WIKA SENSeOR AMS01 User manual

24/7 ASSET MONITORING SOLUTION
AMS01 USER MANUAL
Document revision: UM00403EN-AC
Date: 2023-08
SENSeOR (head office)
Bâtiment Natura 2
1198, avenue du Docteur
Maurice Donat
06250 Mougins
France
Contact address:
support.senseor@wika.com
Regional distributors
Visit
www.senseor.com for
the latest distribution
locations.

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 2/28
www.senseor.com
WARRANTY
These products are warranted to be free from functional defects in material and in workmanship at
the time of the manufacturing and to conform at that time to the specifications set forth in the
relevant instruction manuals or in the data sheets, for such products for a period of one year.
Reference SENSeOR terms and conditions provided at time of purchase for complete warranty details.
SENSeOR (head office)
Bâtiment Natura 2
1198, avenue du Docteur Maurice Donat,
06250 Mougins
France
SENSeOR reserves the right to make technical changes or to modify the content of this document
without prior notice.
SENSeOR is not responsible for errors or for possible lack of information in this document.
All rights reserved. No part of this document may be reproduced, distributed, or transmitted in any
form or by any means, including photocopying, recording, or other electronic or mechanical methods,
without the prior written permission of SENSeOR, except in the case of brief quotations embodied in
critical reviews and certain other non-commercial uses permitted by copyright law.
Copyright © 2023, SENSeOR

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 3/28
www.senseor.com
TABLE OF CONTENTS
WARRANTY.............................................................................................................................................. 2
TABLE OF CONTENTS............................................................................................................................... 3
SAFETY INSTRUCTIONS............................................................................................................................ 5
1.0 CONVENTIONS......................................................................................................................... 5
1.1 SAFETY INFORMATIONS .......................................................................................................... 6
OVERVIEW............................................................................................................................................... 7
1.0 RELATED DOCUMENTS............................................................................................................ 7
1.1 AVAILABLE PRODUCTS............................................................................................................. 7
1.2 INSTRUCTIONS FOR USE.......................................................................................................... 8
1.3 READER OVERVIEW ................................................................................................................. 9
1.3.1 SERIALIZATION LABEL...................................................................................................... 9
1.3.2 FRONT LABELS ................................................................................................................. 9
1.4 CONNECTORS & FUNCTIONS................................................................................................. 10
1.4.1 INPUT POWER (1) .......................................................................................................... 10
1.4.2 ENVIRONMENTAL SENSOR (2)....................................................................................... 10
1.4.3 RF ANTENNAS (3)........................................................................................................... 10
1.4.4 ETHERNET PORT (4)....................................................................................................... 11
1.4.5 SD CARD (5) ................................................................................................................... 11
1.4.6 RS485 PORTS (6)............................................................................................................ 12
1.4.7 USB PORT (7) ................................................................................................................. 12
1.4.8 RELAY OUTPUT (8)......................................................................................................... 12
1.4.9 LEDS INTERFACE (9)....................................................................................................... 12
1.5 STATUS LEDS.......................................................................................................................... 13
1.5.1 DFU MODE LEDS INDICATION (DEVICE FIRMWARE UPGRADE) .................................... 13
1.5.2 APPLICATIVE MODE LEDS INDICATION.......................................................................... 14
INSTALLATION ....................................................................................................................................... 15
1.6 UNPACKING........................................................................................................................... 16
1.6.1 PHYSICAL DIMENSIONS ................................................................................................. 16
1.7 DIN RAIL MOUNTING............................................................................................................. 17
1.7.1 READER EMPLACEMENT................................................................................................ 18
1.7.2 RECOMMENDED SPACING............................................................................................. 18
WIRING.................................................................................................................................................. 19
1.8 POWER................................................................................................................................... 19
1.8.1 INPUT POWER................................................................................................................ 19

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 4/28
www.senseor.com
1.8.2 RELAY OUTPUT .............................................................................................................. 20
1.8.3 INTERNAL BATTERY ....................................................................................................... 20
1.9 COMMUNICATION CONNECTIONS........................................................................................ 21
1.9.1 CABLING FOR RS485 COMMUNICATION....................................................................... 21
1.9.2 BUS RESISTIVE TERMINATION ....................................................................................... 21
1.9.3 BUS DATA RATE ............................................................................................................. 22
1.9.4 BUS LENGTH .................................................................................................................. 22
1.9.5 NUMBER OF READERS................................................................................................... 22
1.9.6 MODBUS-RTU DEFAULT CONFIGURATION.................................................................... 22
1.9.7 CABLING FOR ETHERNET COMMUNICATION................................................................ 23
1.10 ENVIRONMENTAL SENSOR CONNECTION............................................................................. 23
1.11 CONNECTING TO EARTH........................................................................................................ 24
1.12 CONNECTING RF ANTENNAS................................................................................................. 24
SYSTEM INSTALLATION AND CONFIGURATION..................................................................................... 25
1.13 SAW TEMPERATURE SENSORS INSTALLATION...................................................................... 25
1.14 SYSTEM CONFIGURATION ..................................................................................................... 25
1.15 DFU & NETWORK PARAMETERS RESET................................................................................. 25
1.15.1 DFU MODE..................................................................................................................... 25
1.16 SD CARD................................................................................................................................. 26
1.16.1 NETWORK PARAMETERS RESET .................................................................................... 27
CERTIFICATIONS .................................................................................................................................... 28
1.17 CERTIFICATIONS .................................................................................................................... 28

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 5/28
www.senseor.com
SAFETY INSTRUCTIONS
IT IS IMPORTANT TO READ THIS MANUAL BEFORE INSTALLING OR COMMISSIONING SENSEOR ASSETS
MONITORING SYSTEM.
1.0 CONVENTIONS
DANGER
DANGER INDICATES AN IMMINENTLY HAZARDOUS SITUATION, WHICH, IF NOT AVOIDED, WILL RESULT
IN DEATH OR SERIOUS INJURY.
FAILURE TO FOLLOW THE INSTRUCTIONS GIVEN WILL RESULT IN DEATH OR SERIOUS INJURY.
WARNING
WARNING INDICATES A POTENTIALLY HAZARDOUS SITUATION, WHICH, IF NOT AVOIDED, COULD
RESULT IN DEATH OR SERIOUS INJURY.
FAILURE TO FOLLOW THE GIVEN INSTRUCTIONS CAN RESULT IN DEATH OR IN SERIOUS INJURY.
CAUTION
CAUTION INDICATES A POTENTIALLY HAZARDOUS SITUATION, WHICH, IF NOT AVOIDED, MAY RESULT
IN MINOR OR MODERATE INJURY.
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN PERSONAL INJURY.
NOTICE
NOTICE PROVIDES GUIDANCE ON DAMAGE UNRELATED TO PERSONAL INJURY, SUCH AS THOSE THAT
CAN CAUSE DETERIORATED PROPERTY.
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN PROPERTY DAMAGE.
IMPORTANT
IMPORTANT INDICATES ADDITIONAL INFORMATION ABOUT MAKING EFFECTIVE USE OF THIS
PRODUCT.

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 6/28
www.senseor.com
1.1 SAFETY INFORMATIONS
►Protect product from moisture and humidity.
►Protect product from too high or too low temperature.
►Protect product from fire.
►Do not paint the product.
►Do not modify or disassemble the product. Service must be carried out by SENSeOR.
►Store products in dry and dust-free place.

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 7/28
www.senseor.com
OVERVIEW
CAUTION
THIS READER IS DEDICATED TO SWITCHGEAR MONITORING WITH WIRELESS PASSIVE SAW
TEMPERATURE SENSORS, ENVIRONMENTAL SENSOR AND UHF PARTIAL DISCHARGE DETECTION. IT IS
DESIGNED FOR USE INSIDE METALLIC CAVITIES ONLY LIKE THE SWITCHGEAR CABINET AND TUNED TO
BE COMPLIANT WITH IEC 62271 ENABLING A LICENSE-FREE USE IN SWITCHGEAR WORLDWIDE.
1.0 RELATED DOCUMENTS
-UM00400-EN: AMS01 Configuration Tool User Manual.
-UM00417-EN: AMS01 Modbus table.
-UM00418-EN: AMS01 Modbus table with HTR02 compatibility mode.
-UM00419-EN: AMS01 SD card file management.
-SD00385-EN: AMS01 readers Datasheet.
For additional related documentation and file downloads see support website at
senseor.com/downloads.
1.1 AVAILABLE PRODUCTS
This manual covers the following products:
-AMS01-T: Temperature monitoring only.
-AMS01-P: Partial discharge monitoring only.
-AMS01-TP: Temperature & partial discharge monitoring.

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 8/28
www.senseor.com
1.2 INSTRUCTIONS FOR USE
The AMS01 reader is dedicated to monitor electrical equipment like switchgears. The temperature of
live conductors is measured by SAW sensors and prevent overheating and overload. Partial discharges
are measured by antenna pairs and prevent equipment failure. Ambient temperature and humidity
measurements are also available through an optional environmental sensor connected with wires to
the reader.
The reader is intended to be installed in low voltage compartments of switchgear or in similar type of
assets. It can also be installed in a weatherproof environmental enclosure.
The reader is intended for use at a maximum altitude of 5 km, typically between -20°C to +70°C (refer
to reader specification for the complete specification) and between 10% to 95% non-condensing
relative humidity.
WARNING
THE READER IS NOT INTENDED FOR INSTALLATION INTO MEDIUM OR HIGH VOLTAGE COMPARTMENT
ASSETS. ONLY SAW TEMPERATURE SENSORS, ENVIRONMENTAL SENSOR AND RF ANTENNAS ARE
INTENDED FOR INSTALLATION INTO MEDIUM VOLTAGE COMPARTMENTS.

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 9/28
www.senseor.com
1.3 READER OVERVIEW
Included in scope of delivery:
-1x AMS01 reader.
-1x AMS01 system user manual.
-1x µSD card.
-1x 2-pin power connector.
-1x 4-pin environmental sensor connector.
-1x 2-pin relay connector.
-1x 35 mm DIN rail mount with 2x M3x6 mm screws.
1.3.1 SERIALIZATION LABEL
Figure 1: Product serialization label
1.3.2 FRONT LABELS
Figure 2: Example of front product labels

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 10/28
www.senseor.com
1.4 CONNECTORS & FUNCTIONS
Figure 3: Rear connection view
1.4.1 INPUT POWER (1)
Pin
Type
Description
1 (left)
+24VDC
Main power supply input (24VDC 0.2A)
2 (right)
GND
Ground
CAUTION
DO NOT REVERSE THE POWER SUPPLY POLARITY, THIS MAY CAUSE ELECTRICAL DAMAGE.
1.4.2 ENVIRONMENTAL SENSOR (2)
Pin
Type
Description
1 (left)
+5VDC
Power supply of environmental sensor (5V out from reader)
2
CLK
Clock
3
DAT
Data
4 (right)
GND
Ground
1.4.3 RF ANTENNAS (3)
Connector
Type
Description
1A (left)
RF
Antenna 1A
2A
Antenna 2A
3A
Antenna 3A
4A
Antenna 4A
5A
Antenna 5A
1B
Antenna 1B
2B
Antenna 2B
3B
Antenna 3B
4B
Antenna 4B
5B (right)
Antenna 5B
1
2
3

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 11/28
www.senseor.com
Figure 4: Front connection view
1.4.4 ETHERNET PORT (4)
Standard RJ45 socket for Modbus-TCP communication and reader configuration.
Pin
Type
Description
1
Tx +
Transmit data +
2
Tx -
Transmit data -
3
Rx +
Receive data +
4
-
Not used
5
-
Not used
6
Rx -
Receive data -
7
-
Not used
8
-
Not used
1.4.5 SD CARD (5)
Memory card slot for µSD cards.
Specification
Form factor
File system
Bus interface
Speed class
Others
Version 3.0.1 (2010)
MicroSD HC
FAT32
UHS-I
Class 10
SD Smart
8
6
5
4
9
7
10
Figure 5: Ethernet socket pinout

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 12/28
www.senseor.com
1.4.6 RS485 PORTS (6)
RJ45 ports for Modbus-RTU communication.
Pin
Type
Description
1 (left)
-
Not used
2
-
Not used
3
-
Not used
4
A
Data +
5
B
Data -
6
-
Not used
7
-
Not used
8 (right)
GND
Ground
1.4.7 USB PORT (7)
Mini USB port reserved for future use.
1.4.8 RELAY OUTPUT (8)
Pin
Type
Description
1 (left)
COM
Common for relay
2 (right)
Normally Open (N.0.)
Alarm relay activation output (240VAC 0.8A max)
1.4.9 LEDS INTERFACE (9)
Status LEDs.
Figure 6: RS485 socket pinout
Figure 7: Relay output cabling
Internal view
FUSE

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 13/28
www.senseor.com
1.5 STATUS LEDS
Status LEDs are used to indicate the functional state of reader.
1.5.1 DFU MODE LEDS INDICATION (DEVICE FIRMWARE UPGRADE)
DFU is an AMS01 internal recovery/update program mode automatically called during firmware
update process.
Following table indicates reader status in this mode.
Description
LED1 status (L1)
LED2 status (L2)
LED3 status (L3)
No power
LEDs OFF
Firmware update in progress
LEDs blinking
Manually entered
Corrupted
firmware detected
DFU mode
LEDs blinking

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 14/28
www.senseor.com
1.5.2 APPLICATIVE MODE LEDS INDICATION
1.5.2.1 LED 1 (L1) indication description
Description
Status
No power
LED OFF
System is working properly
LED ON
System warning
LED ON
System error
LED ON
1.5.2.2 LED 2 (L2) indication description
Description
Status
No notifier configured
LED OFF
At least one notifier configured
LED ON
At least one notifier in temperature warning or PD medium level state
LED ON
At least one notifier in temperature alarm or PD high level state
LED ON
1.5.2.3 LED 3 (L3) indication description
Reserved for future use.

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 15/28
www.senseor.com
INSTALLATION
IMPORTANT
THE INSTALLATION INSTRUCTIONS ARE ONLY FOR THE AMS01 READER.
IT IS ASSUMED THAT SAW TEMPERATURE SENSORS AND PARTIAL DISCHARGE PROBE ANTENNAS HAVE
BEEN CONFIGURED AND INSTALLED.
WARNING
PROFESSIONAL INSTALLATION REQUIRED.
INSTALLATION AND CONFIGURATION SHOULD BE PERFORMED ONLY BY USERS WHO ARE
TECHNICALLY COMPETENT AND AUTHORIZED TO DO SO.
LOCAL REGULATIONS REGARDING ELECTRICAL INSTALLATION AND SAFETY MUST BE OBSERVED.
FAILURE TO FOLLOW THE GIVEN INSTRUCTIONS CAN RESULT IN DEATH OR IN SERIOUS INJURY.
WARNING
THE USE OF THIS EQUIPMENT IN A MANNER NOT SPECIFIED IN THIS MANUAL OR BY THE
MANUFACTURER MAY IMPAIR PROTECTION OF THE USER AND EQUIPMENT.
CAUTION
THIS EQUIPMENT IS DESIGNED FOR INSTALLATION IN AN ENCLOSURE THAT PROVIDES ADEQUATE
PROTECTION AGAINST ELECTRICAL SHOCK.

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 17/28
www.senseor.com
1.7 DIN RAIL MOUNTING
CAUTION
ENSURE THAT THE LOW-LEVEL COMPARTMENT WHERE THE READER IS MOUNTED IS SUFFICIENTLY
VENTILATED TO PREVENT OVERHEATING. THE DEVICE MUST BE ELECTRICALLY GROUNDED FOR EMC
COMPLIANCE.
The reader is designed for installation on a grounded 35 mm DIN rail. The reader could be mounted in
two different positions to facilitate integration.
Using the fixing clip and the two screws provided, screw it onto the box enclosure according to the
preferred orientation.
SENSeOR recommends to mount the device vertically with antennas output to the top.
Figure 9: DIN rail fixation –Configuration 1
Figure 10: DIN rail fixation –Configuration 2

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 18/28
www.senseor.com
1.7.1 READER EMPLACEMENT
The reader is intended to be installed in the low voltage compartment of the switchgear. The other
electrical assets are recommended to be weather protected in an enclosed location.
The reader is required to be installed within a maximum distance of 10 meters from the antennas,
corresponding to the maximum length of the antenna coaxial cable for SAW temperature sensors and
partial discharge measurement.
1.7.2 RECOMMENDED SPACING
For connectors access, it is recommended to leave the minimum clearance for top and bottom panels
of 5 cm (2 inches).
5 cm
5 cm
Figure 11: Reader emplacement in switchgear
Figure 12: Reader access clearance

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 19/28
www.senseor.com
WIRING
1.8 POWER
The reader power connector is a 2-pin male connector. This screw connector supports from 16 to 26
AWG wires. For stranded conductor use connector ferrules on the termination.
1.8.1 INPUT POWER
The reader operates at 24VDC nominal with a total power consumption of 6 Watts maximum.
SENSeOR recommends the use of a DC power supply in the same low-voltage compartment as the
reader. It is possible to run a DC power bus to power multiple readers from one DC power supply.
However, this option requires a careful consideration of the wire diameter, AC/DC and circuit breaker
capabilities.
Power connections are recommended to be at a minimum of 16 AWG.
If bussed power is being considered, the wire gauge must be selected to prevent excessive voltage
drop between the DC power source and the reader that is electrically farthest from the source.
The following block diagram outlines the recommended power wiring for the reader with a 2-pole
circuit breaker and an AC/DC power supply. Surge suppression devices can also be installed between
the input line and the neutral only if higher safety rating is required.
Figure 13: Connector ferrule
Figure 14: Reader power cabling

24/7 ASSET MONITORING SOLUTION UM00403EN-AC
SENSeOR AMS01 User Manual 20/28
www.senseor.com
1.8.2 RELAY OUTPUT
Output relay connections are recommended to be at a minimum of 16 AWG.
1.8.3 INTERNAL BATTERY
SENSeORreader has an internal 3VDC non rechargeable battery to keep the UTC date and the time in
case of power down. Battery needs to be replaced if voltage value is under 2.1V.
It can be replaced only by authorized person using the following or an equivalent reference:
1.8.3.1 Battery replacement procedure
►Disconnect all the AMS01 reader connections (antennas, environmental sensor, relay and power
supply).
►Using a PZ1 screwdriver, disconnect the ground lug and remove the screw.
►Extract the reader from its location on the DIN rail.
►Remove the 4 screws from the front panel.
►Remove the electronic card from the enclosure.
►Identify and replace the CR2032 battery by carefully respecting its polarity.
►Reinsert the electronic card in the enclosure.
►Screw the front panel on the enclosure.
►Reposition the reader on its location on the DIN rail.
►Reconnect the ground lug with the corresponding screw.
►Reconnect all the AMS01 reader connections (antennas, environmental sensor, relay and power
supply).
WARNING
THERE IS A RISK OF EXPLOSION IF THE BATTERY IS REPLACED BY AN INCORRECT TYPE.
BE CAREFUL OF USED BATTERY IN ACCORDANCE WITH YOUR REGIONAL LEGAL INSTRUCTIONS.
Figure 15: 3V Lithium CR2032 battery
Other manuals for SENSeOR AMS01
2
Table of contents
Other WIKA Measuring Instrument manuals

WIKA
WIKA TC82 Operating instructions

WIKA
WIKA CTD9100-1100 User manual

WIKA
WIKA FLC-2300 User manual

WIKA
WIKA CPH6300-S1 User manual

WIKA
WIKA PG23HP Series User manual

WIKA
WIKA air2guide A2G-20 User manual

WIKA
WIKA 712.15.160 User manual

WIKA
WIKA F73.100 User manual

WIKA
WIKA 432.55 User manual

WIKA
WIKA DG-05 User manual