WIKA F-20 User manual

Operating instructions
Betriebsanleitung
EN
DE
Pressure transmitter models F-20, F-21
Druckmessumformer, Typen F-20 und F-21
Pressure transmitter, models F-20 and F-21

2WIKA operating instructions pressure transmitters, models F-20, F-21
EN
DE
2103870.07 10/2021 EN/DE
© 2012 WIKA Alexander Wiegand SE & Co. KG
All rights reserved. / Alle Rechte vorbehalten.
WIKA®is a registered trademark in various countries.
WIKA®ist eine geschützte Marke in verschiedenen Ländern.
Prior to starting any work, read the operating instructions!
Keep for later use!
Vor Beginn aller Arbeiten Betriebsanleitung lesen!
Zum späteren Gebrauch aufbewahren!
Operating instructions models F-20 and F-21 Page 3 - 16
Betriebsanleitung Typen F-20 und F-21 Seite 17 - 31

3
WIKA operating instructions pressure transmitters, models F-20, F-21
EN
2103870.07 10/2021 EN/DE
Contents
Contents
1. General information 4
2. Function 5
3. Safety 5
4. Packaging 7
5. Starting, operation 7
6. Specications 11
7. Adjustment of zero point / span 13
8. Maintenance 14
9. Trouble shooting 14
10. Storage, disposal 16

4WIKA operating instructions pressure transmitters, models F-20, F-21
EN
2103870.07 10/2021 EN/DE
1. General information
1. General information
■
The instrument described in the operating instructions has been designed and manufactured using state-of-the-
art technology. All components are subject to stringent quality and environmental criteria during production. Our
management systems are certied to ISO 9001 and ISO 14001.
■
These operating instructions contain important information on handling the instrument.Working safely requires that
all safety instructions and work instructions are observed.
■
Observe the relevant local accident prevention regulations and general safety regulations for the instrument’s range
of use.
■
The operating instructions are part of the product and must be kept in the immediate vicinity of the instrument and
readily accessible to skilled personnel at any time. Pass the operating instructions onto the next operator or owner of
the instrument.
■
Skilled personnel must have carefully read and understood the operating instructions prior to beginning any work.
■
The general terms and conditions contained in the sales documentation shall apply.
■
Subject to technical modications.
■
Further information:
- Internet address: www.wika.de / www.wika.com
- Relevant data sheet: PE 81.19
- Application consultant: Tel.: +49 9372 132-0
Fax: +49 9372 132-406
Abbreviations
2-wire Two connection lines are intended for the voltage supply.
The supply current is the measurement signal.
3-wire Two connection lines are intended for the voltage supply.
One connection line is intended for the measurement signal.
U+ Positive supply connection
U- Negative supply connection
S+ Positive measurement connection

5
WIKA operating instructions pressure transmitters, models F-20, F-21
EN
2103870.07 10/2021 EN/DE
2. Function
F-20: Pressure connection with internal diaphragm (standard version).
F-21: Pressure connection with ush diaphragm for highly viscous or solids entrained media which might clog the
pressure port.
The pressure prevailing within the application is transformed into a standardised electrical signal through the deection
of the diaphragm, which acts on the sensor element with the power supply fed to the transmitter.This electric signal
changes in proportion to the pressure and can be evaluated correspondingly.
3. Safety
3.1 Explanation of symbols
WARNING!
... indicates a potentially dangerous situation that can result in serious injury or death, if not avoided.
CAUTION!
... indicates a potentially dangerous situation that can result in light injuries or damage to equipment or
the environment, if not avoided.
WARNING!
... indicates a potentially dangerous situation that can result in burns, caused by hot surfaces or liquids,
if not avoided.
Information
... points out useful tips, recommendations and information for ecient and trouble-free operation.
3.2 Intended use
The pressure transmitter is used for measuring pressure.The measured pressure is output as an electrical signal.
Only use the pressure transmitter in applications that lie within its technical performance limits (e.g. max. ambient
temperature, material compatibility, ...).
2. Function / 3. Safety

6WIKA operating instructions pressure transmitters, models F-20, F-21
EN
2103870.07 10/2021 EN/DE
→ For performance limits, see chapter 6 “Specications”.
The instrument has been designed and built solely for the intended use described here, and may only be used
accordingly.
The manufacturer shall not be liable for claims of any type based on operation contrary to the intended use.
3.3 Personnelqualication
Skilled personnel
Skilled personnel, authorised by the operator, are understood to be personnel who, based on their technical training,
knowledge of measurement and control technology and on their experience and knowledge of country-specic
regulations, current standards and directives, are capable of carrying out the work described and independently
recognising potential hazards.
WARNING!
■
Select the appropriate pressure transmitter with regard to scale range, performance and specic
measurement conditions prior to installing and starting the instrument.
■
Observe the relevant national regulations and observe the applicable standards and directives for
special applications (e.g. with dangerous media such as acetylene, ammable gases or liquids
and toxic gases or liquids and with refrigeration plants or compressors). If you do not observe the
appropriate regulations, serious injuries and/or damage can occur!
■
Open pressure connections only after the system is without pressure!
■
Please make sure that the pressure transmitter is only used within the overload threshold limit all the time!
■
Observe the ambient and working conditions outlined in chapter 6 “Specications”.
■
Observe the technical data for the use of the pressure transmitter in connection with aggressive /
corrosive media and for the avoidance of mechanical hazards.
■
Ensure that the pressure transmitter is only operated in accordance with the provisions i.e. as
described in the following instructions.
■
Do not interfere with or change the pressure transmitter in any other way than described in these
operating instructions.
■
Remove the pressure transmitter from service and mark it to prevent it from being used again
accidentally, if it becomes damaged or unsafe for operation
■
Take precautions with regard to remaining media in removed pressure transmitter. Remaining media
in the pressure port may be hazardous or toxic!
■
Have repairs performed by the manufacturer only.
■
Open circuit before removing connector / cover.
3. Safety

7
WIKA operating instructions pressure transmitters, models F-20, F-21
EN
2103870.07 10/2021 EN/DE
4. Packaging
Has everything been supplied?
Check the scope of supply:
■
Completely assembled pressure transmitters.
■
With ush version (F-21) including pre-assembled sealings and protection cap.
■
Inspect the pressure transmitter for possible damage during transportation. Should there be any obvious damage,
inform the transport company and WIKA without delay.
■
Keep the packaging, as it oers optimal protection during transportation (e.g. changing installation location,
shipment for repair).
■
Ensure that the pressure connection thread and the connection contacts will not be damaged.
In order to protect the diaphragm, the pressure connection of the instrument F-21 is provided with a special protection cap.
■
Remove this protection cap only just before installing the pressure transmitter in order to prevent any damage to the
diaphragm or the thread.
■
Keep the protection cap of the pressure connection thread and the diaphragm for later storage or transport.
■
Mount the protection cap when removing and transporting the instrument.
5. Starting, operation
Required tools: wrench (ats 27), screw driver
Diaphragm test for your safety
It is necessary that before starting the pressure transmitter you test the diaphragm visually, as this is a safety-relevant
component.
WARNING!
■
Pay attention to any liquid leaking out, for this points to a diaphragm damage.
■
Check the diaphragm visually for any damage (F-21).
■
Use the pressure transmitter only if the diaphragm is undamaged.
■
Use the pressure transmitter only if it is in a faultless condition as far as the safety-relevant features
are concerned.
4. Packaging / 5. Starting, operation

8WIKA operating instructions pressure transmitters, models F-20, F-21
EN
2103870.07 10/2021 EN/DE
Mechanical connection
max. 50 Nm
Product label (example)
Made in Germany 4C
WIKA Alexander Wiegand SE & Co. KG 63911 Klingenberg
Transmitter F-20
0 ... 10 bar 1+ 2-
3+ 4-
4 ... 20 mA
DC 11 ... 30 V
S# 0639110
P# 0639080
4 ... 20 mA
Test
Coded manufacture date
PIN assignment
Product No.
Serial No.
Power Supply
Test circuit
connection
Signal
5. Starting, operation

9
WIKA operating instructions pressure transmitters, models F-20, F-21
EN
2103870.07 10/2021 EN/DE
■
Remove the protection cap only just before installation and absolutely avoid any damage to the
diaphragm during installation as well (F-21).
■
For Model F-20 you have to provide for a sealing element; exceptions are instruments with
self-sealing threads (e.g. NPT thread). For Model F-21 the sealing is included in delivery.
■
Please refer to our data sheet “Pressure gauge sealing washers AC 09.08” or our website www.wika.de
for details about sealing washers.
■
When mounting the instrument, ensure that the sealing faces of the instrument and the measuring
point are clean and undamaged.
■
Screw in or unscrew the instrument only via the ats using a suitable tool and the prescribed torque.
The appropriate torque depends on the dimension of the pressure connection and on the sealing
element used (form/material). Do not use the case as working surface for screwing in or unscrewing
the instrument.
■
When screwing the transmitter in, ensure that the threads are not jammed.
■
For tapped holes and welding sockets please see Technical Information IN 00.14 for download at
www.wika.de
Electrical connection
■
Connect the instrument to earth via the pressure connection and/or connection terminal 5.
■
For instruments with voltage output or 3 wire current output, use shielded cables, and, if the cables
are longer than 30 m or leave the building, earth the shield at least at one end of the cable.
■
Ensure that the cable diameter you select ts to the cable gland of the connector. Ensure that the
cable gland of the mounted connector is positioned correctly and that the sealings are available and
undamaged.Tighten the threaded connection and check the correct position of the sealings in order
to ensure the ingress protection.
■
Please make sure that the ends of cables with ying leads do not allow any ingress of moisture.
5. Starting, operation

10 WIKA operating instructions pressure transmitters, models F-20, F-21
EN
2103870.07 10/2021 EN/DE
Wiring details
Field case (with internal
spring clip terminals)
2-wire U+ = 1 U- = 2 Test+ = 3 Test- = 4 screen = 5
3-wire U+ = 1 U- = 2 S+ = 3 screen = 5
Wire gauge 7 ... 13 mm
Ingress protection per
IEC 60529
IP67
Cableconnection in the spring clip terminal
■
Cover the stripped wire ends with end splices.
■
Unscrew the case cover.
■
Loosen the cable gland using an open-end wrench, wrench size 24.
■
Lead the cable through the cable gland into the opened case head.
■
Press the corresponding plastic lever at the spring clip terminal down using a screw driver, so that the clamped
contact will be released.
■
Lead the prepared ying lead into the opening and let go of the plastic lever, so that the ying lead will be squeezed
inside the spring clip terminal.
■
After connecting the individual wires, tighten the cable gland and screw down the case cover.
Function of the test circuit for 2-wire
By means of the test circuit the current can be metered during normal operation without having to disconnect the
instrument. For that purpose you have to connect an ammeter (internal resistance < 15 Ohm) to the test +/- terminals.
5. Starting, operation

11
WIKA operating instructions pressure transmitters, models F-20, F-21
EN
2103870.07 10/2021 EN/DE
6. Specications
Specications Model F-20 / F-21
Pressure ranges bar 0.1 0.16 0.25 0.4 0.6 11.6 2.5 4 610 16 25
Over pressure safety bar 1 1.5 2 2 4 5 10 10 17 35 35 80 50
{Vacuum, gauge pressure, compound range, absolute pressure are available}
Materials (other materials see WIKA diaphragm seal program)
■Wetted parts
- Model F-20 Stainless steel
- Model F-21 Stainless steel O-ring: NBR {FPM/FKM}
■Case Stainless steel
■Electrical connection With internal spring clip terminal; cross section max. 2.5 mm2, ground terminals, internal for brass
nickel-plated and {stainless steel} and {stainless steel conduit} threaded connection
■Internal transmission
uid
Synthetic oil
Power supply U+DC 11 ... 30 V
(14 ... 30 V with signal output 0 ... 10 V)
Signal output and
maximum ohmic load RA
RAin
Ohm
4 ... 20 mA, 2-wire RA≤(UB– 10 V) / 0.02 A
0 ... 10 V, 3-wire RA> 10 k
Test circuit signal / max.
load RA
Only for instruments with 4 ... 20 mA signal output. RA< 15 Ohm with 20 mA
Adjustability zero/span %±5 using potentiometers inside the instrument
Response time
(10 ... 90 %) ms ≤1 1)
Insulation voltage DC 500 V
Accuracy 2) % of
span
≤0.5
≤ {0.25} for measuring ranges ≥ 0.25 bar
Non-linearity % of
span
≤ 0.2 (BFSL) according to IEC 61298-2
Non-repeatability % of
span
≤ 0.1
1-year stability % of
span
≤ 0.2 (at reference conditions)
6.Specications

12 WIKA operating instructions pressure transmitters, models F-20, F-21
EN
2103870.07 10/2021 EN/DE
Specications Model F-20 / F-21
Permissible temperature of
■Medium -30 ... +100 °C {-40 ... +125 °C} 1)
■Ambience -20 ... +80 °C {-30 ... +105 °C}
■Storage -40 ... +100 °C
Compensated temp.
range 0 ... +80 °C
Temperature coecients
within compensated temp
range
■Mean TC of zero % of
span ≤0.2 / 10 K (< 0.4 for pressure range ≤0.25 bar)
■Mean TC of range % of
span ≤0.2 / 10 K
CE-conformitiy ■Pressure equipment directive
■EMC directive 3)
EN 61326 emission (group 1, class B) and immunity (industrial environments)
■RoHS directive
Shock resistance g 600 according to IEC 60068-2-27 (mechanical shock)
Vibration resistance g 10 according to IEC 60068-2-6 (vibration under resonance)
Wiring protection
■Overvoltage protection DC 36 V
■Short-circuit proofness Sig+ towards UB-
■Reverse polarity
protection UB+ towards UB-
Weight kg Approx. 0.35
{ } Items in curved brackets are optional extras for additional price
1) Response time: ≤10 ms at medium temperatures below <-30 °C
2) Including non-linearity, hysteresis, zero point and full scale error (corresponds to error of measurement per IEC 61298-2). Calibrated in vertical mounting position
with process connection facing downwards.
3) The existence of strong electromagnetic elds in a frequency range of < 2.7 GHz can result in increased measured errors up to 1 % of span. Do not install the
instruments in the vicinity of strong electromagnetic sources of interference (e.g. transmitting device, radio equipment), or use sheath current lters where applicable.
When designing your plant, take into account that the stated values (e.g. over pressure safety) apply
depending on the material, thread and sealing element used.
6.Specications

13
WIKA operating instructions pressure transmitters, models F-20, F-21
EN
2103870.07 10/2021 EN/DE
Functional test
The output signal must be proportional to the pressure. If not, this might point to a damage of the
diaphragm. In that case refer to chapter 9 “Troubleshooting”.
WARNING!
■
Open pressure connections only after the system is without pressure!
■
Observe the ambient and working conditions outlined in chapter 6 “Specications”.
■
Please make sure that the pressure transmitter is only used within the overload threshold limit at all times!
WARNING!
■
When touching the pressure transmitter, keep in mind that the surfaces of the instrument components
might get hot during operation.
7. Adjustment of zero point / span
We do not recommend to adjust the span potentiometer. It is used for adjustment ex factory and should not
be adjusted by you unless you have adequate calibration equipment at your disposal (at least three times
more accurate than the instrument being tested).
■
Make sure wires are not cut or pinche during disassembly and reassembly of the connector. Open the pressure
transmitter by twisting o the eld case cover.
■
Adjust the zero point (Z) by generating the lower limit of the pressure range.
■
Adjust the span (S) by generating the higher limit of the pressure range.
■
Check the zero point.
■
If the zero point is incorrect, repeat procedure as required.
■
Reassemble the instrument carefully.
■
Make sure all sealings and o-rings are not damaged and correctly installed to assure the rated moisture ingress protection.
6.Specications/7.Adjustmentofzeropoint/span

14 WIKA operating instructions pressure transmitters, models F-20, F-21
EN
2103870.07 10/2021 EN/DE
Recommended recalibration cycle: 1 year
8. Maintenance
WIKA pressure transmitters require no maintenance.
Have repairs performed by the manufacturer only.
9. Trouble shooting
WARNING!
Open pressure connections only after the system is without pressure!
WARNING!
■
Take precautions with regard to remaining media in removed pressure transmitters. Remaining media
in the pressure port may be hazardous or toxic!
■
Remove the pressure transmitter from service and mark it to prevent it frombeing used again
accidentally, if it becomes damaged or unsafe for operation.
■
Have repairs performed by the manufacturer only.
Z = Zero
S = Span
7. Adjustment of zero point / span / 8. Maintenance / 9. Trouble shooting

15
WIKA operating instructions pressure transmitters, models F-20, F-21
EN
2103870.07 10/2021 EN/DE
Do not insert any pointed or hard objects into the pressure port for cleaning to prevent damage to the diaphragm of the
pressure connection.
Please verify in advance if pressure is being applied (valves/ ball valve etc. open) and if the right voltage supply and the
right type of wiring (2-wire/ 3-wire) has been chosen?
Fault Possible cause Procedure
No output signal No/incorrect voltage supply or current spike Adjust the voltage supply to correspond
with the Operating Instructions *)
Cable break Check connections and cable
No/False output signal Incorrectly wired (e.g. Connected as 2-wire instead of
3-wire system)
Follow pin assignment (see Instrument
Label / Operating Instructions)
Output signal unchanged
after change in pressure
Mechanical overload through overpressure Replace instrument; if failure reoccurs,
consult the manufacturer *)
Wrong supply voltage or current spike Replace instrument
Abnormal output signal Span incorrectly adjusted Use appropriate reference
Signalspandroppingo/
too small
Diaphragm is damaged, e.g. through impact, abrasive/
agressive media; corrosion of diaphragm/pressure
connector; transmission uid missing.
Contact the manufacturer and replace the
instrument
Seal/Sealing face damaged/contaminated, seal mounted
incorrectly, threads crossed
Clean the seal/sealing face, possibly
replace the seal.
Moisture present (e.g. at the cable tail) Install the cable correctly
Power supply too high/too low Correct the power supply in line with the
Operating Instructions
Mechanical overload through overpressure Re-calibrate the instrument *)
Signal span erratic Electromagnetic interference source in the vicinity, e.g.
inverter drive
Shield the device; shield the cables;
remove the interference source.
Abnormal zero point signal Diaphragm is damaged, e.g. through impact, abrasive/
agressive media; corrosion of diaphragm/pressure
connector.
Replace instrument
Zero point signal unstable/
too low/high
Moisture present (e.g. at the cable tail) Install the cable correctly
In case of unjustied reclamation we charge the reclamation handling expenses.
*) Make sure that after the setting the unit is working properly. In case the error continues to exist send in the instrument for reparation (or replace the unit).
If the problem persists, contact our sales department.
9. Trouble shooting

16 WIKA operating instructions pressure transmitters, models F-20, F-21
EN
2103870.07 10/2021 EN/DE
CAUTION!
If faults cannot be eliminated by means of the measures listed above, the pressure transmitter must be
shut down immediately, and it must be ensured that signal is no longer present, and it must be prevented
from being inadvertently put back into service. In this case, contact the manufacturer.
USA, Canada
If the problem continues, contact WIKA or an authorized agent for assistance. If the pressure transmitter must be
returned obtain an RMA (return material authorization) number and shipping instructions from the place of purchase.
Be sure to include detailed information about the problem. Pressure transmitters received by WIKA without a valid RMA
number will not be accepted.
Processmaterialcerticate(Contaminationdeclarationforreturnedgoods)
Purge / clean dismounted instruments before returning them in order to protect our employees and the environment
from any hazard caused by adherent remaining media. Service of instruments can only take place safely when a
Product Return Form has been submitted and fully lled-in. This Return Form contains information on all materials with
which the instrument has come into contact, either through installation, test purposes, or cleaning. You can nd the
Product Return Form on our internet site (www.wika.de / www.wika.com).
10. Storage, disposal
WARNING!
When storing or disposing of the pressure transmitter, take precautions with regard to remaining media
in removed pressure transmitters. We recommend cleaning the transmitter properly and carefully.
Remaining media in the pressure port may be hazardous or toxic!
Storage
Mount the protection cap when storing the pressure transmitter in order to prevent any damage to the diaphragm (F-21).
Disposal
Dispose of instrument components and packaging materials in accordance with the respective waste treatment and
disposal regulations of the region or country to which the instrument is supplied.
Do not dispose of with household waste. Ensure a proper disposal in accordance with national regulations.
9. Trouble shooting / 10. Storage, disposal

17
WIKA Betriebsanleitung Druckmessumformer, Typen F-20, F-21
DE
2103870.07 10/2021 EN/DE
Inhalt
Inhalt
1. Allgemeines 18
2. Funktion 19
3. Sicherheit 19
4. Verpackung 21
5. Inbetriebnahme, Betrieb 21
6. Technische Daten 25
7. Einstellung Nullpunkt / Spanne 27
8. Wartung 28
9. Störbeseitigung 28
10. Lagerung, Entsorgung 31

18 WIKA Betriebsanleitung Druckmessumformer, Typen F-20, F-21
DE
2103870.07 10/2021 EN/DE
1. Allgemeines
1. Allgemeines
■
Der in der Betriebsanleitung beschriebene Druckmessumformer wird nach den neuesten Erkenntnissen konstruiert
und gefertigt. Alle Komponenten unterliegen während der Fertigung strengen Qualitäts- und Umweltkriterien. Unsere
Managementsysteme sind nach ISO 9001 und ISO 14001 zertiziert.
■
Diese Betriebsanleitung gibt wichtige Hinweise zum Umgang mit dem Gerät.Voraussetzung für sicheres Arbeiten ist
die Einhaltung aller angegebenen Sicherheitshinweise und Handlungsanweisungen.
■
Die für den Einsatzbereich des Gerätes geltenden örtlichen Unfallverhütungsvorschriften und allgemeinen
Sicherheitsbestimmungen einhalten.
■
Die Betriebsanleitung ist Produktbestandteil und muss in unmittelbarer Nähe des Gerätes für das Fachpersonal
jederzeit zugänglich aufbewahrt werden.
■
Das Fachpersonal muss die Betriebsanleitung vor Beginn aller Arbeiten sorgfältig durchgelesen und verstanden haben.
■
Die Haftung des Herstellers erlischt bei Schäden durch bestimmungswidrige Verwendung, Nichtbeachten dieser
Betriebsanleitung, Einsatz ungenügend qualizierten Fachpersonals sowie eigenmächtiger Veränderung am Gerät.
■
Es gelten die allgemeinen Geschäftsbedingungen in den Verkaufsunterlagen.
■
Technische Änderungen vorbehalten.
■
Weitere Informationen:
- Internet-Adresse: www.wika.de / www.wika.com
- zugehöriges Datenblatt: PE 81.19
- Anwendungsberater: Tel.: +49 9372 132-0
Fax: +49 9372 132-406
Abkürzungen
2-Leiter Zwei Anschlussleitungen dienen zur Spannungsversorgung. Der Speisestrom ist das Mess-Signal.
3-Leiter Zwei Anschlussleitungen dienen zur Spannungsversorgung.Eine Anschlussleitung dient für das Mess-Signal.
U+ Positiver Versorgungsanschluss
U- Negativer Versorgungsanschluss
S+ Positiver Messanschluss

19
WIKA Betriebsanleitung Druckmessumformer, Typen F-20, F-21
DE
2103870.07 10/2021 EN/DE
2. Funktion / 3. Sicherheit
2. Funktion
F-20: Druckanschluss mit innenliegender Membran (Standardausführung).
F-21: Druckanschluss mit frontbündiger Membrane für hochviskose oder kristallisierende Medien, die die Bohrung des
Druckanschlusses zusetzen können.
Mittels Sensorelement und unter Zuführung von Hilfsenergie wird über die Verformung einer Membran der anstehende
Druck in Ihrer Anwendung in ein verstärktes standardisiertes elektrisches Signal umgewandelt. Dieses elektrische
Signal verändert sich proportional zum Druck und kann entsprechend ausgewertet werden.
3. Sicherheit
3.1 Symbolerklärung
WARNUNG!
… weist auf eine möglicherweise gefährliche Situation hin, die zum Tod oder zu schweren Verletzungen
führen kann, wenn sie nicht gemieden wird.
VORSICHT!
… weist auf eine möglicherweise gefährliche Situation hin, die zu geringfügigen oder leichten
Verletzungen bzw. Sach- und Umweltschäden führen kann, wenn sie nicht gemieden wird.
WARNUNG!
… weist auf eine möglicherweise gefährliche Situation hin, die durch heiße Oberächen oder
Flüssigkeiten zu Verbrennungen führen kann, wenn sie nicht gemieden wird.
Information
… hebt nützliche Tipps und Empfehlungen sowie Informationen für einen ezienten und störungsfreien
Betrieb hervor.
3.2 Bestimmungsgemäße Verwendung
Der Druckmessumformer dient der Messung von Druck. Der gemessene Druck wird als elektrisches Signal ausgegeben.
Den Druckmessumformer nur in Anwendungen verwenden, die innerhalb seiner technischen Leistungsgrenzen liegen
(z. B. max. Umgebungstemperatur, Materialverträglichkeit, ...).

20 WIKA Betriebsanleitung Druckmessumformer, Typen F-20, F-21
DE
2103870.07 10/2021 EN/DE
→ Leistungsgrenzen siehe Kapitel 6 „Technische Daten“.
Das Gerät ist ausschließlich für den hier beschriebenen bestimmungsgemäßen Verwendungszweck konzipiert und
konstruiert und darf nur dementsprechend verwendet werden.
Ansprüche jeglicher Art aufgrund von nicht bestimmungsgemäßer Verwendung sind ausgeschlossen.
3.3 Personalqualikation
Fachpersonal
Das Fachpersonal ist aufgrund seiner fachlichen Ausbildung, seiner Kenntnisse der Mess- und Regelungstechnik
und seiner Erfahrungen sowie Kenntnis der landesspezischen Vorschriften, geltenden Normen und Richtlinien in der
Lage, die beschriebenen Arbeiten auszuführen und mögliche Gefahren selbstständig zu erkennen.
Spezielle Einsatzbedingungen verlangen weiteres entsprechendes Wissen, z. B. über aggressive Medien.
WARNUNG!
■
Wählen Sie das richtige Druckmessgerät hinsichtlich Messbereich, Ausführung und spezischen
Messbedingungen vor Montage oder Inbetriebnahme.
■
Halten Sie die entsprechenden landesspezischen Vorschriften ein und beachten Sie bei speziellen
Anwendungen die geltenden Normen und Richtlinien (z. B. bei gefährlichen Messstoen wie
Acetylen, brennbaren oder giftigen Stoen sowie bei Kälteanlagen und Kompressoren). Wenn
Sie die entsprechenden Vorschriften nicht beachten, können schwere Körperverletzungen und
Sachschäden entstehen!
■
Önen Sie Anschlüsse nur im drucklosen Zustand!
■
Betreiben Sie das Druckmessgerät immer innerhalb des Überlastgrenzbereiches!
■
Beachten Sie die Betriebsparameter gemäß Kapitel 6 „Technische Daten“.
■
Beachten Sie die Technischen Daten zur Verwendung des Druckmessgerätes in Verbindung mit
agressiven / korrosiven Medien und zur Vermeidung von mechanischen Gefährdungen.
■
Stellen Sie sicher, dass das Druckmessgerät nur bestimmungsgemäß -also wie in der folgenden
Anleitung beschrieben- betrieben wird.
■
Unterlassen Sie unzulässige Eingrie und Änderungen am Druckmessgerät, welche nicht in dieser
Betriebsanleitung beschrieben sind.
■
Setzen Sie das Druckmessgerät außer Betrieb und schützen Sie es gegen versehentliche
Inbetriebnahme, wenn Sie Störungen nicht beseitigen können.
■
Ergreifen Sie Vorsichtsmaßnahmen für Messstoreste in ausgebauten Druckmessgeräten.
Messstoreste können zur Gefährdung von Menschen, Umwelt und Einrichtung führen!
■
Lassen Sie Reparaturen nur vom Hersteller durchführen.
■
Önen Sie den Stromkreis, bevor Sie den Stecker / Deckel abnehmen.
3. Sicherheit
Other manuals for F-20
1
This manual suits for next models
1
Table of contents
Languages:
Other WIKA Transmitter manuals
Popular Transmitter manuals by other brands

Boston Scientific
Boston Scientific REF3200 user manual

RKI Instruments
RKI Instruments 65-2396RK 04 Series Operator's manual

FlowLine
FlowLine EchoPulse LR30 Series quick start guide

WAREMA
WAREMA WMS operating instructions

Vega
Vega VEGABAR 82 operating instructions

Gems Sensors & Controls
Gems Sensors & Controls UCL-510 manual