WEG ABW Series User manual

Motors | Automation | Energy | Transmission & Distribution | Coatings
Instruction Manual
Manual de Instrucciones
Manual de Instruções
ABW
Air Circuit Breaker
ABW
Interruptor Abierto
ABW
Disjuntor Aberto


User Manual
Series: ABW Air Circuit Breaker
Language: English


Summary
Sumário
1 INTRODUCTION 8
1.1 CONSIDERATIONS ABOUT SAFETY...................................................................................................8
1.1.1 Preliminary guidelines.................................................................................................................8
1.1.2 Qualified professionals ...............................................................................................................8
1.1.3 Alert messages............................................................................................................................8
1.2 SERVICE CONDITIONS......................................................................................................................10
1.2.1 Ambient temperature ................................................................................................................10
1.2.2 Altitude of installation ...............................................................................................................10
1.2.3 Relative humidity.......................................................................................................................11
1.2.4 Presence of gases.....................................................................................................................11
1.2.5 Installation - minimum instalation distance and insulation voltage........................................11
1.3 STRUCTURE .......................................................................................................................................12
1.4 FRONT VIEW .......................................................................................................................................13
1.4.1 Configuration of terminals ........................................................................................................13
1.5 CODIFICATION....................................................................................................................................14
1.6 TECHNICAL DATA ..............................................................................................................................15
1.7 DIMENSIONS ......................................................................................................................................16
1.8 RECEIPT INSPECTION.......................................................................................................................26
1.9 STORAGE............................................................................................................................................26
1.9.1 Maximum stacking....................................................................................................................26
1.10 HANDLING/MOVEMENT..................................................................................................................27
2 INSTALLATION 28
2.1 FIXED CIRCUIT BREAKER.................................................................................................................28
2.2 DRAW -OUT CIRCUIT BREAKER......................................................................................................28
2.3 ADDITIONAL PRECAUTIONS ............................................................................................................29
2.4 DO NOT LAY THE CIRCUIT BREAKER IN ITS SIDE ........................................................................29
3 OPERATION 30
3.1 MANUAL OPERATION........................................................................................................................30
3.1.1 Manual loading of the springs ..................................................................................................30
3.1.2 Manual loading..........................................................................................................................30
3.1.3 Manual opening.........................................................................................................................30
3.2 ELECTRICAL OPERATION.................................................................................................................31
3.3 EXTRACTION/INSERTION PROCEDURES.......................................................................................31
3.3.1 Insertion.....................................................................................................................................31
3.3.2 Extraction ..................................................................................................................................33
4 PROTECTION UNITS 34
4.1 ADJUSTMENT SELECTORS..............................................................................................................34
4.2 ADJUSTMENT SELECTORS..............................................................................................................35
4.3 CONNECTORS........................................................................................................................................
35
4.4 PROTECTION FUNCTIONS................................................................................................................36
4.4.1 Type N units...............................................................................................................................36
4.4.2 Type A units ...............................................................................................................................37
4.4.3 P and S type units .....................................................................................................................38
4.5 FEATURES OF OPERATION...............................................................................................................39
4.5.1 Long delay protection (L)..........................................................................................................39
4.5.2 Short delay protection (S) .........................................................................................................39
4.5.3 Instantaneous protection (I)...................................................................................................... 40
4.5.4 Shortage current to ground protection (G)...............................................................................40
4.5.5 Leakage current to ground protection (G) - optional...............................................................41

Summary
5 FEATURES AND INSTALATION INSTRUCTIONS 42
5.1 EARTH LEAKAGE ADJUST: ...............................................................................................................42
5.2 DIMENSIONS: .....................................................................................................................................42
5.2.1 Toroidal CT WEG (30/5 A ratio) .................................................................................................42
5.3 EXTERNAL CT INSTALATION............................................................................................................42
5.4 ROGRAMMING MENUS .....................................................................................................................43
5.4.1 Menus ........................................................................................................................................43
5.4.2 LCD screen................................................................................................................................43
5.4.3 Keys ...........................................................................................................................................44
5.4.4 Start screen (current measurement).........................................................................................44
5.4.5 Protection functions..................................................................................................................45
5.4.6 Other Functions.........................................................................................................................46
5.4.7 Communication in network, clock and list of events ..............................................................47
6 TRIPPING CURVES 48
6.1 LONG DELAY PROTECTION (FUNCTION L).....................................................................................48
6.2 SHORT DELAY PROTECTION (FUNCTION S) ..................................................................................49
6.3 INSTANTANEOUS (FUNCTION I) AND SHORTAGE CURRENT TO GROUND (FUNCTION G) PRO-
TECTION.........................................................................................................................................50
6.4 PROTECTION AGAINST DEFINED TIME TYPE OVERCURRENTS (IDMTL) ..................................51
6.5 PROTECTION AGAINST DEFINED TIME TYPE SHORTAGE CURRENT TO GROUND (IDMTL)...52
7 INSPECTION AND MAINTENANCE CYCLES 53
8 FAILURES AND DIAGNOSES 54
9 ABW WIRING DIAGRAM 55


www.weg.net
8 | ABW - Air Circuit Breaker
1 INTRODUCTION
1.1 CONSIDERATIONS ABOUT SAFETY
1.1.1 Preliminary guidelines
Read this manual carefully before installing and operating the circuit breaker. This manual was specifically conceived
to provide the instructions of installation, operation and maintenance of ABW air circuit breakers. However, it may not
cover all the possible contingencies, variations or details which can arise during the installation, operation and
maintenance of the circuit breaker. If you have any queries, please contact WEG.
The information contained herein is generic and does not apply to special situations, as well as not exempting
the user from being responsible for executing the correct application, installation, operation and maintenance
of the circuit breaker. WEG reserves the right to make any alterations to the specifications contained herein or
execute improvements at any moment, without prior notice. If there is any conflict between the information which
is contained in this publication and the contents of designs, supplementary material, or both, the latter shall prevail.
1.1.2 Qualified professionals
Only qualified professionals can execute the installation, operation and maintenance of this equipment. These
professionals must also be trained and authorized to:
Energize, de-energize, ground and identify electrical equipment and circuits, as per the standards and
practices in force;
Use individual and collective equipment, as per the safety standards and procedures in force;
Provide first aid.
1.1.3 Alert messages
Throughout this manual there are several alert messages to call the user’s attention to potential risks or provide
additional information which clarifies o simplifies a determined procedure.
These messages are identified as follows:
DANGER!
It indicates procedures which certainly involve high risks for the user. Failure to observe this warning can lead to serious
injury or death.
ATTENTION!
It indicates procedures which involve some risk for the user. Failure to observe this warning can lead to serious injury or death.
CAUTION!
It indicates procedures which involve some risk of damage to the equipment.
Besides attentively observing the procedures described in this manual, the users must obey the following
instructions:
Always work with the circuit and equipment de-energized, even if they are test, maintenance or repair
procedures;
Use interlocking and safety devices, and check that they function naturally, without needing to be forced or
suppressed

www.weg.net
ABW - Air Circuit Breaker | 9
DANGER!
Only qualified professionals with training and experience in electrical circuits must execute the work described in this
manual. These people must also understand the risks involved in the work, and only execute it after reading all the
contents of this manual.
The correct operation of the ABW circuit breakers depends upon the appropriate handling and correct instal ation,
operation and maintenance. Neglecting the basic requirements of installation and maintenance can lead to injury to the
user and/or damage to the equipment and instal ation.
The ABW circuit breakers have features developed to prevent undue operation. However, such features do not by
themselves eliminate all and any risk. Thus, the user is responsible for recognizing the potential risks, using individual
and collective protective equipment, and for taking suitable safety measures.
Do not execute any adjustment or operate the equipment if the safety devices are not present.
Before executing the visual inspection, test or maintenance in this equipment, disconnect all the power supply circuits.
Consider the circuits to be energized until they are all really de-energized, tested, grounded and identified. Particular
attention should be paid to the electrical system where the equipment is installed, as there may be reverse power supply.
Before installing covers or closing the doors of the panel, inspect the area of the busbars to check that no tools or other
objects have been left in contact with them. Also check that there are no parts of covers or closings of the panel in
contact with or very near the busbars.
Before executing any electrical connection ensure that the circuits are de-energized and grounded.
Introducing foreign objects in the equipment can cause a short-circuit, which can result in irreparable damage, injury or
death. Short-circuits release a large quantity of energy, which leads to the quick expansion of superheated and ionized
gases. As a result, burns can occur even before preventive actions are taken. People and objects can also be thrown
several meters from the equipment.
Such foreign objects can be tools, test remains, instruments, wires, cables or other objects, conductors or not. It is also
advisable to maintains cloths and other materials a long way from the equipment.
ATTENTION!
Ensure that the screws of the terminals are tightened as per the torque recommended in this manual. The screws and
their tightening must be checked periodically, always with the circuits de-energized and grounded.
Do not install the circuit breaker in dirty places at high temperatures, with humidity, dust, corrosive gases, vibration or
lows. The non observance of this recommendation can result in the malfunctioning of the circuit breaker.
Whenever the circuit breaker is turned off by the action of the protection unit, eliminate the cause of the failure before
turning the circuit breaker on again.
Only use the circuit breaker in circuits of 50 HZ or 60 HZ, paying attention to the corresponding model of the protection unit.
CAUTION!
Receipt
Execute the visual inspection immediately after receiving the circuit breaker, and even before removing it from the
pallet. If there is any sign of damage or flaws caused by the transportation, inform the carrier and WEG directly.
Transportation
Maintain the circuit breaker attached to the pallet and transport the unit using a trolley or forklift. Observe the
following additional recommendations:
- Always maintain the pallet horizontal;
- Ensure that the load is balanced on the forks of the forklift;
- Attach the pallet to the forks so that it does not move or fall during the transportation;
- Transport the unit at a low speed, without abrupt movements, avoiding collisions with other structures, equipment
or people;
- Only raise the unit to the extent required to pass over obstacles on the floor, and never above people.
Handling / Movement
Removable hooks are supplied with each circuit breaker so that it is removed from the pallet or extraction car,
suspended by a crane. This is the only method recommended for moving the circuit breaker. Be careful not to
damage the equipment if using other methods. Further details can be found on page 22.
Other important recommendations:
- Do not put cords or cables through the suspension eyelets. Always use safety hooks with a lock;
- The suspension cables must not be less than 45º from the horizontal.
Storage
If it is necessary to store the circuit breaker before installing it, maintain it in its original packaging, in a clean, dry,
ventilated and heated place to avoid condensation. As with any other electrical equipment, protect it from dust and
humidity. Do not store the circuit breaker in an uncovered place orexposed to bad weather.
Introducing foreign objects in the equipment can cause a short-circuit, which can result in irreparable damage,
injury or death. Short-circuits release a large quantity of energy, which leads to the quick expansion of superheated
and ionized gases. As a result, burns can occur even before preventive actions are taken. People and objects can
also be thrown several meters from the equipment. Such foreign objects can be tools, test remains, instruments,
wires, cables or other objects, conductors or not. It is also advisable to maintains cloths and other materials a
long way from the equipment.

www.weg.net
10 | ABW - Air Circuit Breaker
1.2 SERVICE CONDITIONS
1.2.1 Ambient temperature
Operation: -5...40 ºC, with an average of 24h of up to 35 ºC. In order to apply the ABW circuit breakers with
a temperature above 40 °C, consider the maximum values of nominal current presented in the table below:
Circuit
breaker
Maximum
current @
40 ºC (A)
Terminals
of circuit
breaker
(mm)
Recom-
mended
bars
(mm)
Nominal current (A)
Terminals of position
Horizontal Vertical
Ambient temperature Ambient temperature
40 ºC 45 ºC 50 ºC 55 ºC 60 ºC 40 ºC 45 ºC 50 ºC 55 ºC 60 ºC
ABW06D..
630
50x15
50x10 630 630 630 630 630 630 630 630 630 630
ABW08D..
800 800 800 800 800 800 800 800 800 800 800
ABW10D..
1,000 (2x)
50x10
1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000
ABW13D..
1,250 1,250 1,250 1,250 1,250 1,250 1,250 1,250 1,250 1,250 1,250
ABW16D..
1,600 1,600 1,600 1,600 1,550 1,550 1,600 1,600 1,600 1,600 1,550
ABW20E..
2,000
75x20
(2x)
80x10 2,000 2,000 2,000 2,000 2,000 2,000 2,000 2,000 2,000 2,000
ABW25E..
2,500 (3x)
80x10 2,500 2,500 2,500 2,400 2,300 2,500 2,500 2,500 2,450 2,350
ABW32E..
3,200 (4x)
80x10 3,200 3,200 3 ,10 0 3,000 2,900 3,200 3,200 3,15 0 3,050 2,950
ABW40E..
4,000 (3x)
100x10
(4x)
100x10 4,000 4,000 3,900 3,800 3,650 -----
.(2x)
125x15
(3x)
120x10 -----4,000 4,000 3,950 3,900 3,850
ABW5 0 F.
5,000 (2x)
125x20
(4x)
120x10 5,000 5,000 4,900 4,800 4,700 5,000 5,000 4,950 4,850 4,750
ABW63G.
6,300 (2x)
150x20
(4x)
160x10 6,300 6,300 6,200 6 ,10 0 6,000 6,300 6,300 6,250 6,150 6,050
Tab l e 1.1:
Storage: -20...60 ºC.
1.2.2 Altitude of installation
≤ 2,000 m. In order to apply the ABW circuit breakers in altitudes above 2,000 m, apply the nominal current and
voltage reduction factors presented in the table below.
Altitude (m) 2,000 3,000 4,000 5,000
Insulation voltage (V)
1,000 900 700 600
Maximum operational voltage (V)
690 590 520 460
Current correction factor
1 x In 0.99 x In 0.96 x In 0.94 x In
Table 1.2:

www.weg.net
ABW - Air Circuit Breaker | 11
1.2.3 Relative humidity
≤ 85% @ 40 ºC.
≤ 90% @ 20 ºC.
1.2.4 Presence of gases
H2S ≤ 0.01 ppm; SO2≤ 0.01 ppm.
1.2.5 Installation - minimum instalation distance and insulation voltage
Figure 1.1:
Type A B
Fixed N/S 50 150
Draw out N/S 50 150
Table 1.3:
NOTE!
The aforesaid minimum distances also apply to the accessories installed at the side of the circuit breaker, such
as the mechanical interlocking and modules.
Figure 1.2:
Insulation voltage (Ui) Minimum insulation of distance X (mm)
600 V 8
1,000V 14
Table 1.4:

www.weg.net
12 | ABW - Air Circuit Breaker
1.3 STRUCTURE
Extinguishing chamber
Mobile contact
Fixed contact
Contact claws
Extraction car
Connection terminals
Internal CTs
Lower terminals
Block of auxiliary contacts
Undervoltage coil
Closing coil
Motorized drive
On button
Off button
Extinguishing chamber
Terminals of auxiliary contacts
Terminals of control power supply
Terminals of protection unit
Suspension support
Operating mechanism
Openning coil
Circuit breaker
Counter of operations
Magnetic trip system
Protection unit
Front cower
Block of control connections
Connections terminals
Block of auxiliary contacts
Protection unit
Front cover
Operating mechanism
Loading rod
Opening springs
Closing springs
Insertion extraction system
Coils
Figure 1.3: Structure

www.weg.net
ABW - Air Circuit Breaker | 13
1.4 FRONT VIEW
Fixed Withdrawable
1 - On button
2 - Off button
3 - Extinction chamber
4 - Identification plate
5 - Indicator of status of
springs
6 - Indicator of status of
circuit breaker
7 - Protection unit
8 - Loading rod
9 - Maneuvering rod
10 - Position of indicator
11 - Opening of insertion
of lever
12 - Position of lock
Figure 1.4: Front view
1.4.1 Configuration of terminals
Horizontal terminals
Vertical terminals
Plane terminals
Horizontal/vertical
terminals
Vertical/horizontal
terminals
Horizontal/plane
terminals
Vertical/plane
terminals
Plane/horizontal
terminals Plane/vertical
terminals
Figure 1.5: Configuration of terminals

www.weg.net
14 | ABW - Air Circuit Breaker
1.5 CODIFICATION
Version
FFixed
EWithdrawable
ABW16 DN 3 - 16 AZ1 F -A 0 2 2 0
Accessories supplied as optional items
Motorized operator
Undervoltage release
Condenser trip device
Key lock
Key interlock
Motorized operator
Standard
0No motor operator
Optional
1 100~130 V ac/dc
2 200~250 V ac/dc
3 24~30 V dc
4 48~60 V ac/dc
5 380 V ac
6 480 V ac
Undervoltage release
Standard
0No release
Optional
1100~130 V ac/dc
2200~250 V ac/dc
324~30 V dc
448~60 V ac/dc
5380~480 V ac
6200~250 V ac/dc with delay
7100~130 V ac/dc with delay
848~60 V ac/dc with delay
9380~480 V ac with delay
Standard opening coil
2 200~250 V ac/dc
Optional
0No release
1100~130 V ac/dc
324~30 V dc
448~60 V ac/dc
5380~480 V ac
Standard closing coil
2200~250 V ac/dc
Optional
0No release
1100~130 V ac/dc
324~30 V dc
448~60 V ac/dc
5380~480 V dc
Protection unit
Standard unit
AZ1 LSIG + current - electronics power supply 100~250 V ac/dc and measurement frequency
60 Hz
Optional units
000 No protection unit
AZ6 LSIG + current - electronics power supply 100~250 V ac/dc and measurement frequency
50 Hz
AZ2 LSIG + current - electronics power supply 24~60 V dc and measurement frequency
60 Hz LSI
AZ7
LSIG + current - electronics power supply 24~60 V dc and measurement frequency 50 Hz
AF1 LSI + earth leakage + current - electronics power supply 100~250 V ac/dc and
measurement frequency 60 Hz
AF6 LSI + earth leakage + current - electronics power supply 100~250 V ac/dc and
measurement frequency 50 Hz
AF2 LSI + earth leakage + current - electronics power supply 24~60 V dc and measurement
frequency 60 Hz
AF7 LSI + earth leakage + current - electronics power supply 24~60 V dc and measurement
frequency 50 Hz
AC1 LSIG + current + communication2) - electronics power supply 100~250 V ac/dc and
measurement frequency 60 Hz
AC6 LSIG + current + communication2) - electronics power supply 100~250 V ac/dc and
measurement frequency 50 Hz
AC2 LSIG + current + communication2) - electronics power supply 24~60 V dc and
measurement frequency 60 Hz
AC7 LSIG + current + communication2) - electronics power supply 24~60 V dc and
measurement frequency 50 Hz
PC1 LSIG + voltage + current + communication2) - electronics power supply
100~250 V ac/dc and measurement frequency 60 Hz
PC6 LSIG + voltage + current + communication2) - electronics power supply
100~250 V ac/dc and measurement frequency 50 Hz
PC2 LSIG + voltage + current + communication2) - electronics power supply 24~60 V dc and
measurement frequency 60 Hz
PC7 LSIG + voltage + current + communication2) - electronics power supply 24~60 V dc and
measurement frequency 50 Hz
Door frame
Transparent cover
Mechanical interlock
Door interlock
Position auxiliary contact
Maximum current
08 800 A
16 1,600 A
20 2,000 A
25 2,500 A
32 3,200 A
40 4,000 A
50 5,000 A
63 6,300 A
Phase sequence
DN p/ 1,600 A - RST (N)
ES p/ 2,000~3,200 A - RST (N)
FS p/ 4,000~5,000 A - RST (N)
GS p/ 6,300 A - RST (N)
Number of poles
3 3P
Standard auxiliary contacts
A5NO+5NC
Optional (withdrawable version)
BPosition auxiliary contact
Rated current
08 800 A
16 1,600 A
20 2,000 A
25 2,500 A
32 3,200 A
40 4,000 A
50 5,000 A
63 6,300 A
Accessories
No accessories
B ON/OFF button lock
K Key lock
K2 Key interlock
M Mechanical interlock for 2 circuit
breakers1)
M3 Mechanical interlock for 3 circuit
breakers1)
D Door interlock
BK B+K
B2 B+K2
BM B+M
BD B+D
KM K+M
KD K+D
CP Profibus communication
CM Modbus communication
Accessories supplied as standard for the entire range
Auxiliary contacts (5NO+5NC)
Alarm contacts
Opening coil 200~250 V ac/dc
Closing coil 200~250 V ac/dc
Operation counter
Position locking with padlock (padlock not included) - withdrawable version
Position indicator (Inserted /Test/ Withdrawn) - withdrawable version
Notes: 1) 2 circuit breakers are already considered for mechanical interlock M.
3 circuit breakers are already considered for mechanical interlock M3.
2) For communication via Profibus network, it is necessary to use the ABW-CP accessory.
For communication via Modbus network, see the Communication section of this catalog.
Figure 1.6: Coding

www.weg.net
ABW - Air Circuit Breaker | 15
1.6 TECHNICAL DATA
Circuit breaker ABW08 ABW16 ABW20 ABW25 ABW32 ABW40 ABW50 ABW63
Standard IEC 60947-2
Maximum rated current (40 °C) - In max. (A) 800 1,600 2,000 2,500 3,200 4,000 5,000 6,300
Current setting (0.4 ~1.0) x In max
Rated operational voltage - Ue (V) 690
Rated insulation voltage - Ui (V) 1,000
Impulse voltage - Uimp (kV) 12
Frequency (Hz) 50 / 60
Number of poles 3
Versions Fixed - withdrawable
Protection units LSIG Electronics
Rated ultimate short-circuit
breaking capacity - Icu (kA)
220 / 380 / 415 V 65 85 100 120
440 / 480 / 500 V 65 85 100 120
600 / 690 V 50 85 85 100
Rated service short-circuit
breaking capacity - Ics (kA)
220 / 380 / 415 V 65 85 100 120
440 / 480 / 500 V 65 85 100 120
600 / 690 V 50 85 85 100
Rated short-time withstand current
- Icw (kA)
1s 50 85 85 100
2s 42 75 75 90
3s 36 65 65 85
Rated making capacity
- Icm (kA peak)
220 / 380 / 415 V 143 187 220 264
440 / 480 / 500 V 143 187 220 264
600 / 690 V 105 187 187 220
Utilization categories B
Operating time (ms) Opening (max.) 40
Closing (max.) 80
Mechanical lifespan
(number of operations)
Without maintenance 20,000 15,000 10,000 10,000
With maintenance1) 30,000 20,000 15,000 15,000
Electrical lifespan
(number of operations)
Without maintenance 5,000 5,000 2,000 2,000
With maintenance1) 10,000 10,000 5,000 5,000
Altitude (m) ≤2,0002)
Ambient temperature Operation -5...40 °C3)
Storage -20...60 °C
Weight (kg)4) Withdrawable 61 85 143 184
Fixed 32 42 74 101
Connection terminals -
withdrawable/fixed
Horizontal Standard Standard Standard Standard
Vertical Optional Optional Optional Optional
External dimensions
H x W x D (mm)
Withdrawable
430 x 334 x 375 430 x 412 x 375 430 x 629 x 375
430 x 785 x 375
Fixed
300 x 300 x 295 300 x 378 x 295 300 x 597 x 295
300 x 751 x 295
Notes:
1) According to the maintenance routines indicated in the manual.
2) For installation above 2,000 m from sea level, please consider the voltage and current derating factors, as shown in the chart below.
3) For ambient temperature above 40 °C, check maximum rated current values in the chart below.
4) It may vary according to the configuration of optional accessories.
Table 1.5: Technical data

www.weg.net
16 | ABW - Air Circuit Breaker
1.7 DIMENSIONS
Horizontal Rear Terminal - Top View
Vertical Rear Terminal - Top View
8585
5 0
4 - Ø14 Assembly
hole
330
354
25
45
165
20
Front View
300
280
150
Operating panel
center
165 165 12
354
12
300
320
270
35
20
85 85
15
4516520
330
354
4- 14
Mounting hole
25
3P
4- Ø14
Assembly hole
85 85
15
25
20 165 45
330
354
3P
Rear Terminal Dimensions
2 - Ø13
30
15
25
50
Horizontal Rear Terminal - Side View
Vertical Rear Terminal - Side View
Insulation
barrier
32.5
45
295
20
65 165
15
270
35
15118
133
67
59.5 15
90
(Insulation
barrier)
15
90
270
35
65 20
295
16545
32.5
42 50 5083
133
67
15
90
(Insulation
barrier)
27035
65
20 295
165 45
32.5
42
67 133
8350 50
Figure 1.7: ABW08...16 - Fixed Version

www.weg.net
ABW - Air Circuit Breaker | 17
Vertical Rear Terminal - Top View
Horizontal Rear Terminal - Side View
Horizontal Rear Terminal - Top View
Front View
Rear Terminal Dimensions
85 85
5 0
260
334
115200
20 394 20
167
2-M12 Tap
CMB-U/F
334
260
405
430
35
2 - Ø13
15
25
50
Vertical Rear Terminal - Side View
Disconnected & Test
Connected
50
15 55
Zero arc space
Insulation
barrier
4 - Ø13 Mounting hole
38.5
115200
375
60
10
15
133
350
97
270
18
41
6
90
85 85
15
115
200
260
334
P3
334
200 115
15
85 85
260
3P
Disconnected & Test
Connected
ARC Chute surface
6- 13 Mounting hole
(Insulation
barrier)
90
55
50
15
50
133
350
97
38.5
115
375
200
60
10
6 41 18 270
50
15 55
90
50
13397
38.5
115200
375
60
10
64118 270
350
Disconnected & Test
Connected
Arc chute surface
(Insulation
barrier)
6 - Ø13 Mounting hole
Figure 1.8: ABW08...16 - Withdrawable Version

www.weg.net
18 | ABW - Air Circuit Breaker
115 115
408
432
7 5
4 - Ø14
Mounting hole
25
45
165
20
Front View
378
280
189 189
Operating panel
center
204 204 12
432
12
300
320
270
35
20
3 - Ø13
30
15
25 25
75
90
Insulation
barrier
32.5
45
295
20
65 165
15
270
35
113
133
67
57 20 20
4- 14
Mounting hole
115 115
20
45
165
20
408
432
25
P3
4 - Ø14
Mounting hole
3P
432
408
25
115 115
20
4520 165
Rear Terminal Dimensions
(Insulation
barrier)
90
7575 58
29.5
67 133
32.5
45
295
165
20
65
35 270 15
20 165
295
45
75
67
58
133
75
90
(Insulation
barrier)
270 15
32.5
29.5
65
35
Horizontal Rear Terminal - Top View
Horizontal Rear Terminal - Side View
Vertical Rear Terminal - Top View
Vertical Rear Terminal - Side View
Figure 1.9: ABW20...32 - Fixed Version

www.weg.net
ABW - Air Circuit Breaker | 19
115 115
7 5
260
412
115200
Front View
20 472 20
206
2-M12 Tap
CMB-U/F
412
260
405
430
34
3 - Ø13
15
25 25
75
Disconnected & Test
Connected
50
15 55
Zero arc space
90
Insulation
barrier
6 - Ø13 Mounting hole
38.5
115
200
375
60
10
20
133
350
97
270
18
41
6
Vertical Terminal Dimensions
115 115
20
260
412
200 115
3P
115
115200
3P
412
260
115
20
Disconnected & Test
Connected
ARC Chute surface
(Insulation
barrier)
6- 13 Mounting hole
50
15 55
90
75
13397
350
38.5
115
200
60
375
10
6 41 18 270
6 - Ø13 Mounting hole
10 60
641 18 270
200375 115
97 133
350
75
90
(Insulation
barrier)
Arc chute surface
Connected
Disconnected & Test
50
15 55
38.5
Horizontal Rear Terminal - Top View
Horizontal Rear Terminal - Side View
Vertical Rear Terminal - Top View
Vertical Rear Terminal - Side View
Figure 1.10: ABW20...32 - Withdrawable Version

www.weg.net
20 | ABW - Air Circuit Breaker
Front View
90
Insulation
barrier
67.5
45
295
2065 165
15
270
193
97
42
18
95
20 2020 83
70 7 0 20
Rear Terminal Dimensions
5 - Ø13
34
15
252525
25
125
595
280
150
Operating panel
center
460 165 12
649
12
300
380
270
35
60
95
80
190 190
125
625
649
4 - Ø14
Mounting hole
45
165
20
(Insulation
barrier)
90
15
270
95
65 20
295
16545
67.5
20.5
39.5
102
12558
183
125
295
165
67.5
20.5
95 270 15
90
(Insulation
barrier)
39.5
102
125 12558
183
20
65
190190
20 70 20
625
649
20 45165
4- 14
Mounting hole
3P
190 190
625
649
3P
20 2070
45
20 165
4 - Ø14
Mounting hole
Horizontal Rear Terminal - Top View
Horizontal Rear Terminal - Side View
Vertical Rear Terminal - Side View
Vertical Rear Terminal - Side View
45
Figure 1.11: ABW40...50 - Fixed Version
This manual suits for next models
11
Table of contents
Languages:
Other WEG Circuit Breaker manuals
Popular Circuit Breaker manuals by other brands

ABB
ABB ReliaMod RMS212522LRLR installation instructions

Siemens
Siemens AFCI quick start guide

Eaton
Eaton DILM820-XHI11 Series Instruction leaflet

ABB
ABB Sace Emax UL Listed Installation, service and maintenance instructions

hager
hager h3 x160 Series User instructions

hager
hager RCCB 25-63A quick start guide

Circutor
Circutor RECmax-CVM series instruction manual

Westinghouse
Westinghouse DB-50 instructions

Siemens
Siemens MTRPB installation instructions

Reliance electric
Reliance electric FEDERAL PACIFIC DST-2 instruction manual

ABB
ABB SACE Emax 2 manual

Siemens
Siemens GMI Series Installation operation & maintenance