
11
Dimensions in parentheses are in
millimeters unless otherwise specified.
INSTALLATION INSTRUCTIONS
CONTACT
INFORMATION
Copies of the
standards listed
may be obtained
from:
*National Fire
Protection
Association
Batterymarch Park
Quincy,
Massachusetts
02269
**Canadian
Standard
Association
178 Rexdale Blvd.
Etobicoke
(Toronto), Ontario
M9W 1R3
GAS SUPPLY REQUIREMENTS
LINE PRESSURE TESTING
Testing above 1/2psi (3.5 kPa) 14" (34.9 mb)
WC (gauge):
The cooktop and its individual
shut-off valve must be disconnected from
the gas supply piping system during any
pressure testing of that system at test pres-
sures greater than 1/2psi (3.5 kPa).
Testing below 1/2psi (3.5 kPa) 14" (34.9 mb)
WC (gauge) or lower:
The cooktop must be
isolated from the gas supply piping system
by closing its individual manual shut-off
valve during any pressure testing of the gas
supply piping system at test pressures
equal to or less than 1/2psi (3.5 kPa).
ELECTRICAL REQUIREMENTS
ELECTRICAL SHOCK HAZARD—
Plug into a grounded 3-prong adapter.
Do not remove ground prong.
Do not use an adapter.
Failure to follow these instructions can
result in electric shock, fire or death.
A120 VAC, 60 Hz, 15-amp, fused electrical
supply is required. A time-delay fuse or circuit
breaker is recommended. It is recommended
that a separate circuit serving only this appli-
ance be provided.
Electronic ignition systems operate within
wide voltage limits, but proper ground and
polarity are necessary. In addition to checking
that the outlet provides 120 VAC power and is
correctly grounded, the outlet must be checked
by a qualified electrician to see if it is wired
with correct polarity. A wiring diagram is
provided in the literature package.
This appliance, when installed, must be electri-
cally grounded in accordance with local codes
or, in the absence of local codes, with the
National Electrical Code, ANSI/NFPA 70 latest
edition or Canadian Electrical Code (CSA).
RECOMMENDED GROUND METHOD
IMPORTANT NOTE:
For your personal safety,
this cooktop must be grounded. This cooktop
is equipped with a 3-prong ground plug. To
minimize possible shock hazard, the cord must
be plugged into a mating 3-prong ground-type
outlet, grounded in conformance with the
National Electrical Code, ANSI/NFPA 70 latest
edition*, or Canadian Electrical Code (CSA)**
and all local codes and ordinances. If a mating
outlet is not available, it is the obligation of
the customer to have a properly grounded,
3-prong outlet installed by a qualified electri-
cian.
IMPORTANT NOTE:
If product is connected to
aGFCI protected outlet, nuisance tripping of
power supply may occur, resulting in loss of
product operation.
WIRING DIAGRAM
Awiring diagram covering the control circuit
for each Wolf gas cooktop model can be found
on page 15.
IMPORTANT NOTE:
If codes permit and a
separate ground wire is used, it is recom-
mended that a qualified electrician determine
that the ground path is adequate.
IMPORTANT NOTE:
Check with a qualified
electrician if you arenot surewhether the
cooktop is properly grounded.
IMPORTANT NOTE:
Do not ground to a gas
pipe.