Tyco LFII Series User manual

Page 1 of 6 APRIL 2022 TFP461
Worldwide
Contacts
www.tyco-fire.com
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/series-lfii-
res-4_4-k-hori-side-dry-type
Series LFII Residential Sprinkler
4.4 K-factor Horizontal Sidewall, Dry Type
Wet Pipe System
The Series LFII Dry Type Residential
Horizontal Sidewall Sprinklers are typ-
ically used where sprinklers and/or a
portion of the connecting piping are
exposed to freezing temperatures (for
example, horizontal sprinkler supplied
from wet systems into unheated areas).
The Series LFII Dry Type Residen-
tial Horizontal Sidewall Sprinklers are
intended for use in Residential Sprin-
kler systems for one- and two-family
dwellings and mobile homes per NFPA
13D; residential sprinkler systems for
residential occupancies up to and
including four stories in height per
NFPA 13R; or, sprinkler systems for the
residential portions of any occupancy
per NFPA 13.
The recessed version is intended
for use in areas with finished walls.
It employs a two-piece Style 20
Recessed Escutcheon. The Recessed
Escutcheon provides 1/4 in. (6,4 mm)
of recessed adjustment or up to 1/2 in.
(12,7 mm) of total adjustment from the
flush mounting surface position. The
design of this escutcheon provides a
level of flexibility in adjusting sprinkler
supply connections.
The Series LFII Dry Type Residential
Horizontal Sidewall Sprinklers have
been designed with heat sensitivity and
water characteristics proven to help in
the control of residential fires and to
improve the chance for occupants to
escape or be evacuated.
Corrosion-resistant coatings, where
applicable, are utilized to extend the life
of copper alloy sprinklers beyond that
which would otherwise be obtained
when exposed to corrosive atmo-
spheres. Although corrosion-resistant
coated sprinklers have passed the
standard corrosion tests of the appli-
cable Approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently,
it is recommended that the end user
be consulted with respect to the suit-
ability of these coatings for any given
corrosive environment. The effects of
General
Description
The TYCO Series LFII Dry Type Res-
idential Horizontal Sidewall (HSW)
Sprinklers (TY2335) are dry-type dec-
orative, fast response, frangible bulb
sprinklers designed for use in residen-
tial occupancies such as homes, apart-
ments, dormitories, and hotels.
ambient temperature, concentration of
chemicals, and gas/chemical velocity
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
NOTICE
The Series LFII Dry Type Residential
Horizontal Sidewall Sprinklers (TY2335)
described herein must be installed and
maintained in compliance with this doc-
ument and the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA), in addition to
the standards of any authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN)
TY2335

TFP461
Page 2 of 6
Operation
When the TYCO Series LFII Dry Type
Residential Horizontal Sidewall Sprin-
kler is in service, water is prevented
from entering the assembly by the Plug
with Sealing Assembly (see Figure 1) in
the Inlet of the Sprinkler.
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb to release the Bulb Seat. The
system’s water pressure is then able to
unseat the Plug with Sealing Assem-
bly. The Plug Spring turns the Plug with
Sealing Assembly aside, allowing the
sprinkler to activate and flow water.
Design
Criteria
The TYCO Series LFII Dry Type Resi-
dential Horizontal Sidewall Sprinklers
(TY2335) are UL and C-UL Listed for
installation in accordance with this
section.
Residential Sprinkler Design Guide
When conditions exist that are outside
the scope of the criteria provided in
this section, refer to the technical data
sheet entitled Residential Sprinkler
Design Guide (TFP490) for the manu-
facturer’s recommendations that may
be acceptable to the local authority
having jurisdiction.
System Type
Wet Pipe
Hydraulic Design
(NFPA 13D and 13R)
For systems designed to NFPA 13D or
NFPA 13R, the minimum required sprin-
kler flow rates are given in Table A as a
function of temperature rating and the
maximum allowable coverage areas.
The sprinkler flow rate is the minimum
required discharge from each of the
total number of design sprinklers, as
specified in NFPA 13D or NFPA 13R.
Hydraulic Design
(NFPA 13)
For systems designed to NFPA 13, the
number of required design sprinklers is
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is the greater of the following:
•
ow rates listed in Table A as a
function of temperature rating and
the maximum allowable coverage
area.
•
minimum discharge of 0.1 gpm/ft²
over the design area comprised
of the four most hydraulically
demanding sprinklers for the actual
coverage areas protected by four
sprinklers.
Obstruction to Water Distribution
Sprinklers are to be located in accor-
dance with the obstruction rules of
NFPA 13D, 13R, and 13 as applicable
for residential sprinklers as well as with
the obstruction criteria described within
the Technical Data Sheet TFP490.
Operational Sensitivity
The sprinkler must be located relative
to the mounting surface as shown in
Figures 2 and 3.
Sprinkler Spacing
The minimum lateral spacing between
sprinklers is 8 ft (2,4 m). The maximum
lateral spacing between sprinklers
cannot exceed the length of the cov-
erage area (see Table A) hydraulically
calculated (for example, a maximum of
12 ft for a 12 ft x 12 ft coverage area or
18 ft for a 18 ft x 20 ft coverage area.)
Sprinkler Fittings
The following fittings may be used:
•
the 1 in. NPT outlet or run of a
malleable or ductile iron threaded
tee ttings that meet the dimen-
sional requirements of ANSI B16.3
(Class 150)
•
the 1 in. NPT outlet or run of a cast
iron threaded tee tting that meet
the dimensional requirements of
ANSI B16.4 (Class 125)
Technical
Data
Approvals
UL and C-UL Listed
Certified to all requirements of
NSF/ANSI 61
Note: Sprinklers with a polyester finish are
UL and C-UL Listed as corrosion-resistant
sprinklers.
See the Design Criteria section for details
on these approvals.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=4.4 GPM/psi½(63,4 LPM/bar½)
Inlet Thread Connections
1 in. NPT
ISO 7-R 1
Sprinkler Temperature Rating
155°F (68°C)
Finishes
Natural Brass, Signal White Polyester
Coated, or Chrome Plated
Order Lengths
Minimum: 3-3/4 in. (95,3 mm)
Maximum: 24 in. (609,6 mm)
Physical Characteristics
Inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Brass
Plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Brass
Yoke....................... Stainless Steel
Casing ....................Galvanized Steel
Insert . . . . . . . . . . . . . . . . . . . . . . . . . . . Bronze
Bulb Seat. . . . . . . . . . . . . . . . . . . Stainless Steel
Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . . . . . . . . . . . . . .Brass
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . . Brass
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Guide Tube . . . . . . . . . . . . . . . . . Stainless Steel
Water Tube . . . . . . . . . . . . . . . . . Stainless Steel
Bushing . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Plug Spring . . . . . . . . . . . . . . . . . Stainless Steel
Sealing Assembly ..Beryllium Nickel w/TEFLON
Escutcheon . . . . . . . . . . . . . . . . . . .Carbon Steel
WATER
TUBE
VENT
HOLE
GUIDE
TUBE
BULB
SEAT
COMPRESSION
SCREW
3 mm
BULB
INLET
BAND
PLUG
SPRING
ESCUTCHEON
MOUNTING PLATE
INLET
YOKE
CASINGBUSHING
FRAMEPLUG WITH
SEALING
ASSEMBLY
DEFLECTOR
FIGURE 1
SERIES LFII DRY TYPE
RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLERS (TY2335) ASSEMBLY

TFP461
Page 3 of 6
Do not install the Series LFII Dry Type
Residential Horizontal Sidewall Sprin-
klers into elbow fittings. The Inlet of the
sprinkler can contact the interior of the
elbow, potentially damaging the Inlet
seal.
Only use the configuration in Figure 4
where the sprinkler fitting and water-
filled pipe at the sprinkler fitting are
not subject to freezing and where
the length of the Series LFII Sprinkler
has the minimum exposure length per
Figure 5. See the Exposure Length
section and Table B.
•
the 1 in. NPT outlet of a GRINNELL
Figure 730 Mechanical Tee in wet
pipe systems only
•
the 1 in. NPT CPVC outlet of a
1 in. x 1 in. x 1 in. NPT Sprinkler
Head Adapter Tee (P/N 80249) in
wet systems only
•
the 1 in. NPT CPVC outlet of a
1 in. x 1 in. NPT Female Adapter
(P/N 80145) in wet systems only
• the 1 in. NPT outlet of a 1 in. x 1 in.
x 1 in. NPT CPVC Sprinkler Head
Adapter Tee (P/N 80259) in wet pipe
systems only
Notes:
a. For coverage area dimensions less than or between those indicated, use the minimum required ow for the next highest coverage area for which hydraulic design criteria are
stated.
b. This dimension refers to the Width (backwall where the sprinkler is located) times the Length (horizontal throw of the sprinkler).
c. The requirement is based on minimum ow in gpm (lpm) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. See Hydraulic
Design under the Design Criteria section for details.
d. For NFPA 13 residential applications, the greater of 0.1 gpm/ft² over the design area or the ow in accordance with the criteria in this table must be used.
e. For sprinklers installed prior to May 1, 2015, a ow rate of 17 gpm at a pressure of 14.9 psi may be used.
f. For sprinklers installed prior to May 1, 2015, a ow rate of 15 gpm at a pressure of 11.6 psi may be used.
g. For sprinklers installed prior to May 1, 2015, a ow rate of 19 gpm at a pressure of 18.6 psi may be used.
h. For sprinklers installed prior to May 1, 2015, a ow rate of 20 gpm at a pressure of 20.7 psi may be used.
j . For sprinklers installed prior to May 1, 2015, a ow rate of 25 gpm at a pressure of 32.3 psi may be used.
NOTICE
Do not install the Series LFII Dry Type
Residential Horizontal Sidewall Sprin-
klers into any other type fitting without
first consulting Johnson Controls Tech-
nical Services. Failure to use the appro-
priate fitting may result in the following:
• failure of the sprinkler to operate
properly due to formation of ice over
the Inlet Plug or binding of the Inlet
Plug.
• insufficient engagement of the
inlet pipe threads with consequent
leakage.
Exposure Length
When using Series LFII Dry Type Resi-
dential Horizontal Sidewall Sprinklers
in wet pipe sprinkler systems to protect
areas subject to freezing temperatures,
use Table B to determine the appro-
priate exposed sprinkler barrel length
to prevent water from freezing in the
connecting pipes due to conduction.
The exposed barrel length measure-
ment must be taken from the face of
the sprinkler fitting to the surface of the
structure or insulation that is exposed
to the heated area. See Figure 5 for an
example.
Clearance Space
When connecting an area subject to
freezing and an area containing a wet-
pipe sprinkler system, the clearance
space around the sprinkler barrel of
Dry Type Residential Sprinklers must
be sealed, in accordance with the
NATIONAL FIRE PROTECTION ASSO-
CIATION. Due to temperature differ-
ences between the two areas, the
potential for the formation of conden-
sation in the sprinkler and subsequent
ice build-up is increased. If this con-
densation is not controlled, ice build-up
can occur that might damage the dry
type sprinkler and/or prevent proper
operation in a re situation.
Use of the Model DSB-2 Dry Sprin-
kler Boot, described in Technical Data
Sheet TFP591 and shown in Figures 4
and 5, can provide the recommended
seal.
Maximum
Coverage Area(a,b)
Width x Length
ft x ft
(m x m)
Maximum
Spacing
ft
(m)
WET PIPE SYSTEM
Minimum Flow and Residual Pressure(c,d)
155°F (68°C)
Flow
gpm
(lpm)
Pressure
psi
(bar)
Deflector to
Ceiling Installation
Type
Minimum
Spacing
ft
(m)
12 x 12
(3,7 x 3,7)
12
(3,7)
13
(49,2)
8.7
(0,60)
4 in. to 6 in.
Recessed
or Plain
Barreled
8
(2,4)
14 x 14
(4,3 x 4,3)
14
(4,3)
14
(53,0)
10.1
(0,70)
16 x 16
(4,9 x 4,9)
16
(4,9)
18(e)
(6 8,1)
16.7(e)
(1,15)
16 x 18
(4,9 x 5,5)
16
(4,9)
21(g)
(79,5)
22.8(g)
(1,57)
16 x 20
(4,9 x 6,1)
16
(4,9)
25
(94,6)
32.3
(2,23)
12 x 12
(3,7 x 3,7)
12
(3,7)
15
(56,8)
11.6
(0,80)
6 in. to 12 in.
14 x 14
(4,3 x 4,3)
14
(4,3)
16(f)
(60,6)
13.2(f)
(0,91)
16 x 16
(4,9 x 4,9)
16
(4,9)
19
(71,9)
18.6
(1,28)
16 x 18
(4,9 x 5,5)
16
(4,9)
22(h)
(83,3)
25(h)
(1,72)
16 x 20
(4,9 x 6,1)
16
(4,9)
30(j)
(113 ,6)
46.5(j)
(3,20)
TABLE A
WET PIPE SYSTEM
SERIES LFII DRY TYPE HORIZONTAL SIDEWALL SPRINKLERS
NFPA 13D, 13R AND 13 HYDRAULIC DESIGN CRITERIA

TFP461
Page 4 of 6
5/16"
(7,9 mm)
CENTERLINE
OF WATERWAY
FITTING
SPRINKLER
FACE OF
5-1/2" to 24" (139,7 to 609,6 mm)
IN 1/4" (6,4 mm) INCREMENTS
ORDER LENGTHS:
SPRINKLER FITTING
CRITERIA SECTION)
(REFER TO DESIGN
2-1/4" (57,2 mm)
MINIMUM
SURFACE
MOUNTING
MAXIMUM
DEFLECTOR TO
6" (152,4 mm)
5/16"
(7,9 mm)
CENTERLINE
OF WATERWAY
(73,0 mm)
2-7/8" DIA.
1-3/4" DIA.
(44,5 mm)
FITTING
SPRINKLER
FACE OF
SPRINKLER FITTING
CRITERIA SECTION)
(REFER TO DESIGN
2-3/16" ± 1/4"
(55,6 ± 6,4 mm)
3-3/4" to 24" (95,3 to 609,6 mm)
IN 1/4" (6,4 mm) INCREMENTS
ORDER LENGTHS:
SURFACE
MOUNTING
FACE OF
PLUG
OUTLET
TO WET
SYSTEM
FITTING
(SEE DESIGN
CRITERIA
SECTION)
SPRINKLER
DSB-2
BOOT
HEATED
AREA
(SEE DESIGN
CRITERIA
SECTION)
FACE OF
SPRINKLER
FITTING
LENGTH
EXPOSURE
DSB-2
BOOT
HEATED
AREA
FIGURE 3
SERIES LFII DRY TYPE RESIDENTIAL HORIZONTAL
SIDEWALL SPRINKLERS WITH STYLE 20 RECESSED ESCUTCHEON
FIGURE 2
SERIES LFII DRY TYPE RESIDENTIAL
HORIZONTAL SIDEWALL SPRINKLERS WITHOUT ESCUTCHEON
FIGURE 5
SPRINKLER BARREL
EXPOSURE LENGTH
FIGURE 4
SPRINKLER FITTING IN
HEATED AREA

TFP461
Page 5 of 6
Installation
TYCO Series LFII Dry Type Residential
Horizontal Sidewall Sprinklers must
be installed in accordance with this
section.
General Instructions
The Series LFII Dry Type Residential
Horizontal Sidewall Sprinklers must
only be installed in fittings that meet
the requirements of the Design Criteria
section. For other important require-
ments regarding piping design and
sealing of the clearance space around
the Sprinkler Casing, see the Design
Criteria section.
Do not install any bulb type sprinkler
if the Bulb is cracked or there is a loss
of liquid from the Bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm).
A leak-tight 1 in. NPT sprinkler joint
should be obtained by applying a min-
imum-to-maximum torque of 20 to 30
lb-ft (26,8 to 40,2 N∙m). Higher levels
of torque can distort the sprinkler Inlet
or Frame with consequent leakage or
impairment of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in an Escutch-
eon Plate by under- or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Note: Install horizontal sidewall sprin-
klers only in the horizontal position
with their centerline of waterway par-
allel to the ceiling. The word TOP on the
Deflector is to face towards the ceiling.
Step 1. With a non-hardening pipe-
thread sealant such as Teflon tape
applied to the inlet threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 2. Wrench-tighten the sprinkler
using a pipe wrench on the Inlet Band
or the Casing (see Figure 1), or using
the W-Type 6 or W-Type 7 Sprinkler
Wrench as follows:
•
For plain-barrel horizontal sidewall
sprinklers, apply the Wrench
Recess End “A” of the W-Type 6
Sprinkler Wrench (see Figure 6) to
the Wrench Flat.
•
For recessed horizontal sidewall
sprinklers, apply the Wrench
Recess of the W-Type 7 Sprinkler
Wrench to the Wrench Flat
(see Figure 7).
Absence of a Recessed Escutch-
eon Plate or a Domed Concealed
Cover Plate to cover a clearance hole
can delay sprinkler operation in a fire
situation.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
A Vent Hole is provided in the Bulb
Seat (see Figure 1) to indicate if the
Series LFII Dry Type Residential Hor-
izontal Sidewall Sprinkler is remain-
ing dry. Evidence of leakage from the
Vent Hole indicates potential leakage
past the Plug with Sealing Assembly
and the need to remove the sprinkler
Ambient
Temperature
Exposed to
Discharge
End of
Sprinkler
Temperatures for
Heated Area(1)
40°F
(4°C) 50°F
(10°C) 60°F
(16°C)
Minimum Exposed
Barrel Length(2),
in.
(mm)
40°F
(4°C) 0 0 0
30°F
(-1°C) 0 0 0
20°F
(-7°C)
4
(100) 0 0
10°F
(-12°C)
8
(200)
1
(25) 0
0°F
(-18°C)
12
(305)
3
(75) 0
-10°F
(-23°C)
14
(355)
4
(100)
1
(25)
-20°F
(-29°C)
14
(355)
6
(150)
3
(75)
-30°F
(-34°C)
16
(405)
8
(200)
4
(100)
-40°F
(-40°C)
18
(455)
8
(200)
4
(100)
-50°F
(-46°C)
20
(510)
10
(255)
6
(150)
-60°F
(-51°C)
20
(510)
10
(255)
6
(150)
Notes:
1. For protected area temperatures that occur
between values listed above, use the next cooler
temperature.
2. These lengths are inclusive of wind velocities up
to 30 mph (18,6 kph).
TABLE B
MINIMUM RECOMMENDED
LENGTHS OF EXPOSED
SPRINKLER BARRELS IN WET
PIPE SYSTEMS
If sprinkler removal is necessary,
remove the sprinkler using the same
wrenching method noted above. Sprin-
kler removal is easier when a non-hard-
ening sealant was used and torque
guidelines were followed. After removal,
inspect the sprinkler for damage.
Step 3. After installation of the gypsum
board or other wall/soffit finish material,
slide the Style 20 Recessed Escutch-
eon Closure over the sprinkler. Push
the closure over the mounting plate
until its flange contacts the wall.
Care and
Maintenance
TYCO Series LFII Dry Type Residential
Horizontal Sidewall Sprinklers (TY2335)
must be maintained and serviced in
accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
WRENCH
RECESS
WRENCH
FLAT
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
WRENCH RECESS
(USE END "A"
ONLY)
FIGURE 7
W-TYPE 7 RECESSED
SPRINKLER WRENCH
FIGURE 6
W-T YPE 6
SPRINKLER WRENCH

TFP461
Page 6 of 6
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a trademark of The Chemours Company FC, LLC
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
to determine the cause of leakage (e.g.,
an improper installation or an ice plug).
Close the fire protection system control
valve and drain the system before
removing the sprinkler.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. See the Installation
section for additional information.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION, for example, NFPA 25,
in addition to the standards of any
authorities having jurisdiction. Contact
the installing contractor or product
manufacturer with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and part number
(P/N).
Horizontal Sidewall
Sprinkler Assemblies
Note: Unless otherwise indicated, see
Table C.
Specify: Series LFII Dry Type Resi-
dential Horizontal Sidewall Sprinkler,
SIN TY2335, with (specify Recessed
or without) Escutcheon, 4.4 K-fac-
tor, Temperature Rating 155°F (68°C),
Sprinkler Finish (specify), Escutcheon
Finish (specify if applicable), Order
Length (specify value per Figure 4
or 5), Inlet Thread Size (1 in. NPT
or ISO 7-R 1), P/N (specify)
Separately Ordered
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench
(Figure 6), P/N 56-000-6-387
Specify: W-Type 7 Recessed Sprinkler
Wrench (Figure 7), P/N 56-850-4-001
Separately Ordered
Escutcheon
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
* Refer to Technical Data Sheet TFP770
P/N163 — XXX — X — XXX
Notes:
1. Use Prex "I" for ISO 7-R 1 Inlet Thread Connection (e.g., I-63-121-9-180)
2. UL and C-UL Listed as corrosion-resistant
ORDER LENGTH
(EXAMPLES)
055 5.50 in.
082 8.25 in.
180 18.00 in.
187 18.75 in.
240 24.00 in.
SPRINKLER
FINISH ESCUTCHEON
FINISH
2NATURAL
BRASS
BRASS
PL ATED
4
SIGNAL WHITE
(RAL9003)
POLYESTER2
SIGNAL WHITE
(RAL9003)
POLYESTER
9CHROME
PL ATED
CHROME
PL ATED
TEMPERATURE
RATING
1155°F (68°C)
SIN
12
HORIZONTAL
SIDEWALL WITH
RECESSED
ESCUTCHEON
TY2335
13
HORIZONTAL
SIDEWALL
WITHOUT
ESCUTCHEON
TY2335
TABLE C
SERIES LFII DRY-TYPE RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLERS
PART NUMBER SELECTION
Other manuals for LFII Series
11
This manual suits for next models
1
Table of contents
Other Tyco Irrigation System manuals

Tyco
Tyco DSB-1 User manual

Tyco
Tyco TY-FRFS User manual

Tyco
Tyco FASTFLEX YN25 User manual

Tyco
Tyco rapidresponse RSV-1 User manual

Tyco
Tyco ESFR-25 User manual

Tyco
Tyco EC-25 User manual

Tyco
Tyco rapid response LFII Series User manual

Tyco
Tyco TY-FRB Series User manual

Tyco
Tyco K17-231 User manual

Tyco
Tyco DS-1 Series User manual