To connect a BMS to the Uponor Smatrix Base PRO controller some
preparations must be made.
1. Connect and register thermostats, and system devices, to the
controllers.
Caution!
If an Uponor Smatrix Base PRO Interface I-147 is
connected, it must be unregistered and disconnected.
Note
Make sure that the thermostats are registered to
consecutive channels so the BMS can read and write
all channels in an efcient way. That is, addressing
multiple channels in one message.
See Uponor Smatrix Base PRO installation and operation manual,
or quick guide, for information registering devices to the controller.
2. Update the software of the controllers with the Modbus RTU
compatible software (available on the Uponor website).
See separate documentation for information on how to update the
software of a controller.
3. Press the <, OK, and >buttons simultaneously (for about
10 seconds) until the power LED ashes, and all channel LEDs
turn off. The controller has been reset to factory default.
4. Edit the U_BMS.txt le, on the controller microSD card, to setup
the controller Modbus RTU interface.
Available settings (default in bold):
- BMS Slave address: 1to 247
- BMS Baud rate: 19200 or 9600
- BMS Parity: even, odd, or no
- Heat pump integration via BMS: off or on
on = enables dynamic heat curve offset in integrated heat
pump, and integrated heat pump defrost state.
- Exclude zone from heat curve offset calculation:
0, or 1 through 12 (0 = no channel)
Select master channels of the zones (lowest numbered
channel in the zone) to exclude.
The zone subchannels follow the state of the master
channel.
Example: 3,5,12 = exludes channels with master channels
3, 5 and 12.
- Bypass zone: 0, or 1 to 12 (0 = no channel, example: 3,12)
Select master channels of the zones (lowest numbered
channel in the zone) to bypass, MAXIMUM 2 channels.
The zone subchannels follow the state of the master
channel.
Example: 4,12 = bypasses zones with master channels 4
and 12.
- Ceiling cooling channel: 0, or 1 to 12 (0 = no channel,
example: 1,4,10)
Select the channels which controls ceiling cooling in the
zones. The zone subchannels will not follow the state of the
master channel.
Example: 1,4,10 = set ceiling cooling to channels 1, 4 and
10.
Repeat for each Base PRO controller in the system.
Caution!
Do not remove the microSD card while the controller
is powered on.
Note
Make sure the correct slave address is set (between
1 and 247, unique for each controller in the system),
and that the other setting match the Modbus RTU
settings in the BMS.
5. Connect the controllers to each other using the Base PRO
controller system device bus.
6. Connect the Base PRO system to the BMS.