11
5774 469 v1.0
Solar Control Module SM1, Installation and Service Connections
DHW heating with two mono mode DHW tanks
Function description
DHW heating with solar energy
If the temperature differential between collector
temperature sensor eQ and DHW tank temperature sensor
qQ is greater than the start temperature differential
(coding address 00), solar circuit pump eE starts and
DHW tank 1 qP is heated.
Solar circuit pump eE stops if:
HActual temperature drops below stop temperature
differential (coding address 01)
HMaximum DHW tank temperature is exceeded (coding
address 08)
HThe temperature selected at high limit safety cut-out qW
(if installed) is reached
Transfer pump qT starts if the temperature at temperature
sensor qZ has reached the start temperature differential
of the differential temperature control 2 (code 22).
The water heated in DHW tank 1 qP is supplied to DHW
tank 2 qI. This means DHW tank 2 qI is also heated
by solar energy.
Transfer pump qT stops if the temperature at temperature
sensor qZ has fallen below the stop temperature differential
of the differential temperature control 2 (code 23).
System Example 2
Additional function for DHW heating
The requirements for the additional function are achieved
through circulation pump qT.
Suppression of DHW tank 2 heating by the boiler with
DHW heating Reheating suppression takes place in two
stages.
Heating DHW tank 2 qI by boiler 1is suppressed
as soon as DHW tank 1 qP is heated by collectors eP.
For this, the set DHW tank temperature for reheating
is reduced by boiler 1. After solar circuit pump eE
has been switched off, suppression remains active
for a certain time.
Boiler installation and service instructions
In the case of uninterrupted heating by the collectors
eP (> 2 h), boiler 1will only heat if the set DHW
temperature selected at boiler control unit 2(coding
address “67”) is not achieved.
A third set DHW temperature can be specified via coding
address “67” [setting range 50 to 203° F (10 to 95° C)].
This value must be below the first set DHW temperature.
DHW tank 2 qI will only be heated by boiler 1, if this
set value is not achieved by the solar thermal system.
DHW heating without solar energy
DHW tank 2 qI is heated by boiler 1.
The DHW tank thermostat with DHW tank temperature
sensor qO of boiler control unit 2starts the internal
circulation pump and changes the 3-way diverter valve
to DHW heating.
Note: Coding address 00 can be set to min. 0.9° F
(0.5 K) above coding address 01.
Coding address 01 can be set to max. 0.9° F
(0.5 K) below coding address 00.
Function/system components
Code in solar group
Adjust Factory set condition
Start temperature differential for solar circuit pump at
connection sF. Factory set condition 8 K (14.4° F)
00:... 00:8
Stop temperature differential for solar circuit pump at
connection sF. Factory set condition 4 K (7.2° F)
01:... 01:4
Solar circuit pump type:
HSolar circuit pump is not speed-controlled
HSolar circuit pump is speed-controlled with wave pack control
HSolar circuit pump is speed-controlled with PWM control
--
02:1
02:2
02:0
02:0
02:0
Maximum DHW tank temperature (Factory set condition 60° C) 08:... 08:60
Start temperature differential with central heating
backup. Factory set condition 8 K (14.4° F)
22:... 22:8
Stop temperature differential with central heating
backup. Factory set condition 4 K (7.2° F)
23:... 23:4
Required codes at the oil/gas boiler control unit