure White*(RAL9010) . . . . . P/N 56-873-3-135
Signal White (RAL9003). . . . . P/N 56-873-4-135
Chrome..................P/N 56-873-9-135
Custom ................. P/N 56-873-X-135
*Eastern Hemisphere sales only.
Sprinkler Wrench
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001