ViM KUBAIR F400 ECOWATT CC User manual

NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
TECHNICAL MANUAL
INSTALLATION | CONNECTION| COMMISSIONING | MAINTENANCE |
AFNOR CERTIFICATION
ISO 14001
Environnement
AFNOR CERTIFICATION
ISO 9001
Qualité
KUBAIR®F400 ECOWATT®
Smoke extract unit F400 - 120 (400°C 120 min)

2/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
INDICE
1. GENERAL........................................................................................................................................... 3
1.1 Disclaimers............................................................................................................................... 3
1.2 Safety instructions.................................................................................................................... 3
1.3 Acceptance – Storage.............................................................................................................. 3
1.4 Warranty................................................................................................................................... 4
2. PRODUCT PRESENTATION.............................................................................................................. 4
3. INSTALLATION .................................................................................................................................. 5
3.1 Dimensions and weight (mm)................................................................................................... 5
3.2 Summary charts of assembly and accessories........................................................................ 6
3.3 Accessories (dimensions in mm).............................................................................................. 8
3.4 Handling ................................................................................................................................. 12
3.5 Casing assembly.................................................................................................................... 12
4. ELECTRICAL CONNECTION.......................................................................................................... 13
4.1 Preliminary precautions.......................................................................................................... 13
4.2 Electrical characteristics......................................................................................................... 13
4.3 Wiring of INTZ safety switch................................................................................................... 13
5. COMMISSIONING AND SETTING................................................................................................... 14
5.1 Preliminary precautions.......................................................................................................... 14
5.2 Controllers.............................................................................................................................. 15
5.3 Operation for smoke extraction .............................................................................................. 20
5.4 Ventilation fault indication ...................................................................................................... 20
5.5 KUBAIR®F400 ECOWATT® Single-phase - VAV variable ow rate control ............................ 20
5.6 KUBAIR®F400 ECOWATT® Single-phase - CAV constant ow rate control ........................... 25
5.7 KUBAIR®F400 ECOWATT®Single-phase - COP constant pressure control......................... 28
5.8 KUBAIR®F400 ECOWATT® 3-phases - VAV variable ow rate control.................................. 30
5.9 KUBAIR®F400 ECOWATT® 3-phases - CAV constant ow rate control ................................ 35
5.10 KUBAIR®F400 ECOWATT®3-phases - COP constant pressure control ................................. 38
6. MAINTENANCE................................................................................................................................ 41
6.1 Maintenance frequency.......................................................................................................... 42
6.2 Spare parts KUBAIR®F400 ECOWATT®............................................................................... 42
7. WASTE MANAGEMENT.................................................................................................................. 43
7.1 Treatment of Packagings and non dangerous wastes ........................................................... 43
7.2 Treatment of a Professional WEEE........................................................................................ 43

3/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
1. GENERAL
1.1 Disclaimers
This product has been manufactured according to rigorous technical rules of safety in conformity with EC
standards. The EC declaration may be downloaded from the Internet site (address given on the last page).
Before installing and using this product, carefully read these instructions, which contain important indications
for your safety and the user’s safety during the installation, commissioning and maintenance of this product.
Once the installation is achieved, keep this manual handy nearby the machine for future consultation.
This product must be installed (installation, connections, commissioning, maintenance) and all other inter-
ventions performed by a professional applying recognized good practice procedures, and respecting the
standards and safety regulations in force. The installation must be made in accordance with the prescrip-
tions indicated in the Electromagnetic Compatibility (EMC) and Low Voltage (LV) Directives.
We advise all people exposed to risks to scrupulously respect the accident prevention standards. The ma-
nufacturer may not be held liable for any human injury and/or material damage resulting from the non-res-
pect of the safety instructions or from a change made on the product.
Smoke extract unit KUBAIR®F400 ECOWATT®are intended for smoke extraction and ventilation applica-
tions in residential buildings, tertiary buildings, industrial buildings and professional kitchens:
• Outdoor installation
• Environmental temperature range: -10°C / +45°C
If the unit remains turned on, minimum temperature is -20°C.
• Max temperature of extracted air in permanent operation: 120°C
• Relative humidity: min 5% - max 95% non-condensing
• Atmosphere not potentially explosive
• Low salinity atmosphere, with no corrosive chemical agents
1.2 Safety instructions
• Wear suitable PPE (Personal Protective Equipment) before any intervention.
• Before installing the roof fan and its accessories, make sure that the support and the location are
suciently resistant to withstand the unit’s weight and the accessories, if any.
• Do not remove mesh grilles to access the impeller before cutting o the electric power supply with
the safety switch.
• If the work is to be done inside the device, cut o the electric power supply with the main circuit brea-
ker and make sure that nobody can accidentally switch it back on.
• Make sure that moving parts are stopped.
• Make sure that the impeller is not accessible from connection tappings (connection duct or mesh
protection).
Before starting, check the following points:
• Make sure that the device does not contain any foreign body.
• Make sure that all the components are attached to their original locations.
• Check manually that the impeller does not rub or is not blocked.
• Make sure that the mesh protection are in place.
• Make sure that the ground connection is connected.
1.3 Acceptance – Storage
In case of missing items or delivery of non conforming, partially or totally damaged products, the Buyer
shall make, in accordance with article 133-3 of the French Commercial Code, reservations in writing on the
transporter receipt and conrm them within seventy-two (72) hours by registered letter along with a copy
addressed to the seller. Should the Buyer fail to make reservations when he receives the equipment, he
will not be allowed to make any future claim against us.
The product must be stored protected from the weather, shocks and dirt due to splashings or splatterings
of any kind during transport from the supplier to the end customer, and onto the worksite before installation.

4/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
1.4 Warranty
The equipment is warranted for twelve (12) months – Parts only – from date of manufacture.
VIM agrees to replace parts or the equipment whose operation is recognised defective by our departments,
excluding all damages or penalties, such as operating losses, commercial prejudice, or other intangible or
indirect losses.
Our warranty does not cover: (1) defects resulting from an abnormal use or an use not conforming to the
recommendations indicated in our manuals; (2) defects observed following normal wear; (3) incidents
caused by negligence, lack of monitoring or maintenance; (4) defects due to the inappropriate installation
of the devices or unsuitable pre-installation storage conditions.
In any case, VIM may not be held liable for transformed or repaired equipment even partially.
2. PRODUCT PRESENTATION
EC Certicate F400 -120 N° 1812-CPR-0040, according to European Standard NF EN 12101-3
Approved F400 120 (400°C 120 min)
• KUBAIR®F400 ECOWATT®CC : complete unit with multi-directio-
nal suction plenum, with horizontal or vertical axis motor.
• KUBAIR®F400 ECOWATT® MV : single ventilation unit, with hori-
zontal or vertical axis motor.
• 6 sizes : 355 / 400 / 450 / 500 / 630 / 710.
• Flowrates from 500 to 24 000 m3/h.
Construction
• Detachable galvanised steel sheet panels.
• Modular structure of aluminium sections.
• Connection by 2 KUBZ 12 plain anges which are included.
• High performance galvanised steel reaction turbine, mounted by direct coupling with the motor.
Motor
• ECOWATT® motor, F class, 3 phases with remote IP55 controller :
-1 phase 230V 50/60Hz controller input for sizes 355 up to 450.
-3 phases 400V 50/60Hz controller input for sizes 500 up to 710.
• Thermal protection tted within the controller.
Kitchen Option
The kitchen option includes a reinforced seal, a double skin panel (insulation option available) and a drain
to dispose of wash water. The drain should be installed at the bottom of the casing to allow the wash water
to be eectively discharged.

5/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
3. INSTALLATION
3.1 Dimensions and weight (mm)
KUBAIR
®
F400 ECOWATT
®
MV
Assembly with horizontal motor axis
A
BH
F
C
D
J
E
K
Tipping risk during
handling operations
Assembly with vertical motor axis(*)
56
A
L
BV
A
C
D
G
KUBAIR
®
F400 ECOWATT
®
CC
Assembly with horizontal motor axis
A
BH
F
D
J
C
EC
KC
Assembly with vertical motor axis(*)
55
A
C
H
C
L
BVC
GC
A
C
D
(*) The unit with vertical motor axis must not be tted with motor down.
Size A BH BV BVC C D E EC F G GC H J K KC L Weight
MV (Kg) Weight
CC (Kg)
Naked Insulated Naked Insulated
355 627 695 327 645 263 559 606 790 660 31 50 315 102 826 1103 321 45 48 65 71
400 699 767 361 678 297 631 606 864 732 31 50 349 102 860 1170 321 56 60 79 87
450 779 847 392 738 326 711 606 990 812 31 50 378 102 892 1230 321 73 78 98 108
500 858 925 424 784 338 768 700 1039 890 42 62 402 112 954 1294 351 94 100 121 132
630 10661133 488 912 403 977 700 11831098 42 62 466 112 10181422 351 133 140 177 195
710 11941261 551 1032 462 1104 906 13251226 42 62 526 112 10701533 446 159 168 279 303

6/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
3.2 Summary charts of assembly and accessories
KUBAIR
®
F400 ECOWATT
®
CC
KUBZ 04
KUBZ 02
MSCZ
MSDZ
KUBZ 12
KUBZ 12
KUBZ 01
KUBZ 04
KUBZ 12
KUBZ 07
KUBAIR
®
F400 ECOWATT
®
MV
KUBZ 03
KUBZ 12
KUBZ 08
KUBZ 01
KUBZ 12
KUBZ 07
KUBZ 03
The TCDZ accessories on the diagram below can be used with the KUBAIR®F400 ECOWATT®MV with
a vertical axis motor: (example below)
KUBZ 08
KUBZ 12
KUBZ 11
TCDZ 05
KUBZ 12
TCDZ 05
TCDZ 04

7/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
KUBAIR
®
F400 ECOWATT
®
MV
with vertical axis motor
TCDZ01
TCDZ05*
TCDZ03
TCDZ03
SIL
TCDZ 04 TCDZ 07 TCDZ 02 TCDZ 09
ou ou
ou
ou ou
Optional accessory according to selection.
TCDZ08

8/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
3.3 Accessories (dimensions in mm)
Circular exible spool piece Rectangular exible spool piece
E
Ø F
E
A+3
B+3
AB
B
A
C
Standard support for horizontal axis motor:
This support allows to x the unit on the oor with motor
in horizontal axis position. Relocate on the 2 unit corners
opposite motor side 2 unit xings and replace the 2 others
with the 2 xings provided with the KUBZ01. Those 4 xings
are screwed to the unit with 16 self-drilling screws 4.8x12
provided. The 2 support arms are to be xed on the 4 unit
xings with their 4 screws M8 x 15 provided.
A
B
Connecting ange
This connecting ange is attached to the plain ange at its
4 corners for the purpose of attaching a sheath.
A
A
ØF
Circular connection to the MV suction, horizontal axis
motor:
ThisconnectionisusedwiththeKUBAIR®F400ECOWATT®
MV for a sheath connection which does not have an ups-
tand and which does not bear the weight of the casing.
The TCDZ 01 allows for this connection by bearing the
casing for sizes 355 and 400, vertical axis motor.
A+3
B+
3
H
Ø F
A+3
B+3
H
ØF
ØF
A+3
B+3
H
Rigid straight or errant circular connection
ØA
H
S
G
Fz
B
C
d
ØA
H
S
G
Fz
B
C
d
Vibration isolating devices
4 vibration isolating devices supplied with 4 screws to
attach them to the casing.
AB
C
Capot KUBAIR®
The motor cowl is used for external installations. It is
screwed (screws supplied) onto the motor support panel.
MSDZ MSCZ
KUBZ 01
KUBZ 02
KUBZ 03
KUBZ 04
KUBZ 05
KUBZ 06

9/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
C
A
B
D
B
A
Rain guard with bird guard
These guards are attached after the supplied plain ange
(KUBZ 12) has been detached from the casing.
C
AA
B
ØD
75 75
EØ12
Double suction plenum
To be bolted under the casing, without any accessory
between the KUBZ 11 and the casing.
A
B
J
Plain ange for spool piece
2 plain anges are supplied already mounted on the air
delivery and suction. Other plain anges can be supplied
and mounted.
AB
B
A
C
Covering - horizontal axis motor
Assembly of the cover: the cover is attached with 4 (MV
version) or 8 (CC version) 4.8 x 12 self-drilling screws
which are supplied.
Dimensions (mm) and weight (kg)
KUBZ 01
Model MV CC
A B A B
355
668 50 848 50
400
668 50 823 50
450
668 50 1048 50
500
762 50 1097 50
630
855 50 1242 50
710
977 50 1401 50
KUBZ 15
Model MV CC
A B A B
355
658 391 658 636
400
731 425 731 721
450
812 453 812 790
500
890 485 890 828
630
1098 550 1098 953
710
1226 610 1226 1112
KUBZ 11
Model A B C ØD E Weight
355
622 448 238 355 662 21
400
694 498 260 400 734 25
450
774 555 289 450 814 30
500
852 675 349 560 892 37
630
1060 805 441 630 1100 81
710
1188 885 481 710 1228 99
KUBZ 08
KUBZ 07
KUBZ 11
KUBZ 12
KUBZ 15
MSDZ - MSCZ - KUBZ 02 à 08 - KUBZ 12 Weight
Model A B C D E ØF H J KUBZ
01 KUBZ
03 KUBZ
04 KUBZ
06 KUBZ
07 KUBZ
08
355 559 263 197 194 160 400 670 80 7,0 2,9 7,5 3,6 1,9 2,0
400 631 297 216 213 160 450 670 80 8,2 3,5 8,5 3,6 2,4 2,4
450 711 326 233 234 160 500 670 80 9,7 4,2 9,6 3,6 2,8 2,8
500 768 338 240 249 160 560 670 80 10,6 4,6 10,5 5,4 3,1 3,1
630 977 403 278 305 160 710 670 80 13,8 6,9 13,2 5,4 4,5 4,3
710 1104 462 311 340 160 800 670 80 17,0 8,3 15,1 6,9 5,6 5,3
Model KUBZ 05 KUBZ 06
A C H G B d S Screws A B C
355 à 450 60 90 24 M6 76 62 3 M6x16 340 325 305
500 et 630 80 120 27 M8 100 82 3 M8x15 415 475 355
710 100 148 28 M10 124 102 3 M10x15 510 465 450

10/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
B
C
A
325 mm mini
Seal
Squares
Collar straps
Standard support (Sizes 355 ou 400)
This assembly is not adapted for the use an energy-saving
component or an adapter plate. Make sure that the duct can
bear the weight of the casing.
• Set up the 4 squares and the 2 collar straps on the
duct.
• Set up the seal on the free edge of the duct.
• Put the casing on the duct by correctly placing it in
the centre.
• Adjust and assemble the squares on the unit.
• Stretch out the 2 collar straps.
E
G
S
Sealing frame
Embed the frame into the constructed support and make
sure that the xing lugs are embedded into the concrete.
A mini
70 mm
E
G
M
K
Energy-saving component
Assemble theenergy-saving component insidethe upstands,
under the casing. It is incompatible with the use of the TCDZ
05 adapter plates and the TCDZ 01 standard support. Make
sure that the components are able to move freely before the
casing is assembled. Provide for a drop in pressure of 50 Pa.
Straight, inclined and acoustic upstand
According to DTU 43.1, it is possible to attach a TCDZ 03
energy-saving component or a TCDZ 05 (excluding TCDZ
09) adapter plate which is placed inside the upstand.
For any casing with an acoustic straight upstand (TCDZ
09), provide for a drop in pressure of 80 Pa.
E
G
150
100
100
α
100
G
N
E
R
E
G
N
800
100
G
E
ØD
T
TCDZ 05: Adapter plate
The adapter plate makes it possible to connect the casing
to a circular duct. This part allows the aeraulic connection
and it is not intended to bear the weight of the casing. It is
incompatible with the use of the TCDZ 03 energy-saving
component and the TCDZ 09 acoustic upstand.
TCDZ 01
TCDZ 02
TCDZ 03
TCDZ 07TCDZ 04
TCDZ 09
TCDZ 05

11/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
200
G
E
200 mm upstand lift
Makes it possible to increase the height of the casing by
200 mm, to insert a TCDZ 05 adapter plate between the
casing and the TCDZ 03 energy-saving component or to
mount a TCDZ 03 energy-saving component onto a TCDZ
02 sealing frame.
Costière
droite
Plaque
d’adaptation
Volet d’économie
d’énergie
Réhausse
de costière
A
E
E
G
Ø19
Ø12
J
Sound absorber
Provide for a drop in pressure of 80 Pa.
DRAIN (KITCHEN OPTION KUBZ 14)
To install the drain at the bottom of the casing, drill a hole trough both of the panels. Increase hole size
with a multi-step drill up to Ø20. Screw the plastic drain. Make a silicone seal inside the casing all around
the drain ange. Tightenen manually with a wrench on both panel, taking care of panel deformation.
Accessory TCDZ 02 TCDZ 03 TCDZ 05 SILS
Size Weight (Kg) Weight (Kg) ØD Weight (Kg) Weight (Kg)
355/400 2,5 5,0 315/355/400/450* 1,8/1,5/1,2/0,8 23,0
450/500 4,0 6,0 400/450/500/560* 3,6/3,1/2,5/1,7 37,0
630 4,5 8,0 450/500/560/630 5,1/4,5/3,7/2,7 45,0
710 6,0 11,0 560/630/710 11,8/10,3/8,3 65,0
Accessoire TCDZ 04 TCDZ 07 (30°) TCDZ 09 TCDZ 08
Size R Weight (Kg) Weight (Kg) Weight (Kg) Weight (Kg)
355/400 300/500/700 11,0/15,5/20,0 11,2 34,0 6,2
450/500 300/500/700 13,5/19,0/25,0 14,8 51,0 10,5
630 300/500/700 20,5/29,5/38,0 24,2 65,5 12,2
710 300/500/700 25,5/37,0/48,0 32,4 90,5 15,0
Casing size Accessory size A E G J S
355/400 2 540 450 478 630 30
450/500 3 660 570 598 700 40
630 4 800 668 698 700 40
710 5 930 830 866 700 40
Casing size Accessory size M N K R Ø D T
355/400 2 145 678 400 300/500/700 315/355/400/450* 50/65/80/80
450/500 3 170 798 490 300/500/700 400/450/500/560* 80/80/80/80
630 4 170 898 605 300/500/700 450/500/560/630 80/80/80/90
710 5 190 1066 730 300/500/700 560/630/710 80/90/120
* These adapter plates can only be mounted with the following accessories: TCDZ02, 04, 07 and 08
TCDZ 08
SILS

12/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
3.4 Handling
To keep people safe or prevent damage to property,
use compliant handling equipment that is in a good
condition.
The casing must be lifted at the 4 lifting lugs.
Use slings with a length that is at least double the
height of the casing. Make sure that the slings do
not rub against the motor cowl or the electrical
accessories.
If in doubt, detach it to avoid any damage.
3.5 Casing assembly
The support surface that will support the base of the casing must be as at as possible (sealing frame or
upstand supplied on demand). A seal of foam or similar material (not supplied) is recommended between
the support surface and the base of the casing. A maximum incline of 2.5° is tolerated between the motor
axis and the vertical axis (see diagram below).
Let available space for maintenance operations (§ "6. MAINTENANCE", page 41).
2,5°
Make sure that the support is adapted to the weight
of the whole machine and its various accessories.
Attach the casing at the Ø20 holes provided for
this purpose. You are advised to use a LL washer.
Any screws that are not properly tightened may
make noises and cause harmful vibrations. Once
the machine has been correctly set up, make sure
that the motor turbine is able to rotate freely without
any friction or noise. Vibration isolating devices are
available: KUBZ 05.
Detaching and re-assembling casing panels
The smooth side panels are easy to detach by
loosening their screws. They are repositioned in the
same way.

13/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
4. ELECTRICAL CONNECTION
4.1 Preliminary precautions
Electrical connections must be set up by qualied sta. Electrical connections will be set up in accordance
with the Standard NF C15-100 which indicates that the motor must be protected by an all-pole mechanism
whose opening clearance is 3 mm per contact. Do not forget the earthing connection.
In the event of use in smoke extraction, please refer to Standard NF S 61-932 for connection and
installation. Use high-temperature cables of the CR1-C1 kind. The cable must be protected against UV
radiation. Please note that cables and electrical accessories must be dimensioned according to Article
433-3 of Standard NF C 15-100: "the section of the conductors of the line is determined by a permissible
current equal to 1.5 times the rated current of the motor". No thermal protection device is permitted on the
smoke extraction circuit.
Furthermore, the cables must be protected against any mechanical stress when they are routed if the
connection is established on the terminal box of the motor or on the proximity switch of the casing.
For the purpose of comfort, the motor must be protected by an adapted magnetothermal protection
mechanism.
This electronic commutation motor cannot be directly supplied by the electrical grid, at risk of
being irreparably damaged. The power supply must be realised by the controller.
The unit running and stop must be realized using Start/Stop controller inputs, according to wiring
choice done at §"5. COMMISSIONING AND SETTING", page 14.
Do not stop the unit by switching o directly the main electrical supply.
WARNING: use a voltage tester before you undertake any operation.
4.2 Electrical characteristics
4.3 Wiring of INTZ safety switch
Safety switch delivered factory wired and mounted.
Note: the safety switch is sized to be used in smoke extract application for a 400V three-phases or 230V
single-phase 50/60Hz power supply. The switch is used to isolate the unit from the electrical network in
case of maintenance operations, not to pilot the unit on/o.
Safety switch access
The switch is located next to the controller.
Model P. Nom
(kW) I. Nom. (A)
230V I. Nom. (A)
400V INTZ Electrical protection
necessary
355
0,70 3,05 INTZ 1V15 10 A
400
0,72 3,05 INTZ 1V15 10 A
450
1.24 5,40 INTZ 1V15 10 A
500
1,70 3,52 INTZ 1V15 16 A
630
3,16 6,99 INTZ 1V15 16 A
710
5,91 12,43 INTZ 1V22 16 A

14/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
Wiring of version with INTZ safety switch 1V15
Unit size 355 / 400 / 450
with compacto controller Unit size 500 / 630
with Invento S controller
Neutre
Phase
INTZ 15A
Neutral
L1
L2
INTZ 15 A
L3
Wiring of version with INTZ safety switch 1V22
Unit size 710 with Invento S controller
L1
L2
L3
INTZ 22 A
3
5. COMMISSIONING AND SETTING
5.1 Preliminary precautions
Before starting fan, make sure that the electric motor and impeller assembly rotate freely and that there
is no object likely to be ejected by the turbine. The protection housings must be fastened to roof fan to
prevent any accidental contact with rotating parts.
The machine should be attached to its support before power is applied.
Switch on just an instant to check the turbine’s rotating direction.
WARNING: The impeller rotating direction must correspond to each speed in the direction indi-
cated by the arrow on the product. A centrifugal backward fan unit with an impeller that does not
rotate in the right direction still creates a owrate and a low pressure in the duct. An incorrect ro-
tating direction can lead to an abnormal overheating of the motor, resulting in its destruction and
cancelling our manufacturer’s warranty.
If the rotating direction is incorrect, cut o the electrical power supply, make sure no power is present,
Contact after-sales service. Do not modify wirings, as this might seriously damages the unit.
While running, make sure that the motor’s absorbed current is not more than 10% above the name plate
indicated current .
Once the roof fan is installed and the tests successfully completed, present the main points of the opera-
tion and maintenance manual to the user, and explain:
• How to start up and shut down.
• How to change the operating modes.
Then hand over to the user the technical manual of the roof fan and the mounted accessories so that he
can keep it handy to consult it at any time.

15/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
5.2 Controllers
The ECM motor controller controls this motor according to an adjusting potentiometer on the controller, an
external 0-10V signal or a set point given by Modbus BMS .
The Modbus BMS connection, present as standard, allows you to adjust the ow rate set point or pressure,
and to read the controller registers to nd out the state of the roof fan.
5.2.1 Controller terminal block
Unscrew the plate on the front of the controller (Torx
T20 screwdriver).
5.2.2 Adjustment potentiometer
Adjustment potentiometer
5.2.3 Fault correction
In the event of a fault, restarting operation after switching o the power for 5 minutes may allow the con-
troller to reset. A fault relay allows us to identify the main causes of faults on the controller.
Connection of the relay:
For sizes 355/400/450: Controller - Terminals 4, 5, 6.
For sizes 500/630/710: Controller - Terminals 17, 18, 19.
Regardless of the principle of operation of the roof fan, the relay operates in the following manner:
STATE OF THE UNIT State of
the relay** Compacto Invento
"Normal" operation (COP, CAV, VAV) NO 5-6 18-19
Supply cut o NC 4-5 17-18
On / O switch open - the wheel is stationary but power is on to the controller. NC 4-5 17-18
Loss of phases* - possibility that during a loss of phase the wheel continues to turn. NC 4-5 17-18
*If the control unit detects a fault more than once, notably a phase problem twice, the roof fan will not restart automatically. (**)
NO.: normally open, NC: normally closed.
Switch o the power supply for 5 min and restart the roof fan. If the problem persists, it is possible to
identify the nature of the problem in the registers of the Modbus. The controller operating manual is avail-
able for more information on www.vim.fr.

16/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
For sizes 355/400/450
The "Inputs" table allows you to read the following information:
Register Fault Value Description
0 Power on 0-1 1 = Voltage too low to operate
1 Over voltage 0-1 1 = Voltage too high to operate
2 IGBT over current 0-1 1 = Over current protection triggered
3 Temperature 0-1 1 = Thermal protection triggered, power reduced
4 Phase loss 0-1 1 = loss of phase or motor synchronism
5 PFC over current 0-1 1 = PFC protection (Power Factor Correction) FET triggered
6 CRC settings 0-1 1 = Monitoring of parameters has failed (TBD)
7 Circuit fault 0-1 1 = Error detected during checking of the internal circuits.
8 Motor fault 0-1 1 = Abnormal motor behaviour
9 On temperature 0-1 1 = Converter too hot to operate
10 I2R IGBT fault 0-1 1 = IGBT programme protection triggered
14 Restart fault 0-1 1 = Fault condition repeated more than once in a short time. The power
converter must be restarted or reset.
15 Fire mode 0-1 1 = Fire mode enabled
16 Operation Active 0-1 1 = Operation Active
17 Relay Active 0-1 1 = relay output enabled
18 Awaiting shut-down 0-1 1 = The engine should stop, but is still running.
24 Speed regulation 0-1 Speed regulator enabled
25 Power regulation 0-1 Power limit regulator enabled
26 Current regulation 0-1 Line current regulator enabled
27 Over modulation
regulation 0-1 Over modulation reached. The converter can no longer provide the
voltage required for the motor.
28 Regeneration regulation 0-1 Motor in regeneration. Increased speed to prevent over voltage at the
DC connection.
29 Phase current regulation 0-1 Motor phase RMS current limit
30 Synchronisation
regulation 0-1 Motor still in synchronous mode
For sizes 500/630/710
The "Inputs" table allows you to read the following information:
Register Fault Value Description
0 Power on 0-1 1 = Voltage too low to operate
1 Over voltage 0-1 1 = Voltage too high to operate
2 SW over current 0-1 1 = current protection of the IGBT software
3 On temperature 0-1 1 = Converter too hot to operate
4 Phase loss 0-1 1 = Loss of phase or of main supply
5 Earth current fault 0-1 1 = asymmetrical load (sum of all currents >3 A)
6 CRC settings 0-1 1 = Monitoring of parameters has failed (TBD)
7 Driver fault 0-1 1 = Transistor driver initialization fault
8 ADC fault 0-1 1 = ADC conversion error
9 SPI communication fault 0-1 1 = No communication between the processors
10 Reduction in power 0-1 1 = Reduction in the power of the controller.
11 Stoppage of the reduction in
power 0-1 1 = Stop (motor stop) temperature of the controller reached
12 HW over current 0-1 1 = IGBT software current protection
13 FLW enabled 0-1 1 = Weakening of the active eld
14 System error 0-1 1= Machine error
Refer to the controller operating manual if necessary (available on www.vim.fr).

17/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
5.2.4 Modbus connection - Connection to a BMS
In the case of a connection to a BMS, the Modbus connection, present in standard, allows:
• KUBAIR®F400 ECOWATT® Single phase or 3-phase - Control of the VAV variable ow rate:
-On / Off
-Speed adjustment
-reading of registers (state of the casing).
• KUBAIR®F400 ECOWATT® Single phase or 3-phase - Adjustment to CAV constant ow rate:
-On / Off
-adjustment of the flow rate set point,
-reading of registers (state of the casing).
• KUBAIR®F400 ECOWATT®Single or 3-phase - Adjustment to COP constant pressure:
-On / Off
-adjustment of the pressure set point,
• reading of registers (state of the casing).
Recommendation for ModBus connection.
The protocol used is ModBus RTU 485. It is imperative to respect the rules of the art of a ModBus
network for reliable communication.
You can connect up to 32 controllers on the same segment.
We recommend using twisted shielded cable with the following features :
• Max speed : 10 Mbps,
• Max : 6 dB,
• Impedance : 120Ω (at 100 kHz),
• Capacity between conductors : 52.2 pF/m,
• Section 24 AWG / 0.22 mm².
The maximum recommended length is 1000 m for a segment for a speed of 19200 baud.
Derivations must be at most 40 m. The ModBus communication cable must be separated from the power
cable.
The shielding of the cable must be positioned in the wire rope clamp present in the controllers.
Terminations are required at each end of segment (120Ω + 1 nF).
Cabling example:
Convertisseur USB - RS485
RX / TX +
RX / TX -
Compacto 1Compacto 2Compacto 3
Terminaison 120Ω 1 nF
20 21 22 23 20 21 22 23 20 21 22 23
Segment
Dérivation
A1
B1
A2
B2
A1
B1
A2
B2
A1
B1
A2
B2

18/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
20 21 22 23
Compacto 1
20 21 22 23
Compacto 2
20 21 22 23
Compacto 3
Convertisseur USB - RS485 Terminaison 120Ω 1 nF
RX / TX +
RX / TX -
Segment
Dérivation
A1
B1
A2
B2
A1
B1
A2
B2
A1
B1
A2
B2
Convertisseur USB - RS485
RX / TX +
RX / TX -
5678
Invento 01
5678
Invento 02
5678
Invento 03
Terminaison 120Ω 1 nF
Segment
Dérivation
A1
B1
A2
B2
A1
B1
A2
B2
A1
B1
A2
B2

19/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
Convertisseur USB - RS485 Terminaison 120Ω 1 nF
RX / TX +
RX / TX -
5678
Invento 01
5678
Invento 02
5678
Invento 03
Segment
Dérivation
A1
B1
A2
B2
A1
B1
A2
B2
A1
B1
A2
B2
It is imperative to address a unique address to each controller.
ModBus address :
COMPACTO : Register 7 of Holding Registers.
INVENTO : Register 9 of Holding Registers.
Refer to the corresponding paragraph below for the connection and the setting of your casing.
5.2.5 Default conguration settings
A USB converter with RS 485 is necessary for you to connect to the registers via a PC, as well as an
interface of the same type as ModBus Doctor.
Single-phase model* 3-phase model*
MODBUS address
1 80
Baut rate
19200
START Bit
1
STOP Bit
1
Parity
NONE
* For additional information refer to the roof fan controller manual (available on www.vim.fr).
5.2.6 Input register table
The "Input Register" table allows you to read the following information:
Register Fonction Resolution Description
Single-phase model
4 Speed 1 rpm
8 Power 0,1 W
9 An1 input 0,01 V
10 An2 input 0,01 V
11 Pot input 0,01 V
3-phase model
0 Speed 1 rpm
2 Power 1 W
9 An1 input 0,01 V
10 An2 input 0,01 V
For all other information on the setting of Modbus, contact the After-Sales service department.

20/44 NT-50907601-KUBAIR-F400-ECOWATT-AN-191025
5.3 Operation for smoke extraction
The KUBAIR®F400 ECOWATT® is approved for extraction of hot gases and smoke in the event of a re.
This mode of operation is automatic and does not require any setting: In the case of extraction of gas at a
temperature > 200°C, the roof fan will automatically switch to high speed with its internal thermal protec-
tions inhibited.
The smoke extraction mode must be triggered manually with a BDRA type control unit.
The CAV/VAV/COP modes are no longer accepted.
5.4 Ventilation fault indication
Replaces the use of a BDEZ type pressure switch
Ventilation fault
KUBAIR
®
F400 ECOWATT
®
single phase KUBAIR
®
F400 ECOWATT
®
3-phase
COMPACTO
456
NO
COM
NC
Relay fault
Voyant de signalisation d'un
arrêt de ventilation
Voyant de signalisation d'un
fonctionnement normal
Alimentation
Stop ventilation indicator
light
Running indicator light
Power supply
INVENTO
17 18 19
NO
COM
NC
Relay fault
Voyant de signalisation d'un
défaut de ventilation
Voyant de signalisation d'un
fonctionnement normal
Alimentation
Ventilation defect indi-
cator light
Running indicator light
Power supply
5.5 KUBAIR®F400 ECOWATT® Single-phase - VAV variable ow rate control
VAV - Slaving to an external signal
In variable speed operation, the controller pilots the speed of the roof fan linearly. The controller will vary
the speed of the roof fan between 200 rpm (min. speed), and its maximum speed in proportion to the signal
sent by the external sensor. If the display is present on the roof fan, it will show you the ow rate in m3/h.
The speed adjustment can be done in dierent ways:
• by the potentiometer integrated in the controller,
• by a CVF ON/OFF + variation remote control,
• by an external 0-10V output,
• by a BCCA switch (0/LS/HS with adjustable LS),
• by a VRPZ voltage variator (allowing operation 0 / LS / HS with adjustable LS and HS),
• by ow rate control by Modbus BMS.
VAV - Regulation according to the deviation between the set point / external measurement
During operation at variable speed, the controller regulates the speed of the roof fan according to the set
point-measurement deviation. The set point is adjusted with the potentiometer built into the controller or
a CVF type external control. If the display is present on the roof fan, it will show you the ow rate in m3/h.
This manual suits for next models
13
Table of contents
Other ViM Fan manuals

ViM
ViM JBRB ECOWATT PR VCHV User manual

ViM
ViM JBRB ECOWATT PR User manual

ViM
ViM KUBAIR F400 User manual

ViM
ViM TEDH F400 User manual

ViM
ViM TEDH F400 User manual

ViM
ViM KUBAIR F400 ECOWATT User manual

ViM
ViM KUBAIR F400 ECOWATT User manual

ViM
ViM TEDH F400 User manual

ViM
ViM TEDH F400 User manual

ViM
ViM KDTA-R F400 User manual
Popular Fan manuals by other brands

Lindab
Lindab FORMO PKA installation instructions

Hunter
Hunter Vancouver 21328 Manual de Installatión y Operatión

Titon
Titon Titon Ultimate dMEV product manual

Lütze
Lütze AirBLOWER operating instructions

Lennox
Lennox FLATAIR KFC Series Installation and operating manual

Hyundai
Hyundai H-SF16-RC02 instruction manual