Care and
Maintenance
The TYCO Series TY-B and TY-FRB
must be maintained and serviced in
accordance with this section.
NOTICE
Before closing a fire protection sys-
tem main control valve for maintenance
work on the fire protection system that
it controls, obtain permission to shut
down the affected fire protection sys-
tem from the proper authorities and no-
tify all personnel who may be affected
by this action.
Absence of an escutcheon, which is
used to cover a clearance hole, can de-
lay the time to sprinkler operation in a
fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
ed sprinklers must be replaced. Sprin-
klers that have been exposed to corro-
sive products of combustion, but have
not operated, should be replaced if
they cannot be completely cleaned by
wiping the sprinkler with a cloth or by
brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers before, during, and
after installation. Sprinklers damaged
by dropping, striking, wrench twist/
slippage, or the like, must be replaced.
Also, replace any sprinkler that has a
cracked bulb or that has lost liquid from
its bulb. (Ref. Installation Section).
The owner is responsible for the in-
spection, testing, and maintenance of
their re protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associa
-
tion (e.g., NFPA 25), in addition to the
standards of any other authorities hav-
ing jurisdiction. Contact the installing
contractor or sprinkler manufacturer
regarding any questions.
Automatic sprinkler systems are recom-
mended to be inspected, tested, and
maintained by a qualied Inspection
Service in accordance with local re-
quirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-re.com.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and part
number (P/N).
Sprinkler Assemblies
Specify: (SIN), Series (TY-B or TY-FRB),
(Standard or Quick Response), 10 mm
Orice, (temperature rating), (Pen-
dent or Upright) Sprinkler with (nish),
P/N (from Table B)
Recessed Escutcheon
Specify: Style 70 Recessed Escutcheon
with (specify*) nish, P/N (specify*)
* Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
SPRINKLER
FINISH
1NATURAL BRASS
3PURE WHITE (RAL9010)*
POLYESTER
4SIGNAL WHITE (RAL9003)
POLYESTER
9CHROME PLATED
* Eastern Hemisphere sales only
TEMPERATURE
RATINGS
135 135°F (57°C)
155 155°F (68°C)
175 175°F ( 79°C)
200 200°F (93°C)
286 286°F (141°C)
360 360°F (182°C)
(5 mm Bulb Only)
SIN
580 UPRIGHT 5 mm Bulb TY2108
581 PENDENT 5 mm Bulb TY2208
380 UPRIGHT 3 mm Bulb TY2109
381 PENDENT 3 mm Bulb TY2209
P/N 57 – XXX – X – XXX
TABLE B
SERIES TY-B (5 MM BULB) & TY-FRB (3 MM BULB) 10 MM ORIFICE
UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION