
2.3 OPERATING CONTROLS
The operating controls and electrical connections for the
Model 144 are shown in Figure 2-1. The listing below
discusses each control and its function.
1. Frequency Range/Power Switch —This 11 position
switch selects the generator frequency range. The
extreme counter-clockwise position is the power off
position.
2. Frequency Dial —The main frequency control.
The setting on this dial multiplied by the frequency
range setting (above) equals the output frequency of
the generator. The frequency vernier (3) and the
symmetry control (11) also affect the generator fre-
quency. Note their effect in the listing below.
3. Frequency Vernier —This control allows precision
control over the output frequency. Acomplete turn
of this vernier is equivalent to approximately one half
of the smallest division on the main frequency dial.
When in the full clockwise position (CAL), the set-
tings on the main dial will be accurate.
4. Frequency Index —The scribe line indicates the fre-
quency dial setting. The index is illuminated when
the unit is on.
5. Waveform Selector —This selects the waveform that
appears at the 50L2 output connector. The waveforms
are sine ^,triangle \,square 'Xi .positive go-
ing pulse, and negative going pulse.
6. Amplitude Vernier —Avernier control of the output
amplitude. Maximum clockwise position gives the full
output amplitude of 30 Vpeak-to-peak into an open
circuit or 15 Vp-p into a50J2 load, except positive
and negative pulse which are 7.5 Vzero to peak ampli-
tude into 50£^ load. Counter-clockwise rotation will
continuously reduce the output amplitude. The con-
trol gives aminimum of 20 dB variation (10:1). This
control operates in conjunction with the output atten-
uator (9). For maximum amplitude output this vernier
must be full clockwise and the output attenuator in
the "0 dB" position.
7. 50f2 Out —This connector provides the selected
generator output function. The generator may oper-
ate into an open circuit providing 30 Vpeak-to-peak
maximum, or into a50fl load providing a 15 V
peak-to-peak output.
8. Sweep GCV Output —When the generator is in
continuous, trigger, or gated mode (control 12) this
output provides afixed 0to -i-5 Vsawtooth out-
put. The frequency of this output is controlled by
the sweep rate controls (11). When the generator is
in continuous Swp, Trig Swp, or Swp Hold modes
the output becomes the Generator Control Voltage
(GCV) that is proportional to frequency. The fre-
quency is controlled by the sweep rate controls (11)
and the amplitude is determined by the main fre-
quency dial, VCG input, and sweep width controls.
9. Output Attenuator —Attenuates the output from
0dB (15 Vp-p 5012 max) to -60 dB (15 mV p-p
into 5012) in six, 10 dB steps. The vernier (6) adds
an additional —20 dB, thus, amaximum of —80 dB
(1.5 mV p-p into 5012).
10. Sweep width control —Determines the amount of
sweep when in Cont Sweep, Trig Swp, or Swp
and Hold modes. Clockwise rotation increases sweep
width, counter clockwise rotation decreases sweep
width.
11. Sweep rate control —Determines the frequency of
the 144 ramp generator appearing at the SWP/GCV
OUT. The frequency of this generator is independent
of the frequency of the main generator. When in
any of the sweep modes, this ramp determines the
duration of the sweep cycle. The outer dial deter-
mines the frequency range and the vernier (inner)
dial provides afine adjustment. Note diat the outer
switch detent position is located between two time
ranges. With the vernier in the full clockwise position,
the sweep time is equal to the time to the right of
the detent setting. However, moving the vernier to
the full counterclockwise results in sweep time ap-
proximately 100 times the sweep time to the left of
the detent.
12. Trigger Level Control —Adjusts the sensitivity of the
Trigger Input Circuitry. When in the full counter
clockwise approximately —7.5 Vis required for
triggering. In the full clockwise position approxi-
mately -1-75. Vis required for triggering. At the mid
point, extremely low voltages will trigger the instru-
ment. By rotating the dial, it is possible to manually
trigger the generator. In the gated mode, the generator
will begin to run continuously as the control is
rotated past the mid-point in aclockwise direction.
13. Generator Mode Control —Selects the operating
mode of the main generator as follows:
a) Cont =Continuous Mode —The generator operates
at afixed frequency and runs continuously.
The SWP/GCV output is afixed 0to 5Vramp.
22
8/73