Series TY-B & TY-FRB, 10 mm Orifice, ISO 7-R 3/8
Upright, Pendent, and Recessed Pendent Sprinklers
Standard and Quick Response
Page 1 of 4 APRIL 2015 TFP670
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
General
Description
The TYCO Series TY-B (5 mm Bulb) and
TY-FRB (3 mm Bulb), 10 mm orice Up-
right and Pendent Sprinklers are auto-
matic sprinklers of the frangible bulb
type. They are spray sprinklers intend-
ed for use in re sprinkler systems de-
signed in accordance with the installa-
tion rules recognized by the applicable
approval agency. Both the Upright and
Pendent Sprinklers produce a hemi-
spherical water distribution pattern be-
low the deector.
The recessed version of the Series
TY-B and TY-FRB Pendent Sprinklers,
where applicable, are intended for use
in areas with a nished ceiling. They
use a two-piece Style 70 (3/8 inch NPT)
Recessed Escutcheon with 12 mm of
recessed adjustment or up to 20 mm of
total adjustment from the ush pendent
position. The adjustment provided by
the Recessed Escutcheon reduces the
accuracy to which the xed pipe drops
to the sprinklers must be cut.
NOTICE
The Series TY-B and TY-FRB Sprin-
klers described herein must be installed
and maintained in compliance with this
document and with the applicable
standards recognized by the Approval
Agency, in addition to the standards of
any other authorities having jurisdiction.
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN)
TY2108 .........Upright, 5 mm bulb
TY2208 ........ Pendent, 5 mm bulb
TY2109 .........Upright, 3 mm bulb
TY2209 .........Pendent, 3 mm bulb
Technical
Data
Approvals
LPCB and VdS Approved
Refer to Table A
Maximum Working Pressure
12,1 bar
Discharge Coefficient
K = 58 lpm/bar1/2
Temperature Rating
Refer to Table A
Finishes
Refer to Table A
Physical Characteristics
Frame � � � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze
Button � � � � � � � � � � � � � � � � � � � � � � Brass/Copper
Sealing Assembly ��Beryllium Nickel w/TEFLON
Bulb � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � Glass
Compression Screw � � � � � � � � � � � � � � � � �Bronze
Deflector � � � � � � � � � � � � � � � � � � � � � � � � � Copper
Operation
The glass Bulb contains a uid that ex-
pands when exposed to heat. When the
rated temperature is reached, the uid
expands sufciently to shatter the glass
Bulb, allowing the sprinkler to activate
and water to ow.
Design
Criteria
The TYCO Series TY-B and TY-FRB
10 mm Orice Pendent and Upright
Sprinklers are intended for re protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable approv-
al agency. Only the Style 70 Escutch-
eon is to be used for recessed pendent
installation.
TFP670
Page 2 of 4
Installation
The TYCO Series TY-B and TY-FRB
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb-type sprinkler if
the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F (57°C) to 3/32
inch (2,4 mm) for the 360°F (182°C) tem-
perature ratings.
Do not attempt to compensate for in-
sufcient adjustment in the Escutcheon
Plate by under- or over-tightening the
sprinkler. Re-adjust the position of the
sprinkler tting to suit.
A leak-tight ISO 7-R 3/8 sprinkler joint
should be obtained by applying a mini-
mum to maximum torque of 8 to 16 Nm.
Higher levels of torque can distort the
sprinkler Inlet with consequent leakage
or impairment of the sprinkler.
The Series TY-B and TY-FRB Pendent
and Upright Sprinklers must be in-
stalled in accordance with the follow-
ing instructions.
Step 1.
Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2.
With pipe-thread sealant ap-
plied to the pipe threads, hand-tight-
en the sprinkler into the sprinkler tting.
Step 3.
Tighten the sprinkler into the
sprinkler tting using only the W-Type 6
Sprinkler Wrench (Figure 4). With refer-
ence to Figure 1, the W-Type 6 Sprinkler
Wrench is to be applied to the sprinkler
wrench ats.
SPRINKLER FINISH
TYPE TEMPERATURE BULB LIQUID
COLOR NATURAL
BRASS CHROME
PLATED POLYESTER***
5 mm Bulb
1, 4
UPRIGHT
(TY2108)
PENDENT
(TY2208)
135°F (57°C) Orange
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286°F (141°C) Blue
360°F (182°C) Mauve
RECESSED
PENDENT
(TY2208)
135°F (57°C) Orange
1
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
3 mm Bulb
2, 4
UPRIGHT
(TY2109)
PENDENT
(TY2209)
135°F (57°C) Orange
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286°F (141°C) Blue
RECESSED
PENDENT
(TY2209)
135°F (57°C) Orange
3
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
NOTES:
1. Approved by the Loss Prevention Certication Board (LPCB Ref. No. 094a/05 & 007k/03) as Standard Response.
2. Approved by the Loss Prevention Certication Board (LPCB Ref. No. 007k/04) as Quick Response.
3. Approved by the Loss Prevention Certication Board (LPCB Ref. No. 007k/04) as Unclassied Response.
4. VdS Approved
For details, contact Tyco Fire Protection Products,
Enschede, The Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377.
***Frame and deector only.
N/A: Not Available
TABLE A
LABORATORY APPROVALS
TFP670
Page 3 of 4
The Series TY-B and TY-FRB Re-
cessed Pendent Sprinklers must be in-
stalled in accordance with the following
instructions.
Step A.
After installing the Style 70
Mounting Plate over the sprinkler
threads with pipe-thread sealant ap-
plied to the pipe threads, hand-tight-
en the sprinkler into the sprinkler tting.
Step B.
Tighten the sprinkler into the
sprinkler tting using only the W-Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench ats.
Step C.
After ceiling installation and
nishing, slide on the Style 70 Closure
over the Series TY-FRB Sprinkler and
push the Closure over the Mounting
Plate until its ange comes in contact
with the ceiling.
*
*
*
*
*
PENDENTCROSS SECTION UPRIGHT RECESSED PENDENT
2-7/8" (73,0 mm) DIA.
53 mm
2
4
5
6
1
3
FLATS
WRENCH
38 mm
55 mm
ESCUTCHEON PLATE
SEATING SURFACE
8 mm
MAKE-IN
NOMINAL
or adjacent to orice seat on Frame
Temperature rating is indicated on Deector1
2
Sealing Assembly
Button
Frame
-
-Bulb:
3-
4-
6-Deector
Compression5 -
5 mm Dia. for TY-B
3 mm Dia. for TY-FRB
RECESSED ESCUTCHEON
STYLE 70
Screw
ISO
7-R 3/8
WRENCH RECESS
(USE END "A"
ONLY)
57 mm DIA.
73 mm DIA.
SPRINKLER
MOUNTING
CLOSURE SERIES
SURFACE
FACE OF
FITTING
18 ± 6 mm
3,2 mm
20 mm
32 mm
PLATE
MOUNTING
6 mm
18 mm
TY-B or TY-FRB
RECESS
WRENCH
WITH SPRINKLER
ENGAGEMENT
IN TO ENSURE
WRENCHING AREA
PUSH WRENCH
FIGURE 1
SERIES TY-B (5 MM BULB) & TY-FRB (3 MM BULB) 10 MM ORIFICE
UPRIGHT AND PENDENT SPRINKLERS
FIGURE 2
SERIES TY-B (5 MM BULB) & TY-FRB (3 MM BULB) 10 MM ORIFICE
STYLE 70 RECESSED ESCUTCHEON, ISO 7/1-R 3/8
FIGURE 4
W-TYPE 6
SPRINKLER WRENCH
FIGURE 3
W-TYPE 7 RECESSED
SPRINKLER WRENCH
GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
TFP670
Page 4 of 4
Copyright © 2015 Tyco Fire Products, LP. All rights reserved.
TEFLON is trademark of The DuPont Corporation.
Care and
Maintenance
The TYCO Series TY-B and TY-FRB
must be maintained and serviced in
accordance with this section.
NOTICE
Before closing a fire protection sys-
tem main control valve for maintenance
work on the fire protection system that
it controls, obtain permission to shut
down the affected fire protection sys-
tem from the proper authorities and no-
tify all personnel who may be affected
by this action.
Absence of an escutcheon, which is
used to cover a clearance hole, can de-
lay the time to sprinkler operation in a
fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
ed sprinklers must be replaced. Sprin-
klers that have been exposed to corro-
sive products of combustion, but have
not operated, should be replaced if
they cannot be completely cleaned by
wiping the sprinkler with a cloth or by
brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers before, during, and
after installation. Sprinklers damaged
by dropping, striking, wrench twist/
slippage, or the like, must be replaced.
Also, replace any sprinkler that has a
cracked bulb or that has lost liquid from
its bulb. (Ref. Installation Section).
The owner is responsible for the in-
spection, testing, and maintenance of
their re protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associa
-
tion (e.g., NFPA 25), in addition to the
standards of any other authorities hav-
ing jurisdiction. Contact the installing
contractor or sprinkler manufacturer
regarding any questions.
Automatic sprinkler systems are recom-
mended to be inspected, tested, and
maintained by a qualied Inspection
Service in accordance with local re-
quirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-re.com.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and part
number (P/N).
Sprinkler Assemblies
Specify: (SIN), Series (TY-B or TY-FRB),
(Standard or Quick Response), 10 mm
Orice, (temperature rating), (Pen-
dent or Upright) Sprinkler with (nish),
P/N (from Table B)
Recessed Escutcheon
Specify: Style 70 Recessed Escutcheon
with (specify*) nish, P/N (specify*)
* Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
SPRINKLER
FINISH
1NATURAL BRASS
3PURE WHITE (RAL9010)*
POLYESTER
4SIGNAL WHITE (RAL9003)
POLYESTER
9CHROME PLATED
* Eastern Hemisphere sales only
TEMPERATURE
RATINGS
135 135°F (57°C)
155 155°F (68°C)
175 175°F ( 79°C)
200 200°F (93°C)
286 286°F (141°C)
360 360°F (182°C)
(5 mm Bulb Only)
SIN
580 UPRIGHT 5 mm Bulb TY2108
581 PENDENT 5 mm Bulb TY2208
380 UPRIGHT 3 mm Bulb TY2109
381 PENDENT 3 mm Bulb TY2209
P/N 57 – XXX – X – XXX
TABLE B
SERIES TY-B (5 MM BULB) & TY-FRB (3 MM BULB) 10 MM ORIFICE
UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION

Other manuals for TY-B Series

22

This manual suits for next models

5

Other Tyco Irrigation System manuals

Tyco DSB-2 User manual

Tyco

Tyco DSB-2 User manual

Tyco ESFR-17 User manual

Tyco

Tyco ESFR-17 User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco Rapidresponse LFII Series User manual

Tyco

Tyco Rapidresponse LFII Series User manual

Tyco FTR-1 User manual

Tyco

Tyco FTR-1 User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco ESFR-25 User manual

Tyco

Tyco ESFR-25 User manual

Tyco Grinnell F692 DESIGNER User manual

Tyco

Tyco Grinnell F692 DESIGNER User manual

Tyco Power Pro Series User manual

Tyco

Tyco Power Pro Series User manual

Tyco WP8360 User manual

Tyco

Tyco WP8360 User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco RAPID RESPONSE Series User manual

Tyco

Tyco RAPID RESPONSE Series User manual

Tyco 16.8 K-factor User manual

Tyco

Tyco 16.8 K-factor User manual

Tyco DS-2 Series User manual

Tyco

Tyco DS-2 Series User manual

Tyco DS-1 Series User manual

Tyco

Tyco DS-1 Series User manual

Tyco Ultra K17 User manual

Tyco

Tyco Ultra K17 User manual

Tyco TY-QRF-EU User manual

Tyco

Tyco TY-QRF-EU User manual

Tyco ESFR-22 User manual

Tyco

Tyco ESFR-22 User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco G2 User manual

Tyco

Tyco G2 User manual

Tyco Ultra K17 User manual

Tyco

Tyco Ultra K17 User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco DS-1 TY3255 Operating and maintenance instructions

Tyco

Tyco DS-1 TY3255 Operating and maintenance instructions

Popular Irrigation System manuals by other brands

Viking HORIZON H-3 Technical data

Viking

Viking HORIZON H-3 Technical data

Hunter ST Series owner's manual

Hunter

Hunter ST Series owner's manual

Rain elite 9 VDC instructions

Rain

Rain elite 9 VDC instructions

Tyco Fire Product TFR MAX instruction manual

Tyco Fire Product

Tyco Fire Product TFR MAX instruction manual

Viking MicrofastHP VK341 Technical data

Viking

Viking MicrofastHP VK341 Technical data

Kärcher WU 90/72 manual

Kärcher

Kärcher WU 90/72 manual

Autopot 36Pot system Set-up guidelines

Autopot

Autopot 36Pot system Set-up guidelines

Tyco Fire Product CENTRAL CC1 instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL CC1 instruction manual

Reliable LT56 Series manual

Reliable

Reliable LT56 Series manual

Tyco Fire Product CENTRAL LD instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL LD instruction manual

Tyco Fire Product Gem A instruction manual

Tyco Fire Product

Tyco Fire Product Gem A instruction manual

Tyco Fire Product CENTRAL BV4-QREC instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV4-QREC instruction manual

Tyco Fire Product CENTRAL TY-B Series instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL TY-B Series instruction manual

Tyco Fire Product CENTRAL ELO-16 GB FR instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-16 GB FR instruction manual

Netafim GYRONET TURBO user manual

Netafim

Netafim GYRONET TURBO user manual

Reliable DD56-6 Bulletin

Reliable

Reliable DD56-6 Bulletin

Tyco Fire Product TY-QRF instruction manual

Tyco Fire Product

Tyco Fire Product TY-QRF instruction manual

Eden 96122EDAMZ quick start guide

Eden

Eden 96122EDAMZ quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.