Installation
TYCO Model TY3201, Quick Response,
Standard Coverage, 80K Pendent
Sprinklers must be installed in accor-
dance with this section.
NOTICE
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1,6 mm.
Install pendent sprinklers only in the
pendent orientation with the deflector
parallel to the mounting surface.
General Instructions
A leak-tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of
9.5 to 19,0 N·m. Higher levels of torque
may distort the sprinkler inlet with con-
sequent leakage or impairment of the
sprinkler.
Do not attempt to compensate for
insufficient adjustment of an escutch-
eon plate by under- or over-tightening
the sprinkler. Readjust the position of
the sprinkler fitting to suit.
Step 1. After installing an escutcheon,
as applicable, over the sprinkler pipe
threads, and with pipe thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 2. Wrench-tighten pendent sprin-
klers using only the W-Type 6 (End A)
Sprinkler Wrench. The wrench recess
of the sprinkler wrench (Ref. Figure 2)
is to be applied to the sprinkler wrench
flats (Ref. Figure 1).
Care and
Maintenance
TYCO Model TY3201, Quick Response,
Standard Coverage, 80K Pendent
Sprinklers must be maintained and ser-
vices in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Refer to Installa-
tion Section).
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with
NPT Thread Connections
Specify: Model TY3201, Quick
Response Pendent Sprinklers,
68°C, with Chrome Plated finish,
P/N 51-014-9-155
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
WRENCH RECESS
(USE END "A" FOR
MODEL TY3201)
-
Button
Temperature
rating is
indicated on
Deector.
Deector
Compression
Screw
Bulb
Sealing
-
*
-
-
-
*
*
6
4
5
1
3
2
Components:
Frame
-
1/2"
NPT
MAKE-IN
NOMINAL
WRENCH
FLATS
25,7 mm
Assembly
FIGURE 1
QUICK RESPONSE
MODEL TY3201 PENDENT SPRINKLER
80 K-FACTOR, 1/2 INCH NPT
FIGURE 2
W-T YPE 6
SPRINKLER WRENCH