Display name Register
address
(decimal)
Physical
address
(decimal)
Function
code (Hex)
Type Analogue/
Binary
Coding
Actuator status/channel 8
(bit 7)
10008 10007 0x02 Read Binary Unsigned.1 = ON, 0 = Off.
Actuator status/channel 9
(bit 8)
10009 10008 0x02 Read Binary Unsigned.1 = ON, 0 = Off.
Actuator status/channel 10
(bit 9)
10010 10009 0x02 Read Binary Unsigned.1 = ON, 0 = Off.
Actuator status/channel 11
(bit 10)
10011 10010 0x02 Read Binary Unsigned.1 = ON, 0 = Off.
Actuator status/channel 12
(bit 11)
10012 10011 0x02 Read Binary Unsigned.1 = ON, 0 = Off.
Pump/Boiler (bit 12) 10013 10012 0x02 Read Binary Unsigned.1 = ON, 0 = Off.
GPI status (bit 13) 10014 10013 0x02 Read Binary Unsigned.1 = ON, 0 = Off.
Relative humidity (RH)
cooling shutdown, channel 1
10015 10014 0x02 Read Binary Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Relative humidity (RH)
cooling shutdown, channel 2
10016 10015 0x02 Read Binary Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Relative humidity (RH)
cooling shutdown, channel 3
10017 10016 0x02 Read Binary Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Relative humidity (RH)
cooling shutdown, channel 4
10018 10017 0x02 Read Binary Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Relative humidity (RH)
cooling shutdown, channel 5
10019 10018 0x02 Read Binary Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Relative humidity (RH)
cooling shutdown, channel 6
10020 10019 0x02 Read Binary Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Relative humidity (RH)
cooling shutdown, channel 7
10021 10020 0x02 Read Binary Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Relative humidity (RH)
cooling shutdown, channel 8
10022 10021 0x02 Read Binary Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Relative humidity (RH)
cooling shutdown, channel 9
10023 10022 0x02 Read Binary Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Relative humidity (RH)
cooling shutdown, channel
10
10024 10023 0x02 Read Binary Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Relative humidity (RH)
cooling shutdown, channel
11
10025 10024 0x02 Read Binary Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
Relative humidity (RH)
cooling shutdown, channel
12
10026 10025 0x02 Read Binary Unsigned.
1 = Cooling shutdown, 0 = Cooling
available.
20 | Uponor Smatrix Base PRO Controller X-148 Modbus RTU | Installation manual