YOKOGAWA TC10 Installation and operation manual

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 1
TC10
TEMPERATURE
CONTROLLER
Engineering Manual
Code: IM 05C01E81-02EN
Third edition: Feb. 2018
Yokogawa Electric Corporation
2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750 Japan
www.yokogawa.com/ns
1. OUTLINE DIMENSIONS (mm)
1.1 INSTRUMENT DIMENSIONS
48
48
48
PV
AT
1411
8 mm max.
Optional
gasket
1.2 PANEL CUT-OUT
65 mm min.
2.56 in min.
45+0.6 mm
1.78+0.023 in
45+0.6 mm
1.78+0.023 in
65 mm min.
2.56 in min.
1.3 MOUNTING REQUIREMENTS
This instrument is intended for permanent installation, for
indoor use only, in an electrical panel which encloses the
rear housing, exposed terminals and wiring on the back.
Select a mounting location having the following characteristics:
1. It should be easily accessible;
2. There is minimum vibrations and no impact;
3. There are no corrosive gases;
4. There are no water or other fluids (i.e. condensation);
5. The ambient temperature is in accordance with the
operative temperature (0 to 50°C);
6. The relative humidity is in accordance with the instrument
specifications (20 to 90%);
The instrument can be mounted on panel with a maximum
thickness of 8 mm.
When the maximum front protection (IP65) is desired, the
optional gasket must be mounted.
2. CONNECTION DIAGRAM
D -
D +
+ + +
+
+
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Out1
Out3
Out2
C
NO
+
-
C
NO
+
-
C
NO +
-
DI1
Out4
DI2
Power
supply
RS485
12 VDC/20 mA max.
Relay Out 1: 4 (4) A/250 VAC
Relay Out 2, 3: 2 (1) A/250 VAC
SSR Out 1, 2 , 3: 10 VDC/15 mA
SSR Out4: 12 VDC/20 mA
Current Out1: 0/4 to 20 mA, 0/2 to 10V
Passive TX, 2 wires, 4 to 20 mA
Pt1000
Pt100
TC
4 to 20 mA (active)
0/12 to 60 mV, 0/1 to 5V, 0/2 to 10V
-
+
-
2.1 GENERAL NOTES ABOUT WIRING
1. Do not run input wires together with power cables.
2. External components (like zener barriers, etc.) connected
between sensor and input terminals may cause errors in
measurement due to excessive and/or not balanced line
resistance or possible leakage currents.
3. When a shielded cable is used, it should be connected at
one point only.
4. Pay attention to the line resistance; a high line resistance
may cause measurement errors.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 2
2.2 INPUTS
2.2.1 Termocouple Input
1
2
+
_
External resistance: 100Ωmax., maximum error 25 mV.
Cold junction: automatic compensation between 0 to 50°C.
Cold junction accuracy: 0.05°C/°C after a warm-up of
20 minutes.
Input impedance: > 1 MΩ.
Calibration: According to EN 60584-1.
Note: For TC wiring use proper compensating cable
preferable shielded.
2.2.2 RTD Pt 100 Input
3
RTD
1
2
Input circuit: Current injection (150 µA).
Line resistance: Automatic compensation up to 20Ω/wire
with maximum error ±0.1% of the input span.
Calibration: According to EN 60751/A2.
Note: The resistance of the 3 wires must be the same.
2.2.3 RTD Pt 1000 Input
2
3
Pt1000
Line resistance: Not compensated.
Pt 1000 input circuit: Current injection (15 µA).
Pt 1000 calibration: According to EN 60751/A2.
2.2.4 V and mV Input
mV
V+
_
+
_
1
2
Input impedance: > 1 MΩfor mV Input
500 kΩfor Volt Input.
2.2.5 mA Input
0/4 to 20 mA input wiring for passive transmitter
using the auxiliary pws
+
_
4 to 20 mA
Passive
transmitter
4
1
Input impedance: < 53Ω.
Internal auxiliary PWS: 12 VDC (±10%), 20 mA max..
0/4 to 20 mA input wiring for passive transmitter
using an external pws
+
_
+
_
1
2
0/4 to 20 mA
Passive
transmitter
_
External
PWS
+
0/4 to 20 mA input wiring for active transmitter
0/4 to 20 mA
Active
transmitter +
_
+
_
1
2
2.2.6 Logic Inputs
Safety notes:
–Do not run logic input wiring together with power cables;
–The instrument needs 150 ms to recognize a contact
status variation;
–Logic inputs are NOT isolated by the measuring input.
A double or reinforced isolation between logic inputs and
power line must be assured by the external elements.
Logic input driven by dry contact
Digital
Input 1
Digital
Input 24
15
16
Maximum contact resistance: 100Ω.
Contact rating: DI1 = 10 V, 6 mA;
DI2 = 12 V, 30 mA.
Logic inputs driven by 24 VDC
+
-
+
-
Digital
Input 1
Digital
Input 24
15
16
Logic status 1: 6 to 24 VDC;
Logic status 0: 0 to 3 VDC.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 3
2.3 OUTPUTS
Safety notes:
–To avoid electrical shocks, connect power line at last.
–For supply connections use No. 16 AWG or larger wires
rated for at last 75°C.
–Use copper conductors only.
–SSR outputs are not isolated. A reinforced isolation must
be assured by the external solid state relays.
–For SSR, mA and V outputs if the line length is longer than
30 m use a shielded wire.
–Do not short-circuit the terminals of the SSR output.
WARNING! Before connecting the output actuators,
we recommend to configure the parameters to
suit your application (e.g.: input type, Control
strategy, alarms, etc.).
2.3.1 Output 1 (OP1)
Relay Output
C
NO
7
8
Contact rating: •4A/250Vcosj=1;
•2A/250Vcosj=0.4.
Operation: 1 x 105.
SSR Output
SSR
+
-
7
8
Logic level 0: Vout < 0.5 VDC;
Logic level 1: 12 V ±20%, 15 mA max..
Current Analog Output
mA
+
-
7
8
mA output:
0/4... 20 mA, galvanically isolated, RL max. 600Ω.
Voltage Analog Output
V
+
-
7
8
V output: 0/2... 10 V
, galvanically isolated
, RL min.: 500Ω.
2.3.2 Output 2 (OP2)
Relay Output
C
NO
13
14
Contact rating: •2A/250Vcosj= 1;
•1A/250Vcosj= 0.4.
Operation: 1 x 105.
SSR Output
SSR
-
+
13
14
Logic level 0: Vout < 0.5 VDC;
Logic level 1: 12 V ±20%, 15 mA max..
2.3.3 Output 3 (OP3)
Relay Output
C
NO
11
12
Contact rating: •2A/250Vcosj= 1;
•1A/250Vcosj= 0.4.
Operation: 1 x 105.
SSR Output
SSR
-
+
11
12
Logic level 0: Vout < 0.5 VDC;
Logic level 1: 12 V ±20%, 15 mA max..
2.3.4 Output 4 (OP4)
SSR Output
SSR
+
-
4
Out4 4
16
Logic level 0: Vout < 0.5 VDC;
Logic level 1: 12 V ±20%, 20 mA max..
Note: Overload protected.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 4
2.4 SERIAL INTERFACE
D +
D -
D +
D -
D +
D -
D +
D -
RS-485
5
6
Interface type: Isolated (50 V) RS-485;
Voltage levels: According to EIA standard;
Protocol type: Modbus RTU;
Byte format: 8 bit with no parity;
Stop bit: 1 (one);
Baud rate:
Programmable between 1200 to 38400 baud;
Address: Programmable between 1 to 254.
Notes: 1. RS-485 interface allows to connect up to 30
devices with one remote master unit.
2. The cable length must not exceed 1.5 km at
9600 baud.
2.5 POWER SUPPLY
Power Supply
9
10
Neutral
Line
Supply Voltage: •24VAC/DC(±10%);
•100to240VAC(-15to+10%).
Notes: 1. Before connecting the instrument to the power
line, make sure that line voltage is equal to the
voltage shown on the identification label;
2. The polarity of the power supply has no importance;
3. The power supply input is NOT fuse protected.
Please, provide a T type 1A, 250 V fuse externally.
3. TECHNICAL CHARACTERISTICS
3.1 TECHNICAL SPECIFICATION
Case:
Plastic, self-extinguishing degree: V-0 according to UL 94;
Front protection: IP 65 (when the optional panel gasket is
mounted) for indoor locations according to EN 60070-1;
Terminals protection: IP 20 according to EN 60070-1;
Installation: Panel mounting;
Terminal block:
16 screw terminals for cables of
0.25 to 2.5 mm2(AWG22 to AWG14) with connection diagram,
tightening torque 0.5 Nm;
Dimensions: 48 x 48, depth 73 mm, (1.89 x 1.89 x 2.87 in.)
Panel cutout: 45[-0,+0.6] x 45[-0,+0.6] mm
(1.78[-0.000,+0.023] x 1.78[-0.000,+0.023] in.)
Weight: 180 g max..
Power supply: • 24 VAC/DC (±10% of the nominal value);
•
100to240VAC(-15to+10%ofthe
nominal value);
Power consumption: 4.5 VA max. (24 VAC/DC)
6.0 VA max. (100 to 240 VAC);
Insulation voltage: 2300 V rms according to EN 61010-1;
Display updating time: 500 ms;
Sampling time: 130 ms;
Resolution: 30000 counts;
Total Accuracy: ±0.5% F.S.V. ±1 digit @ 25°C of room
temperature;
Electromagnetic compatibility and safety requirements
Compliance: directive EMC 2004/108/CE (EN 61326-1),
directive LV 2006/95/CE (EN 61010-1),
UL 61010-1 CSA 61010-1;
Note: During the test, the instrument continues to operate at
the measurement accuracy within specification.
Installation category: II;
Pollution category: 2;
Temperature drift: It is part of the global accuracy;
Operating temperature: 0 to 50°C (32 to 122°F);
Storage temperature:-30to+70°C(-22to+158°F);
Humidity: 20 to 90% RH, not condensing.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 5
4. MODEL AND SUFFIX CODES
Model Code
Suffix codes Description
TC10 -N oCooo DoF Temperature Controller
Fixed code -N Always "-N"
Power supply L 24 VAC/DC (Custom order)
H 100 to 240 VAC
Fixed code C Always "C"
OUT1 - 3
R N N Relay output for on/off control
RRR
Relay output with 2 alarm relays,
for ON/OFF or Heat/Cool control
with 1 alarm
V N N DC Output for SSR
V R R
DC Output for SSR with 2 alarm
relays or DCV and relay output
for Heat/Cool control with 1
alarm
V V R 2 DCV outputs for SSR with 1
relay (Custom order)
A R R
Analog output with 2 alarm relays,
or analog output and relay output
for Heat/Cool control with 1 alarm
IN/OUT4 (Fixed code) D
Always "D" - Selectable I/O (logic
input/12 V SSR drive output/12VDC
20 mA transmitter power supply
Serial communication S RS485 Modbus
N None
Fixed code F Always “F”
Option Code /GK Panel gasket for IP65

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 6
5. CONFIGURATION PROCEDURE
5.1 INTRODUCTION
When the instrument is powered, it starts immediately to work
according to the parameters values loaded in its memory.
The instrument behaviour and its performance are governed
by the value of the stored parameters.
At the first start up the instrument will use a “default”
parameter set (factory parameter set); this set is a generic
one (e.g. a TC J input is programmed).
WARNING! Before connecting the output actuators,
we recommend to configure the parameters to
suit your application (e.g.: input type, Control
strategy, alarms, etc.).
To change these parameters you need to enter the
“Configuration mode”.
5.2 INSTRUMENT BEHAVIOUR AT
POWER ON
At power ON the instrument can start in one of the following
mode depending on its configuration:
Auto mode
–The upper display shows the measured value;
–The lower display shows the Set point value;
–The decimal figure of the less significant digit of the lower
display is OFF;
–The instrument is performing the standard closed loop control.
Manual mode (OPLO)
–The upper display shows the measured value;
–The lower display shows the power output [preceded by H
(for heating) or C(forcooling)].TheMANLEDislit;
–The instrument does not perform Automatic control;
–The control output is equal to 0% and can be manually
modified by and buttons.
Stand by mode (St.bY)
–The upper display shows the measured value;
–The lower display shows alternately the set point value and
the message St.bY or od;
–The instrument performs no control (the control outputs
are OFF);
–The instrument is working as an indicator.
We define all the above described conditions as
“Standard Display”.
5.3 HOW TO ENTER THE
“CONFIGURATION MODES”
Note: The TC10 is equipped with two different “configuration”
methods:
A) The “code” configuration method;
B) The “complete” configuration method.
The “code” configuration method is really fast but modifies
only the most common configuration parameters.
The “complete” configuration method allows to take
advantage of all instrument features, giving more capabilities
it requires more actions and time.
Note that you can take advantage by both methods because
if
you use the code configuration and then you enter in the
complete configuration, all selections made by code are still valid.
In both cases the instrument have one complete parameter set.
We call this set “configuration parameter set” (or
“configuration parameters”).
When code configuration method is used all the parameters
not modified by the code will maintain their default values.
In both cases the access to the configuration parameters is
protected by a password (a specific password for each method).
Note: The instrument will show only the parameters consis-
tent with the specific hardware and in accordance with
the value assigned to the previous parameters
(e.g.: if you set an output as “not used” the instrument
will mask all other parameters related to this output).
5.3.1 “Code” configuration procedure
The controller configuration (Input type, Control mode, etc.)
can be made entering two 4-digit codes.
Before to enter into code configuration we suggest you to
prepare the two codes according to the tables that follow.
Notes: 1. During the Code configuration procedure there is
no timeout.
2. To leave, at any time, the Configuration session
without
saving the settings made, press the
button.
To enter into code configuration proceed as follows:
1. Push the button for more than 3 seconds.
The upper display will show PASS (flashing) while the
lower display will show 0;
2. Using and buttons set the password programmed
inparameter[120]PAS4. The factory default password
for Code configuration is 300;
3. Push the button;
If the password is correct the instrument will show one of
the following conditions:
• If no code is present, the display shows codE on the
upper display and oFF on the lower display.
Push the button to continue.
The upper display will flash cod1 while the lower display
shows 0000.
• If a previous code was stored, the upper display will
flash cod1 while the lower display shows the value of
cod1 stored in memory.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 7
4. Using and buttons set the code 1 value
according to the following tables.
LMNO
Prepare your code 1
Input Type and Range L M
TC J -50 to +1000°C 0 0
TC K -50 to +1370°C 0 1
TC S -50 to 1760°C 0 2
TC R -50 to +1760°C 0 3
TC T -70 to +400°C 0 4
PT 100 -200 to +850°C 0 7
PT 1000 -200 to +850°C 0 8
Linear 0 to 60 mV 0 9
Linear 12 to 60 mV 1 0
Linear 0 to 20 mA (this selection forces Out 4 = TX) 1 1
Linear 4 to 20 mA (this selection forces Out 4 = TX) 1 2
Linear 0 to 5 V 1 3
Linear 1 to 5 V 1 4
Linear 0 to 10 V 1 5
Linear 2 to 10 V 1 6
TC J -58 to +1832°F 1 7
TC K -58 to +2498°F 1 8
TC S -58 to 3200°F 1 9
TC R -58 to +3200°F 2 0
TC T -94 to +752°F 2 1
PT 100 -328 to +1562°F 2 4
PT 1000 -328 to +1562°F 2 5
LMNO
c%d1:
Control mode OP1 OP2 OP3 OP4 N O
ON/OFF heating = H H AL1 AL2 AL3 0 0
NU AL1 AL2 H 0 1
ON/OFF cooling = C C AL1 AL2 AL3 0 2
NU AL1 AL2 C 0 3
ON/OFF with neutral
zone (H/C)
H C AL2 AL3 0 4
H AL1 AL2 C 0 5
C H AL2 AL3 0 6
NU H AL2 C 0 7
C AL1 AL2 H 0 8
NU C AL2 H 0 9
PID heating = H H AL1 AL2 AL3 1 0
NU AL1 AL2 H 1 1
PID cooling = C C AL1 AL2 AL3 1 2
NU AL1 AL2 C 1 3
PID double action (H/C)
H C AL2 AL3 1 4
H AL1 AL2 C 1 5
C H AL2 AL3 1 6
NU H AL2 C 1 7
C AL1 AL2 H 1 8
NU C AL2 H 1 9
5. Push the button.
The upper display shows cod2 flashing while the lower
display shows 0000 or the cod2 value stored in memory.
6. Using and buttons set the code 2 value
according to the following tables.
PQRS
Prepare your code 2
Alarm 3 R
Alarm 2 Q
Alarm 1 P
Not used 000
Sensor break 111
Absolute High 222
Low 333
Absolute High/Low External High/Low 444
Internal High/Low 555
Deviation Deviation high 666
Deviation low 777
Band External band 888
Internal band 999
PQRS
c%d2:
Auxiliary functions activation S
None 0
Wattmeter (instantaneous power expressed in W) 1
Wattmeter (energy expressed in Wh) 2
Absolute worked time (expressed in days) 3
Absolute worked time (expressed in hours) 4
7. Push the button.
If the just entered codes are accepted, the upper display
shows code while the lower display shows good.
8. Push the button to save the configuration code and
exit the Code configuration procedure.
Note: After using the “Code configuration” method, it will
always be possible to modify the parameters using the
“Complete configuration” method. If the value of a
parameter among those included in the configuration
codes (cod1 - cod2) gets modified, the instrument
will acquire the change while maintaining all the other
parameters.
WARNING! After a parameter change made as described
in the previous “Note”, when retrieving the
configuration codes (cod1 - cod2), the lower
display will show “oFF” to alert the operator that
one of the parameters has been changed.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 8
5.3.2 Complete configuration procedure
The configuration parameters are collected in various
groups. Every group defines all parameters related with a
specific function (e.g.: control, alarms, output functions).
1. Push the button for more than 3 seconds. The upper
display will show PASS while the lower display will show 0.
2. Using and buttons set the programmed password.
Notes: 1. The factory default password for configuration
parameters is equal to 30.
2. During parameter modification the instrument
continue to perform the control.
In certain conditions, when a configuration chan-
ge can produce a heavy bump to the process, it is
advisable to temporarily stop the controller from
controlling during the programming procedure
(control output will be OFF).
Apasswordequalto2000+theprogrammed
value(e.g.2000+30=2030).
The control will restart automatically when the
configuration procedure will be manually closed.
Push the button
If the password is correct the display will show the acronym
of the first parameter group preceded by the symbol: ]
.
In other words the upper display will show: ]inp
(group of the Input parameters).
The instrument is in configuration mode.
5.4 HOW TO EXIT THE “CONFIGURATION
MODE”
Push button for more than 3 seconds, the instrument will
come back to the “standard display”.
5.5 KEYBOARD FUNCTIONS DURING
PARAMETER CHANGING
A short press allows to exit from the current parameter
group and select a new parameter group.
A long press allows you to close the configuration
parameter procedure (the instrument will come back
to the “standard display”).
When the upper display is showing a group and the
lower display is blank, this key allows to enter in the
selected group.
When the upper display is showing a parameter and
the lower display is showing its value, this key allows
to store the selected value for the current parameter
and access the next parameter within the same group.
Allows to increase the value of the selected parameter.
Allows to decrease the value of the selected parameter.
+ These two keys allow to return to the previous
group. Proceed as follows:
Push the button and maintaining the pressure,
then push the button; release both the buttons.
Note: The group selection is cyclic as well as the selection
of the parameters in a group.
5.6 FACTORY RESET - DEFAULT
PARAMETERS LOADING PROCEDURE
Sometime, e.g. when you re-configure an instrument
previously used for other works or from other people or when
you have made too many errors during configuration and
you decided to re-configure the instrument, it is possible to
restore the factory configuration.
This action allows to put the instrument in a defined
condition (the same it was at the first power ON).
The default data are those typical values loaded in the
instrument prior to ship it from factory.
To load the factory default parameter set, proceed as follows:
1. Press the button for more than 5 seconds. The upper
display will show PASS while the lower display shows 0;
2. Using and buttons set the value -481;
3. Push button;
4. The instrument will turn OFF all LEDs for a few seconds,
then the upper display will show dFLt (default) and then
all LEDs are turned ON for 2 seconds. At this point the
instrument restarts as for a new power ON.
The procedure is complete.
Note: The complete list of the default parameters is available
in Appendix A.
5.7 CONFIGURING ALL THE PARAMETERS
In the following pages we will describe all the parameters of
the instrument. However, the instrument will only show the
parameters applicable to its hardware options in accordance
with the specific instrument configuration (i.e. setting AL1t
[Alarm1type]tononE[notused],allparametersrelatedto
alarm 1 will be skipped).
]inP Group - Main and auxiliary input configuration
[1] SEnS - Input type
Available: Always
Range: J = TC J
crAL = TC K
S = TC S
r = TC R
t = TC T
Pt1 = RTD Pt 100
Pt10 = RTD Pt 1000
0.60 = 0 to 60 mV linear
12.60 = 12 to 60 mV linear
0.20 = 0 to 20 mA linear
4.20 = 4 to 20 mA linear
0.5 = 0 to 5 V linear
1.5 = 1 to 5 V linear
0.10 = 0 to 10 V linear
2.10 = 2 to 10 V linear
Notes: 1. When a TC input is selected and a decimal figure
is programmed (see the next parameter) the max.
displayed value becomes 999.9°C or 999.9°F.
2. Every change of the SEnS parameter setting
willforcethe[2]dP=0anditwillchangeall
parameters related with dP (e.g. set points,
proportional band, etc.).

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 9
[2] dP - Decimal point position
Available: Always.
Range: 0to3 when[1]SenS=Linearinput;
0or1 when[1]SenSdifferentfromlinearinput.
Note: Every change of the dP parameter setting will produce
a change of the parameters related with it (e.g.: set
points, proportional band, etc.).
[3] SSc - Initial scale read-out for linear inputs
Available: Whenalinearinputisselectedby[1]SenS.
Range: -1999 to 9999.
Notes: 1. SSc allows the scaling of the analog input to set
the minimum displayed/measured value.
The instrument will show a measured value up to
5% less then SSc value and than it will show an
underrange error.
2. It is possible to set a initial scale read-out higher
then the full scale read-out in order to obtain a
reverse read-out scaling.
E.g.:
0 mA = 0 mBar and 20 mA = -1000 mBar (vacuum).
[4] FSc - Full scale read-out for linear input
Available: Whenalinearinputisselectedby[1]SenS.
Range: -1999 to 9999.
Notes: 1. Fsc allows the scaling of the analog input to set
the maximum displayed/measured value.
The instrument will show a measured value up to
5%higherthan[4]FScvalueandthenitwillshow
an overrange error.
2. It is possible to set a full scale read-out lower
than the initial scale read-out in order to obtain a
reverse read-out scaling.
E.g.:
0 mA = 0 mBar and 20 mA = -1000 mBar (vacuum).
[5] unit - Engineering unit
Available: Whenatemperaturesensorisselectedby[1]
SenS parameter.
Range: °C = Celsius;
°F = Fahrenheit.
[6] FiL - Digital filter on the measured value
Available: Always.
Range: oFF (No filter);
0.1 to 20.0 s.
Note: This is a first order digital filter applied on the
measured value. For this reason it will affect the
measured value but also the control action and the
alarms behaviour.
[7] inE -
Selection of the Sensor Out of Range type
that will enable the safety output value
Available: Always.
Range: our = When an overrange or an underrange is
detected, the power output will be forced to
thevalueof[8]oPEparameter;
or = When an overrange is detected, the power
outputwillbeforcedtothevalueof[8]oPE
parameter;
ur = When an underrange is detected, the po-
wer output will be forced to the value of
[8]oPEparameter.
[8] oPE - Safety output value
Available: Always.
Range: -100 to 100 % (of the output).
Notes: 1. When the instrument is programmed with one
control action only (heat or cool), setting a value
outside of the available output range, the instrument
will use Zero.
E.g.:
When heat action only has been programmed,
and oPE is equal to -50% (cooling) the instrument
will use Zero.
2. When ON/OFF control is programmed and an out
of range is detected, the instrument will perform
the safety output value using a fixed cycle time
equal to 20 seconds.
[9] io4.F - I/O4 function selection
Available: Always.
Range: on = Out4 will be ever ON (used as a transmitter
power supply);
out4 = Used as digital output 4;
dG2.c = Digital input 2 for contact closure;
dG2.U = Digital input 2 driven by 12 to 24 VDC.
Notes: 1. Setting[9]io4.F=dG2.CordG2U,the[25]O4F
parameterbecomesnotvisiblewhile[11]diF2
parameter will become visible.
2. Setting[9]io4F=onthe[25]O4Fparameterand
the[11]diF2parameterwillNOTbevisible.
3. Setting[9]io4FdifferentfromdG2.cordG2.U,
theinstrumentwillforce[13]diF2parameter
equaltononE.If[11]diF1wasequalto(SP4or
UPDN) it will be forced to nonE.
4. Thetransferfrom[9]io4F=ONto[9]io4F=Out4
willmakethe[25]O4Fparametervisibleequalto
nonE.
[10] diF1 - Digital input 1 function
Available: Always.
Range: oFF = No function;
1 AlarmReset[status];
2 Alarmacknowledge(ACK)[status];
3 Holdofthemeasuredvalue[status]
When the contact is closed the instrument ope-
rates in hold of the measured value;
4 Standbymodeoftheinstrument[status]
When the contact is closed the instrument oper-
ates in stand by mode;
5Manual mode
When the contact is closed the instrument ope-
rates in manual mode;
6 HEAtwithSP1andCooLwith“SP2”[status]
(see “Note about digital inputs”);
7 to 17Reserved;
18 Sequentialsetpointselection[transition]
(see “Note about digital inputs”);
19 SP1/SP2selection[status];
20 Binary selection of the set point made by digital
input 1 (less significant bit) and digital input 2
(mostsignicantbit)[status];
21 Digital input 1 will work in parallel with but-
ton while digital input 2 will work in parallel with
the button.
Note: When[11]diF2isnotavailable,items20and21are
not visible.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 10
[11] diF2 - Digital input 2 function
Available: When[9]Io4.F=diG2.
Range: oFF = No function;
1 AlarmReset[status];
2 Alarmacknowledge(ACK)[status];
3 Holdofthemeasuredvalue[status]
When the contact is closed the instrument ope-
rates in hold of the measured value;
4 Standbymodeoftheinstrument[status]
When the contact is closed the instrument ope-
rates in stand by mode;
5Manual mode
When the contact is closed the instrument ope-
rates in manual mode;
6 HEAtwithSP1andCooLwith“SP2”[status]
(see “Note about digital inputs”);
7 TimerRun/Hold/Reset[transition]
Short closure allows to start timer execution
and to suspend it while a long closure (longer
than 10 seconds) allows to reset the timer;
7 to 17Reserved;
18 Sequentialsetpointselection[transition]
(see “Note about digital inputs”);
19 SP1/SP2selection[status];
20 Binary selection of the set point made by digital
input 1 (less significant bit) and digital input 2
(mostsignicantbit)[status];
21 Digital input 1 will work in parallel with the
button while digital input 2 will work in parallel
with the button.
Notes: 1. When[10]diF1or[11]diF2(e.g.diF1)areequal
to 6 the instrument operates as follows:
• When the contact is open, the control action is an
heating action and the active set point is SP.
• When the contact is closed, the control action
is
a cooling action and the active set point is SP2.
2. When[10]diF1=20,[11]diF2settingisforcedto
20 and diF2 cannot perform another function.
3. When[10]diF1=20and[11]diF2=20,theset
point selection will be in accordance with the
following table:
Dig In1 Dig. In2 Operative set point
Off Off Set point 1
On Off Set point 2
Off On Set point 3
On On Set point 4
4. When[10]diF1isequalto21,[11]diF2setting
is forced to up.du (21 value) and cannot perform
another function.
5. When a “Sequential set point selection” is used
(diF1 or diF2 = 18), every closure of of the logic
input increase the value of SPAT (active set point)
of one step.
The selection is cyclic:
SP -> SP2 -> SP3 -> SP4.
[12] di.A - Digital Inputs Action
Available: Always.
Range: 0 = DI1 Direct action,
DI2 (if configured) Direct action;
1 = DI1 Reverse action,
DI2 (if configured) Direct action;
2 = DI1 Direct action,
DI2 (if configured) Reverse action;
3 = DI1 Reverse action,
DI2 (if configured) Reverse action.
]out Group - Output parameters
13] o1.t - Out 1 type
Available: When the out 1 is a linear output.
Range: 0-20 0 to 20 mA;
4-20 4 to 20 mA;
0-10 0 to 10 V;
2-10 2 to 10 V.
[14] o1.F - Out 1 function
Available: Always.
Range: • When the out 1 is a linear output:
nonE =
Output not used. With this setting the status
of this output can be driven directly from
serial link;
H.rEG = Heating output;
c.rEG = Cooling output;
r.inP = Measured value Analog retransmission.
r.Err = Analog retransmission of the measured
error (PV-SP);
r.SP = Analog retransmission of the operative set
point;
r.SEr = Analog retransmission of a value coming
from serial link;
• When the out 1 is a digital output (relay or SSR):
nonE =
Output not used. With this setting the status
of this output can be driven directly from
serial link;
H.rEG = Heating output;
c.rEG = Cooling output;
AL = Alarm output;
t.out = Reserved;
t.HoF = Reserved;
P.End = Reserved;
P.HLd = Reserved;
P. uit = Reserved;
P.run = Reserved;
P.Et1 = Reserved;
P.Et2 = Reserved;
or.bo = Out-of-range or burn out indicator;
P.FAL = Power failure indicator;
bo.PF = Out-of-range, Burnout and Power failure
indicator;
St.By = Stand By status indicator;
diF1 = Repeats the digital input 1 status;
diF2 = Repeats the digital input 2 status;
on = Out1 always ON;
riSP = Inspection request.
Notes: 1. When two or more outputs are programmed in the
same way, these outputs will be driven in parallel
.
2. The power failure indicator will be reset when the
instrument detect an alarm reset command by
key, digital input or serial link.
3. When no control output is programmed, all the
relative alarm (when present) will be forced to
nonE (not used).

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 11
[15] A.o1L - Initial scale value of the analog
retransmission
Available: WhenOut1isalinearoutputand[14]O1Fis
equal to r.inp, r.Err, r.SP or r.SEr
Range: -1999to[16]Ao1H.
[16] A.o1H
- Full scale value of the analog
retransmission
Available: WhenOut1isalinearoutputand[14]O1Fis
equal to r.inp, r.Err, r.SP or r.SEr.
Range: [15]Ao1Lto9999.
[17] o1.AL - Alarms linked up with the out 1
Available: When[14]o1F=AL.
Range: 0 to 63 with the following rules:
+1= Alarm1;
+2= Alarm2;
+4= Alarm3;
+8= Loopbreakalarm;
+16= Sensorbreak(burnout);
+32=
Overload on Out4 (short circuit on the Out4).
Example 1: Setting3(2+1)theoutputwillbedrivenbythe
alarm 1 and 2 (OR condition).
Example 2:Setting13(8+4+1)theoutputwillbedrivenby
alarm1+alarm3+loopbreakalarm.
[18] o1.Ac - Out 1 action
Available: When[14]o1Fisdifferentfrom“nonE”.
Range: dir = Direct action;
rEU = Reverse action;
dir.r = Direct action with revers LED indication;
rEU.r = Reverse action with reverse LED indication.
Notes: 1. Direct action: the output repeats the status of the
driven element.
E.g.: The output is an alarm output with direct
action. When the alarm is ON, the relay will be
energized (logic output 1).
2. Reverse action: the output status is the opposite
of the status of the driven element.
E.g.: The output is an alarm output with reverse
action. When the alarm is OFF, the relay will be
energized (logic output 1). This setting is usually
named “fail-safe” and it is generally used in
dangerous process in order to generate an alarm
when the instrument power supply goes OFF or
the internal watchdog starts.
[19] o2F - Out 2 function
Available: When the instrument has out 2 option.
Range: nonE = Output not used. With this setting the sta-
tus
of the this output can be driven directly
from
serial link;
H.rEG = Heating output (see warning);
c.rEG = Cooling output;
AL = Alarm output;
t.out = Reserved;
t.HoF = Reserved;
P.End = Reserved;
P.HLd = Reserved;
P. uit = Reserved;
P.run = Reserved;
P.Et1 = Reserved;
P.Et2 = Reserved;
or.bo = Out-of-range or burn out indicator;
P.FAL = Power failure indicator;
bo.PF = Out-of-range, Burnout and Power failure
indicator;
St.By = Stand By status indicator;
diF1 = Out2 repeates the digital input 1 status;
diF2 = Out2 repeates the digital input 2 status;
on = Out 2 always ON;
riSP = Inspection request.For other details see
[14]O1Fparameter.
[20] o2.AL - Alarms linked up with Out 2
Available: When[18]o2F=AL.
Range: 0 to 63 with the following rule:
+1= Alarm1;
+2= Alarm2;
+4= Alarm3;
+8= Loopbreakalarm;
+16= Sensorbreak(burnout);
+32=
Overload on Out 4 (short circuit on OP4).
Formoredetailssee[17]o1.ALparameter.
[21] o2Ac - Out 2 action
Available: When[19]o2Fisdifferentfrom“nonE”.
Range: dir = Direct action;
rEU = Reverse action;
dir.r = Direct action with revers LED indication;
rEU.r = Reverse action with reverse LED indication.
Formoredetailssee[18]o1.Acparameter.
[22] o3F - Out 3 function
Available: When the instrument has out 3 option.
Range: nonE = Output not used. With this setting the status
of the this output can be driven directly from
serial link;
H.rEG = Heating output;
c.rEG = Cooling output;
AL = Alarm output;
t.out = Reserved;
t.HoF = Reserved;
P.End = Reserved;
P.HLd = Reserved;
P. uit = Reserved;
P.run = Reserved;
P.Et1 = Reserved;
P.Et2 = Reserved;
or.bo = Out-of-range or burn out indicator;
P.FAL = Power failure indicator;
bo.PF = Out-of-range, burn out and Power failure
indicator;
St.By = Stand By status indicator
diF1 =
The output repeats the digital input 1 status;
diF2 =
The output repeats the digital input 2 status;
on = Out 3 always ON;
riSP = Inspection request.
Forotherdetailssee[14]O1Fparameter.
[23] o3.AL - Alarms linked up with Out 3
Available: When[21]o3F=AL.
Range: 0 to 63 with the following rule:
+1= Alarm1;
+2= Alarm2;
+4= Alarm3;
+8= Loopbreakalarm;
+16= Sensorbreak(burnout);
+32= OverloadonOut4(shortcircuitonOP4).
Formoredetailssee[17]o1.ALparameter.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 12
[24] o3Ac - Out 3 action
Available: when[21]o3Fisdifferentfrom“nonE”.
Range: dir = Direct action;
rEU = Reverse action;
dir.r = Direct action with revers LED indication;
rEU.r = Reverse action with reverse LED indication.
Formoredetailssee[18]o1.Acparameter.
[25] o4F - Out 4 function
Available: Whenthe[9]io4.F=Out4.
Range: nonE = Output not used. With this setting the status
of the this output can be driven directly
from serial link.
H.rEG = Heating output;
c.rEG = Cooling output;
AL = Alarm output;
t.out = Reserved;
t.HoF = Reserved;
P.End = Reserved;
P.HLd = Reserved;
P. uit = Reserved;
P.run = Reserved;
P.Et1 = Reserved;
P.Et2 = Reserved;
or.bo = Out-of-range or burn out indicator;
P.FAL = Power failure indicator;
bo.PF = Out-of-range, burn out and Power failure
indicator;
St.By = Stand By status indicator.
Forotherdetailssee[14]O1Fparameter.
[26] o4.AL - Alarms linked up with Out 4
Available: When[25]o4F=AL.
Range: 0 to 63 with the following rule.
+1= Alarm1;
+2= Alarm2;
+4= Alarm3;
+8= loopbreakalarm;
+16= Sensorbreak(burnout);
+32= overloadonOut4(shortcircuitonOP4).
Formoredetailssee[17]o1.ALparameter.
[27] o4Ac - Out 4 action
Available: When[25]o4Fisdifferentfrom“nonE”.
Range: dir = Direct action;
rEU = Reverse action;
dir.r = Direct action with revers LED indication;
rEU.r = Reverse action with reverse LED indication.
Formoredetailssee[18]o1.Acparameter.
]AL1 Group - Alarm 1 parameters
[28] AL1t - Alarm 1 type
Available: Always.
Range: • When one or more outputs are programmed as
control output:
nonE = Alarm not used;
LoAb = Absolute low alarm;
HiAb = Absolute high alarm;
LHAo = Absolute band alarm with alarm indication
out of the band;
LHAi = Absolute band alarm with alarm indication
inside the band;
SE.br = Sensor break;
LodE = Deviation low alarm (relative);
HidE = Deviation high alarm (relative);
LHdo = Relative band alarm with alarm indication
out of the band;
LHdi = Relative band alarm with alarm indication
inside the band.
• When no output is programmed as control output:
nonE = Alarm not used;
LoAb = Absolute low alarm;
HiAb = Absolute high alarm;
LHAo = Absolute band alarm with alarm indication
out of the band;
LHAi = Absolute band alarm with alarm indication
inside the band;
SE.br = Sensor break.
Notes: 1. The relative and deviation alarms are “relative” to
the operative set point value.
LoAb
OUT
AL1
AL1
PV
HAL1
time
HiAb
offoffoff OUT
AL1
AL1
PV
HAL1
time
offoffoff
ON ON ON ON
LHAo
PV
AL1H HAL1
time
offoffoff
LHdo
OUT
AL1
AL1L HAL1
PV
AL1H
SP
HAL1
time
OUT
AL1
-AL1L HAL1
offoffoff
ON ON ON ON
2. The (SE.br) sensor break alarm will be ON when
the display shows ---- indication.
[29] Ab1 - Alarm 1 function
Available: When[28]AL1tisdifferentfrom“nonE”.
Range: 0 to 15 with the following rule:
+1=Notactiveatpowerup;
+2=Latchedalarm(manualreset);
+4=Acknowledgeablealarm;
+8=
Relative alarm not active at set point change.
Example:SettingAb1equalto5(1+4)thealarm1willbe
“not active at power up” and “Acknowledgeable”.
Notes: 1. The “not active at power up” selection allows to
inhibit the alarm function at instrument power up
or when the instrument detects a transfer from:
• Manual mode (oplo) to auto mode;
• Stand-by mode to auto mode.
The alarm will be automatically enabled when
the measured value reaches, for the first time,
the alarm threshold ±hysteresis (in other words,
when the initial alarm condition disappears).
PWR ON
AL1
PV
time
offoff
Ab1 = +1
Ab1 = +0
offoff
ON ON
ON
2. A “Latched alarm” (manual reset) is an alarm
that will remain active even if the conditions that
generated the alarm no longer persist. Alarm

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 13
reset can be done only by an external
command
( button, digital inputs or serial link).
Alarm reset Alarm reset
AL1
PV
time
offoff
Ab1 = +2
Ab1 = +0
offoff
ON
ON
3. An “Acknowledgeable” alarm is an alarm that can
be reset even if the conditions that generated the
alarm are still present. Alarm acknowledge can
be done only by an external command ( button,
digital inputs or serial link).
Alarm ACK Alarm ACK
AL1
PV
time
offoff
Ab1 = +4
Ab1 = +0
offoffoff
ON
ON ON
A “relative alarm not active at set point change”
is an alarm that masks the alarm condition after
a set point change until process variable reaches
the alarm threshold ±hysteresis.
Sp2
Sp1
PV
time
Ab1 = +8
Ab1 = +0
ON offoff
AL1
offoffoff
AL1
ON ON ON
ON
4. The instrument does not store in EEPROM the
alarm status. For this reason, the alarm status
will be lost if a power down occurs.
[30] AL1L- For High and low alarms it is the low
limit of the AL1 threshold
- For band alarm it is low alarm threshold
Available: When[28]AL1tisdifferentfrom“nonE”or[28]
AL1t is different from “SE.br”.
Range: From-1999to[31]AL1Hengineeringunits.
[31] AL1H
- For High and low alarms, it is the high
limit of the AL1 threshold
- For band alarm, it is the high alarm
threshold
Available: When[28]AL1tisdifferentfrom“nonE”or[28]
AL1t is different from “SE.br”.
Range: From[30]AL1Lto9999engineeringunits.
[32] AL1- Alarm 1 threshold
Available: When:
[28]AL1t=LoAb-Absolutelowalarm;
[28]AL1t=HiAb-Absolutehighalarm;
[28]AL1t=LodE-Deviationlowalarm(relative);
[28]AL1t=LidE-Deviationhighalarm(relative).
Range: From[30]AL1Lto[31]AL1Hengineeringunits.
[33] HAL1 - Alarm 1 hysteresis
Available: When[28]AL1tisdifferentfrom“nonE”or
[28]AL1tisdifferentfrom“SE.br”.
Range: 1 to 9999 engineering units.
Notes: 1. The hysteresis value is the difference between
the Alarm threshold value and the point the Alarm
automatically resets.
2. When the alarm threshold plus or minus the
hysteresis is out of input range, the instrument
will not be able to reset the alarm.
Example: Input range 0 to 1000 (mBar).
–Set point equal to 900 (mBar);
–Deviation low alarm equal to 50 (mBar);
–Hysteresis equal to 160 (mBar) the theoretical reset point is
900-50+160=1010(mBar)butthisvalueisoutofrange.
The reset can be made only by turning the instrument
OFF, removing the condition that generate the alarm and
then turn the instrument ON again;
–All band alarms use the same hysteresis value for both
thresholds;
–When the hysteresis of a band alarm is bigger than the
programmed band, the instrument will not be able to reset
the alarm.
Example: Input range 0 to 500 (°C).
–Set point equal to 250 (°C);
–Relative band alarm;
–Low threshold equal to 10 (°C);
–High threshold equal to 10 (°C);
–Hysteresis equal to 25 (°C).
[34] AL1d - Alarm 1 delay
Available: When[28]AL1tisdifferentfrom“nonE”.
Range: From oFF (0) to 9999 seconds.
Note: The alarm goes ON only when the alarm condition
persistsforatimelongerthan[34]AL1dtimebutthe
reset is immediate.
[35] AL1o- Alarm 1 enabling during Stand-by mode
and out of range indications
Available: When[28]AL1tisdifferentfrom“nonE”.
Range: 0 = Never;
1 = During stand by;
2 = During overrange and underrange;
3 =
During overrange, underrange and stand-by;
]AL2 Group - Alarm 2 parameters
[36] AL2t - Alarm 2 type
Available: Aways.
Range: • When one or more outputs are programmed as
control output:
nonE = Alarm not used;
LoAb = Absolute low alarm;
HiAb = Absolute high alarm;
LHAo = Absolute band alarm with alarm indication
out of the band;
LHAi = Absolute band alarm with alarm indication
inside the band;
SE.br = Sensor break;
LodE = Deviation low alarm (relative);
HidE = Deviation high alarm (relative);
LHdo = Relative band alarm with alarm indication
out of the band;
LHdi = Relative band alarm with alarm indication
inside the band;
• When no output is programmed as control output:
nonE = Alarm not used;

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 14
LoAb = Absolute low alarm;
HiAb = Absolute high alarm;
LHAo = Absolute band alarm with alarm indication
out of the band;
LHAi = Absolute band alarm with alarm indication
inside the band;
SE.br = Sensor break.
Note: The relative alarm are “relative” to the current set point
(this may be different from the Target setpoint if you
are using the ramp to set point function).
[37] Ab2 - Alarm 2 function
Available: When[36]AL2tisdifferentfrom“nonE”.
Range: 0 to 15 with the following rule:
+1= Notactiveatpowerup;
+2= Latchedalarm(manualreset);
+4= Acknowledgeablealarm;
+8=
Relative alarm not active at set point change.
Example:SettingAd2equalto5(1+4)thealarm2willbe
“not active at power up” and “Acknowledgeable”.
Note: Forotherdetailssee[28]Ab1parameter.
[38] AL2L
- For High and low alarms it is the low
limit of the AL2 threshold
- For band alarm it is low alarm threshold
Available: When[36]AL2tisdifferentfrom“nonE”or[36]
AL2t is different from “SE.br”.
Range: -1999to[39]AL2Hengineeringunits.
[39] AL2H
- For High and low alarms it is the high
limit of the AL2 threshold
-
For band alarm it is high alarm threshold
Available: When[36]AL2tisdifferentfrom“nonE”or
[36]AL2tisdifferentfrom“SE.br”.
Range: From[38]AL2Lto9999engineeringunits.
[40] AL2 - Alarm 2 threshold
Available: When:
[36]AL2t=LoAbAbsolutelowalarm;
[36]AL2t=HiAbAbsolutehighalarm;
[36]AL2t=LodEDeviationlowalarm(relative);
[36]AL2t=LidEDeviationhighalarm(relative).
Range: From[38]AL2Lto[39]AL2Hengineeringunits.
[41] HAL2 - Alarm 2 hysteresis
Available: When[36]AL2tisdifferentto“nonE”or[36]AL2t
is different from “SE.br”.
Range: 1 to 9999 engineering units.
Note: Forotherdetailssee[33]HAL1parameter.
[42] AL2d - Alarm 2 delay
Available: When[36]AL2tdifferentform“nonE”.
Range: From oFF (0) to 9999 seconds.
Note: The alarm goes ON only when the alarm condition
persistforatimelongerthan[42]AL2dtimebutthe
reset is immediate.
[43] AL2o- Alarm 2 enabling during Stand-by mode
and out of range indications
Available: When[36]AL2tdifferentfrom“nonE”.
Range: 0 = Never;
1 = During stand by;
2 = During overrange and underrange;
3 =
During overrange, underrange and stand-by.
]AL3 Group - Alarm 3 parameters
[44] AL3t - Alarm 3 type
Available: Always.
Range: • When one or more outputs are programmed as
control output:
nonE = Alarm not used;
LoAb = Absolute low alarm;
HiAb = Absolute high alarm;
LHAo = Absolute band alarm with alarm indication
out of the band;
LHAi = Absolute band alarm with alarm indication
inside the band;
SE.br = Sensor break;
LodE = Deviation low alarm (relative);
HidE = Deviation high alarm (relative);
LHdo = Relative band alarm with alarm indication
out of the band;
LHdi = Relative band alarm with alarm indication
inside the band.
• When no output is programmed as control output:
nonE = Alarm not used;
LoAb = Absolute low alarm;
HiAb = Absolute high alarm;
LHAo = Absolute band alarm with alarm indication
out of the band;
LHAi = Absolute band alarm with alarm indication
inside the band;
SE.br = Sensor break.
Note: The relative alarm are “relative” to the current set point
(this may be different to the Target set point if you are
using the ramp to set point function).
[45] Ab3 - Alarm 3 function
Available: When[43]AL3tisdifferentfrom“nonE”.
Range: 0 to 15 with the following rule:
+1= Notactiveatpowerup;
+2= Latchedalarm(manualreset);
+4= Acknowledgeablealarm;
+8=
Relative alarm not active at set point change.
Example:SettingAd3equalto5(1+4)thealarm3willbe
“not active at power up” and “Acknowledgeable”.
Note: Forotherdetailssee[29]Ab1parameter.
[46] AL3L- For High and low alarms it is the low
limit of the AL3 threshold
- For band alarm, it is low alarm threshold
Available: When[44]AL3tisdifferentfrom“nonE”or[44]
AL3t is different from “SE.br”.
Range: -1999to[47]AL3Hengineeringunits.
[47] AL3H
-
For High and low alarms it is the high
limit of the AL3 threshold
-
For band alarm it is high alarm threshold
Available: When[44]AL3tisdifferentfrom“nonE”or[44]
AL3t is different from “SE.br”.
Range: From[46]AL3Lto9999engineeringunits.
[48] AL3 - Alarm 3 threshold
Available: When:
• [44]AL3t=LoAbAbsolutelowalarm;
• [44]AL3t=HiAbAbsolutehighalarm;
• [44]AL3t=LodEDeviationlowalarm(relative);
• [44]AL3t=LidEDeviationhighalarm(relative).
Range: From[46]AL3Lto[47]AL3Hengineeringunits.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 15
[49] HAL3 - Alarm 3 hysteresis
Available: When[44]AL3tisdifferentto“nonE”or[44]AL3t
is different from “SE.br”.
Range: 1 to 9999 engineering units.
Note: Forotherdetailssee[33]HAL1parameter.
[50] AL3d - Alarm 3 delay
Available: When[44]AL3tdifferentform“nonE”.
Range: From oFF (0) to 9999 seconds.
Note: The alarm goes ON only when the alarm condition
persistforatimelongerthan[50]AL3dtimebutthe
reset is immediate.
[51] AL3o- Alarm 3 enabling during Stand-by mode
and out of range indications
Available: When[44]AL3tisdifferentfrom“nonE”or
[44]AL3tisdifferentfrom“SE.br”.
Range: 0 = Never;
1 = During stand by;
2 = During overrange and underrange;
3 =
During overrange, underrange and stand-by.
]LbA group - Loop break alarm
General note about LBA alarm
The LBA operate as follows: applying the 100% of the power
output to a process, the process variable, after a time due to the
process inertia, begins to change in a known direction (increases
for an heating action or decreases for a cooling action).
Example: If I apply 100% of the power output to a furnace,
the temperature must go up unless one of the component in
the loop is faulty (heater, sensor, power supply, fuse, etc.)
The same philosophy can be applied to the minimum power.
In our example, when I turn OFF the power to a furnace, the
temperature must go down, if not the SSR is in short circuit,
the valve is jammed, etc..
LBA function is automatically enabled when the PID requires
the maximum or the minimum power.
When the process response is slower than the programmed
limit the instrument generates an alarm.
Notes: 1. When the instrument is in manual mode, the LBA
function is disabled.
2.
When LBA alarm is ON the instrument continues
to perform the standard control. If the process
response comes back into the programmed limit,
the instrument automatically resets the LBA alarm.
3. This function is available only when the programmed
control algorithm is equal to PID (Cont = PID).
[52] LbAt - LBA time
Available: When[56]Cont=PID.
Range: oFF = LBA not used;
1 to 9999 seconds.
[53] LbSt - Delta measure used by LBA during
Soft start
Available: When[52]LbAtisdifferentfromoFF.
Range: oFF = loop break alarm is inhibit during soft start;
1 to 9999 engineering units.
[54] LbAS
- Delta measure used by loop break
alarm (loop break alarm step)
Available: When[52]LbAtisdifferentfromoFF.
Range: 1 to 9999 engineering units.
[55] LbcA - Condition for LBA enabling
Available: when[52]LbAtisdifferentfromoFF.
Range: uP = Enabled when the PID requires the maxi-
mum power only;
dn = Enabled when the PID requires the mini-
mum power only;
both =
Enabled in both condition (when the PID re-
quires the maximum or the minimum power).
LBA application example:
LbAt (LBA time) = 120 seconds (2 minutes);
LbAS (delta LBA) = 5°C.
The machine has been designed in order to reach 200°C in
20 minutes (20°C/min);
When the PID demands 100% power, the instrument starts
the time count.
During time count if the measured value increases more
than 5°C, the instrument restarts the time count. Otherwise
if the measured value does not reach the programmed delta
(5°C in 2 minutes) the instrument will generate the alarm.
]rEG group - Control parameters
The rEG group will be available only when at least one
output is programmed as control output (H.rEG or C.rEG).
[56] cont - Control type:
Available: When at least one output is programmed as con-
trol output (H.rEG or C.rEG).
Range: • When two control action (heat & cool) are pro-
grammed:
Pid = PID (heat and cool);
nr =
Heat/Cool ON/OFF control with neutral zone.
HSEt
HSEt
SP
PV
time
OUTH.rEG
(heating)
OUTc.rEG
(cooling)
offON ON
of
fo
ffON
• When one control action (heat or cool) is programmed:
Pid = PID (heat or cool);
On.FA = ON/OFF asymmetric hysteresis;
On.FS = ON/OFF symmetric hysteresis;
HEAt - On.FA
OUT
H.rEG
SP
PV
HSEt
time
offoff
CooL -On.FA
OUT
C.rEG
SP
PV
HSEt
time
ON ON ON offoff
ON ON ON
HEAt - On.FS
OUT
H.rEG
SP
PV
HSEt
HSEt
time
CooL -On.FS
OUT
H.rEG
SP
PV
HSEt
HSEt
time
ON ON ON
offoff offoff
ON ON ON
Notes: 1. ON/OFF control with asymmetric hysteresis:
• OFF when PV > SP;
• ON when PV < (SP - hysteresis).
2. ON/OFF control with symmetric hysteresis:
• OFF when PV >(SP+hysteresis);
• ON when PV < (SP - hysteresis).

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 16
[57] Auto - Auto tune selection
There are three auto-tune algorithms:
• Oscillating auto-tune;
• Fast auto-tune;
• EvoTune.
1. The oscillating auto-tune is the usual auto-tune and:
• It is more accurate;
• Can start even if PV is close to the set point;
• Can be used even if the set point is close to the
ambient temperature.
2. The fast type is suitable when:
• The process is very slow and you want to be opera-
tive in a short time;
• When an overshoot is not acceptable;
• In multi loop machinery where the fast method reduces
the calculation error due to the effect of the other loops.
3. The EvoTune type is suitable when:
• You have no information about your process;
• You can not be sure about the end user skills;
• You desire an auto tune calculation independently
from the starting conditions (e.g. set point change
during tune execution, etc).
Note: Fast auto-tune can start only when the measured
value(PV)islowerthan(SP+1/2SP).
Available: When[56]cont=PID
Range: -4 to 8 where:
-4 = Oscillating auto-tune with automatic restart
at all set point change;
-3 = Oscillating auto-tune with manual start;
-2 = Oscillating auto-tune with automatic start at
the first power up only;
-1 = Oscillating auto-tune with automatic restart
at every power up;
0 = Not used;
1 = Fast auto tuning with automatic restart at
every power up;
2 = Fast auto-tune with automatic start at the
first power up only;
3 = FAST auto-tune with manual start;
4 = FAST auto-tune with automatic restart at all
set point change.
5 = EvoTune with automatic restart at every
power up;
6 = EvoTune with automatic start at the first
power up only;
7 = EvoTune with manual start;
8 = EvoTune with automatic restart at all set
point change.
[58] Aut.r - Manual start of the auto-tune
Available: When[56]cont=PID.
Range: oFF =
The instrument is not performing the auto-tune;
on = The instrument is performing the auto-tune.
[59] SELF - Self-tune enable
The self-tuning is an adaptive algorithm able to optimize
continuously the PID parameter value.
This algorithm is specifically designed for all process subjected to
big load variation able to change heavily the process response.
Available: When[56]cont=PID.
Range: YES = self-tune active;
no = self-tune not active.
[60] HSEt - Hysteresis of the ON/OFF control
Available: When[56]contisdifferentfromPID.
Range: 0 to 9999 engineering units.
[61] cPdt - Time for compressor protection
Available: When[56]cont=nr.
Range: OFF = Protection disabled
1 to 9999 seconds.
[62] Pb - Proportional band
Available: When[56]cont=PIDand[59]SELF=no.
Range: 1 to 9999 engineering units.
Note: Auto-tune functions calculate this value.
[63] ti - Integral time
Available: When[56]cont=PIDand[59]SELF=no.
Range: • OFF = Integral action excluded;
• 1 to 9999 seconds;
• inF= Integral action excluded.
Note: Auto-tune functions calculate this value.
[64] td - Derivative time
Available: When[56]cont=PIDand[59]SELF=no.
Range: • oFF - derivative action excluded;
• 1 to 9999 seconds.
Note: Auto-tune functions calculate this value.
[65] Fuoc - Fuzzy overshoot control
This parameter reduces the overshoot usually present at
instrument start up or after a set point change and it will be
active only in this two cases.
Setting a value between 0.00 and 1.00 it is possible to slow
down the instrument action during set point approach.
Setting Fuoc = 1 this function is disabled.
PV
SP
time
2
1
3
Available: When[56]cont=PIDand[59]SELF=no.
Range: 0 to 2.00.
Note: Fast auto-tune calculates the Fuoc parameter while
the oscillating one sets it equal to 0.5.
[66] tcH - Cycle time of the heating output
Available: When at least one output is programmed in order
to be the heating output (H.rEG),
[56]cont=PIDand[59]SELF=no.
Range: 1.0 to 130.0 seconds.
[67] rcG - Power ratio between heating and
cooling action (relative cooling gain)
The instrument uses the same PID parameter set for heat
and for cool action but the efficiency of the two actions are
usually different.
This parameter allows to define the ratio between the efficiency
of the heating system and the efficiency of the cooling one.
An example will help us to explain you the philosophy.
Consider one loop of a plastic extruder. The working
temperature is equal to 250°C.
When you want to increase the temperature from 250 to 270°C
(DT = 20°C) using 100% of the heating power (resistor), you
will need 60 seconds.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 17
On the contrary, when you want to decrease the temperature
from 250 to 230°C (DT = 20°C) using 100% of the cooling
power (fan), you will need 20 seconds only.
Inourexampletheratioisequalto60/20=3([67]rcG=3)
and it say that the efficiency of the cooling system is 3 time
more efficient of the heating one.
Available: When two control action are programmed
(H.rEGandc.rEG)and[56]cont=PIDand
[59]SELF=no.
Range: 0.01 to 99.99.
Note: auto-tune functions calculate this value.
[68] tcc - Cycle time of the cooling output
Available: When at least one output is programmed in order
tobethecoolingoutput(c.rEG),[56]cont=PID
and[59]SELF=no.
Range: 1.0 to 130.0 seconds.
[69] rS - Manual reset (integral pre-load)
It allows to drastically reduce the undershoot due to a
hot restart. When your process is steady, the instrument
operates with a steady power output (e.g.: 30%).
If a short power down occurs, the process restarts with a
process variable close to the set point while the instrument
starts with an integral action equal to zero.
Setting a manual reset equal to the average power output (in our
example 30%) the instrument will start with a power output equal
to the value it will use at steady state (instead of zero) and the
undershoot will become very little (in theory equal to zero).
Available: When[56]cont=PID.
Range: -100.0to+100.0%.
[72] od - Delay at power up
Available: When at least one output is programmed as
control output.
Range: oFF: Function not used;
0.01 to 99.59 hh.mm.
Notes: 1. This parameter defines the time during which
(after a power up) the instrument remains in stand
by mode before to start all other function (control,
alarms, program, etc.).
2. When a program with automatic start at power up
and od function are programmed, the instrument
performs od function before to start the program.
3. When an auto-tune with automatic start at power
up and od function are programmed, the autotune
will start at the end of od delay.
[73] St.P - Maximum power output used during
soft start
Available: When at least one output is programmed as
control output.
Range: -100to+100%.
Notes: 1. When St.P parameter have a positive value, the
limit will be applied to the heating output(s) only.
2. When St.P parameter have a negative value, the
limit will be applied to the cooling output(s) only.
3. When a program with automatic start at power
up and soft start function are programmed, the
instrument performs the soft start and than the
program function.
4. The auto-tune function will be performed after
soft start function.
5. The Soft start function is available also when ON/
OFF contro l is used.
[74] SSt - Soft start time
Available: When at least one output is programmed as
control output.
Range: oFF = Function not used;
0.01 to 7.59 hh.mm;
inF = Soft start always active.
[75] SS.tH - Threshold for soft start disabling
Available: When at least one output is programmed as
control output.
Range: -1999 to 9999 engineering units.
Notes: 1. When the power limiter have a positive value (the
limit is applied to the heating action) the soft start
function will be aborted when the measured value
is greater or equal to SS.tH parameter.
2. When the power limiter have a negative value
(the limit is applied to the cooling action) the soft
start function will be aborted when the measured
value is lower or equal to SS.tH parameter.
]SP Group - Set point parameters
The SP group will be available only when at least one output
is programmed as control output (H.rEG or C.rEG).
[76] nSP - Number of used set points
Available: When at least one output is programmed as
control output.
Range: 1 to 4.
Note: When you change the value of this parameter, the
instrument operates as follows:
• [83]A.SPparameterwillbeforcedtoSP.
• The instrument verifies that all used set point are
withinthelimitsprogrammedby[77]SPLLand[78]
SPHL. If an SP is out of this range, the instrument
forces it to the maximum acceptable value
[77] SPLL - Minimum set point value
Available: When at least one output is programmed as
control output.
Range: From-1999to[78]SPHLengineeringunits.
Notes: 1. Whenyouchangethe[77]SPLLvalue,the
instrument checks all local set points (SP, SP2,
SP3 and SP4 parameters) and all set points of the
program([97]Pr.S1,[102]Pr.S2,[107]Pr.S3,[112]
Pr.S4 parameters). If an SP is out of this range, the
instrument forces it to the maximum acceptable value
2. A[77]SPLLchangeproducesthefollowingactions:
• When[84]SP.rt=SPtheremotesetpointwill
be forced to be equal to the active set point
• When[84]SP.rt=trimtheremotesetpointwill
be forced to zero
• When[84]SP.rt=PErctheremotesetpoint
will be forced to zero
[78] SPHL - Maximum set point value
Available: When at least one output is programmed as
control output.
Range: From[78]SPLLto9999engineeringunits.
Note: Forotherdetailssee[78]SPLLparameter.
[79] SP - Set Point 1
Available: When at least one output is programmed as
control output.
Range: From[77]SPLLto[78]SPHLengineeringunits.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 18
[80] SP 2 - Set Point 2
Available: When at least one output is programmed as con-
troloutputand[76]nSP> 2.
Range: From[77]SPLLto[78]SPHLengineeringunits.
[81] SP 3 - Set Point 3
Available: When at least one output is programmed as con-
troloutputand[76]nSP> 3.
Range: From[77]SPLLto[78]SPHLengineeringunits.
[82] SP 4 - Set Point 4
Available: When at least one output is programmed as con-
troloutputand[76]nSP=4.
Range: From[77]SPLLto[78]SPHLengineeringunits.
[83] A.SP - Selection of the active Set point
Available: When at least one output is programmed as
control output.
Range: From“SP”to[76]nSP.
Notes: 1. A[83]A.SPchangeproducesthefollowingactions:
• When[84]SP.rt=SP-theremotesetpoint
will
be forced to be equal to the active set point;
• When[84]SP.rt=trin-theremotesetpointwill
be forced to zero;
• When[84]SP.rt=PErc-theremotesetpoint
will be forced to zero.
2. SP2, SP3 and SP4 selection will be shown
only when the relative set point is enabled (see
[76]nSPparameter).
[84] SP.rt - Remote set point type
These instruments will communicate with each other, using
RS 485 serial interface without a PC. An instrument can be
set as a Master while the other are (as usual) Slave units. The
Master unit can send his operative set point to the slave units.
In this way, for example, is possible to change simultaneously
the set point of 20 instruments by changing the set point of the
master unit (e.g. hot runner application).
SP.rt parameter defines how the slaves units will use the value
coming from serial link.
[133]tr.SPparameter[selectionofthevaluetoberetransmitted
(Master)]allowstodenethevaluesentbymasterunit.
Available: When at least one output is e programmed as
control output and the serial interface is present.
Range: rSP = The value coming from serial link is used
as remote set point (RSP);
trin = The value coming from serial link will be
algebraically added to the local set point
selected by A.SP and the sum becomes
the operative set point;
PErc = The value coming from serial will be scaled
on the input range and this value will be
used as remote set point.
Note: A[84]SPrtchangeproducesthefollowingactions:
• When[84]SP.rt=rSP-theremotesetpointwillbe
forced to be equal to the active set point;
• When[84]SP.rt=trin-theremotesetpointwill
be forced to zero;
• When[84]SP.rt=PErc-theremotesetpointwill
be forced to zero.
Example: A 6 zone reflow-oven for PCB.
The master unit sends its set point value to 5 other zones
(slave controllers).
The Slave zones use it as a set point trim.
The first zone is the master zone and it uses a set point
equal to 210°C.
The second zone has a local set point equal to -45°C.
The third zone has a local set point equal to -45 (°C).
The fourth zone has a local set point equal to -30.
Thefthzonehasalocalsetpointequalto+40.
Thesixthzonehasalocalsetpointequalto+50.
In this way, the thermal profile will be the following:
–Master SP = 210°C;
–Second zone SP = 210 -45 = 165°C;
–Third zone SP = 210 -45 = 165°C;
–Fourth zone SP = 210 - 30 = 180°C;
–FifthzoneSP=210+40=250°C;
–SixthzoneSP=210+50=260°C.
Changing the SP of the master unit, all the other slave units
will immediately change their operative set point.
[85] SPLr - Local/remote set point selection
Available: When at least one output is programmed as
control output.
Range: Loc= Localsetpointselectedby[83]A.SP;
rEn = Remote set point (coming from serial link).
[86] SP.u - Rate of rise for positive set point
change (ramp up)
Available: When at least one output is e programmed as
control output.
Range: • 0.01 to 99.99 units per minute;
• inF = ramp disabled (step transfer).
[87] SP.d - Rate of rise for negative set point
change (ramp down)
Available: When at least one output is e programmed as
control output.
Range: 0.01 to 99.99 units per minute;
inF = ramp disabled (step transfer).
General note about remote set point: when the remote set
point (RSP) with trim action is programmed, the local set
point range becomes the following:
from[77]SPLL+RSPto[78]SPHL-RSP
]PAn group - Operator HMI
[118] PAS2
- Level 2 password: Limited access level
Available: Always.
Range: oFF = Level 2 not protected by password
(as level 1 = Operator level);
1 to 200.
[119] PAS3
- Level 3 password:
Complete configuration level
Available: Always.
Range: 3 to 200.
Note: Setting[118]PAS2equalto[119]PAS3,thelevel2
will be masked.
[120] PAS4
- Level 4 password:
CODE configuration level
Available: Always.
Range: 201 to 400.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 19
[121] uSrb - button function during RUN TIME
Available: Always.
Range: nonE = No function;
tunE = Auto-tune/self-tune enabling. A single
press (longer than 1) starts the auto-tune;
oPLo =
Manual mode. The first pressure puts the
instrument in manual mode (OPLO) while
a
second one puts the instrument in Auto mode;
AAc = Alarm reset;
ASi = Alarm acknowledge;
chSP = Sequential set point selection (note);
St.by = Stand by mode. The first press puts the in-
strument in stand by mode while a second
one puts the instrument in Auto mode;
Str.t = Reserved;
P.run = Reserved;
P.rES = Reserved;
P.r.H.r = Reserved.
Notes: 1. When “Sequential set point selection” is used,
every press of the button (longer than 1
second) increase the value of A.SP (active set
point) of one step.
The selection is cyclic: SP -> SP2 -> SP3 -> SP4
When a new set point is selected using the
key, the display will show for 2 seconds the
acronym of the new set point (e.g. SP2).
2. When “Sequential set point selection” is used, the
numberofsetpointsselectableislimitedby[74]nSP.
[122] diSP - Display management
Available: Always.
Range: nonE = Standard display;
Pou = Power output;
SPF = Final set point;
SPo = Operative set point;
AL1 = Alarm 1 threshold;
AL2 = Alarm 2 threshold;
AL3 = Alarm 3 threshold;;
Pr.tu = Reserved;
Pr.td = Reserved;
P.t.tu = Reserved;
P.t.td = Reserved;
ti.uP = Reserved;
ti.du = Reserved;
PErc =
Percent of the power output used during soft
start (when the soft start time is equal to
infinite, the limit is ever active and it can be
used also when ON/OFF control is selected);
PoS = Reserved.
[123] di.CL - Display colour
Available: Always.
Range: 0 = The display colour is used to show the
actual deviation (PV - SP);
1 = Display red (fix);
2 = Display green (fix);
3 = Display orange (fix).
[124] AdE - Deviation for display colour management
Available: When[123]di.CL=0.
Range: 1 to 9999 engineering units.
[125] diS.t - Display time out
Available: Always.
Range: oFF = The display is ever ON;
0.1 to 99.59 minutes and seconds.
Note: This function allows to turn OFF the display when no
alarm is present and no action is made on the instrument.
When diS.t is different from OFF and no button is
pressed for more than the programmed time out, the
display goes OFF and only 4 segments of the less
significant digit are turned ON in sequence in order to
show that the instrument is working correctly.
If an alarm occures or a buton is pressed, the display
will come back to the normal operation.
[126] FiLd - Filter on the displayed value
Available: Always.
Range: oFF = Filter disabled;
From 0.0 (oFF) to 20.0 engineering units.
Note: This is a “window filter” related to the set point; it is
applied to the displayed value only and it have no
effect on the other functions of the instrument (control,
alarms, etc.).
[128] dSPu - Status of the instrument at power up
Available: Always.
Range: AS.Pr = Starts in the same way it was prior to the
power down;
Auto = Starts in Auto mode;
oP.0 = Starts in manual mode with a power output
equal to zero.
St.bY = Starts in stand-by mode
Notes: 1. Whenyouchangethevalueof[129]oPr.E,the
instrumentforces[130]oPErparametertoAuto.
2. Ifthe“[128]dSPu”parameterisdifferentfrom
“AS.Pr” the memorization function is inhibited.
[129] oPr.E - Operative modes enabling
Available: Always.
Range: ALL = All modes will be selectable by the next
parameter;
Au.oP = Auto and manual (OPLO) mode only will be
selectable by the next parameter;
Au.Sb = Auto and Stand-by modes only will be se-
lectable by the next parameter.
Note: Whenyouchangethevalueof[129]oPr.E,the
instrumentforces[130]oPErparameterequaltoAuto.
[130] oPEr - Operative mode selection
Available: Always.
Range: • When[129]oPr.E=ALL:
Auto = Auto mode;
oPLo = Manual mode;
St.bY = Stand by mod.e
• When[129]oPr.E=Au.oP:
Auto = Auto mode;
oPLo = Manual mode.
• When[129]oPr.E=Au.Sb:
Auto = Auto mode;
St.bY = Stand by mode.
]Ser group - Serial link parameter
[131] Add - Instrument address
Available: Always.
Range: oFF = Serial interface not used;
1 to 254.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 20
[132] bAud - Baud rate
Available: When[131]AdddifferentfromoFF.
Range: 1200 = 1200 baud;
2400 = 2400 baud;
9600 = 9600 baud;
19.2 = 19200 baud;
38.4 = 38400 baud.
[133] trSP
- Selection of the value to be
retransmitted (Master)
Available: When[131]AdddifferentfromoFF.
Range: nonE = Retransmission not used (the instrument is
a slave);
rSP = The instrument become a Master and it
retransmits the operative set point;
PErc = The instrument become a Master and it
retransmits the power output.
Note: Formoredetailssee[84]SP.rt(Remotesetpointtype)
parameter.
]COn Group - Consumption parameters
[134] Co.tY - Count type
Available: Always.
Range: oFF Not used;
1 Instantaneous power (kW);
2 Consumed energy (kWh);
3 Reserved;
4 Total worked days: number of hours the instru-
ment is turned ON divided by 24;
5 Total worked hours: number of hours that the
instrument is turned ON;
6 Total worked days with threshold: number of
hours the instrument is turned ON divided by 24,
the controller is forced in stand-by when Co.ty
valuereachesthethresholdsetin[137]h.Job;
7
Total worked hours with threshold: number of
hours that the instrument is turned ON, the
controller is forced in stand-by when Co.ty value
reachesthethresholdsetin[137]h.Job;
8 Totalizer of control relay worked days: number
of hours the control relay has been in ON condi-
tion, divided by 24;
9
Totalizer of control relay worked hours: number of
hours the control relay has been in ON condition;
10 Totalizer of control relay worked days with
threshold: number of hours the control relay
has been in ON condition divided by 24, the
controller is forced in stand-by when Co.ty
value
reachesthethresholdsetin[137]h.Job;
11 Totalizer of control relay worked hours with
threshold: number of hours the control relay has
been in ON condition, the controller is forced in
stand-by when Co.ty value reaches the th-
resholdsetin[137]h.Job.
Notes: 1. Selections 4 to 11 represent an internal count:
these modes calculate the instrument work in
hours or days. When the count reaches the
thresholdsetwithparameter[137]h.Jobthe
display shows “r.iSP” (Inspection Requested).
The count reset (with r.iSP cancellation) can be
done only by changing the threshold value
-
parameter[137]h.Job.
Using counting methods 6, 7, 10, 11, the count
reset causes the controller to exit the stand-by
status returning to the control status
.
[135] UoLt - Nominal Voltage of the load
Available: When[134]Co.tY=istor
[134]Co.tY=hor
[134]Co.tY=S.S.
Range: 1 to 9999 (V).
[136] cur - Nominal current of the load
Available: When[134]Co.tY=istor
[134]Co.tY=hor
[134]Co.tY=S.S.
Range: 1 to 999 (A).
[137] h.Job - Threshold of the working period
Available: When[134]Co.tY=tot.dor
[134]Co.tY=tot.H.
Range: oFF = Threshold not used
1 to 9999 days when [134]Co.tY=4;
1 to 9999 hours when [134]Co.tY=5.
[138] t.Job - Worked time (not resettable)
Available: Always.
Range: 1 to 9999 days.
]CAL group - User calibration group
This function allows to calibrate the complete measuring
chain and to compensate the errors due to:
–Sensor location;
–Sensor class (sensor errors);
–Instrument accuracy.
[139] A.L.P - Adjust Low Point
Available: Always.
Range: -1999 to (AH.P - 10) engineering units.
Note: The minimum difference between AL.P and AH.P is
equal to 10 Engineering Units.
[140] A.L.o - Adjust Low Offset
Available: Always.
Range: -300to+300engineeringunits.
[141] A.H.P - Adjust High Point
Available: Always.
Range: From(AL.P+10)to9999engineeringunits.
Note: The minimum difference between AL.P and AH.P is
equal to 10 Engineering Units.
[142] A.H.o - Adjust High Offset
Available: Always.
Range: -300to+300EngineeringUnits.
Example: Environmental chamber with an operative range:
10 to 100°C.
1. Insert in the chamber a reference sensor connected with
a reference instrument (usually a calibrator).
2. Start the control of the instrument, and set a set point equal to
the minimum value of the operative range (e.g.: 10°C). When
the temperature in the chamber is steady, take note of the
temperature measured by the reference system (e.g.: 9°C).
3. Set[139]A.L.P=10(lowworkingpoint)and[140]
A.L.o = -1
(it is the difference between the reading of the
instrument and the reading of the reference system). Note
that after this set the measured value of the instrument is
equal to the measured value of the reference system.
4. Set a set point equal to the maximum value of the
Other manuals for TC10
2
Table of contents
Other YOKOGAWA Temperature Controllers manuals

YOKOGAWA
YOKOGAWA UP150 User manual

YOKOGAWA
YOKOGAWA TC10 User manual

YOKOGAWA
YOKOGAWA UT130 User manual

YOKOGAWA
YOKOGAWA UT150 User manual

YOKOGAWA
YOKOGAWA UT130 Manual

YOKOGAWA
YOKOGAWA UP150 User manual

YOKOGAWA
YOKOGAWA UP150 User manual

YOKOGAWA
YOKOGAWA TC10 User manual

YOKOGAWA
YOKOGAWA UT150 User manual

YOKOGAWA
YOKOGAWA XS550 User manual
Popular Temperature Controllers manuals by other brands

S+S Regeltechnik
S+S Regeltechnik THERMASGARD RGTF1 Series Operating Instructions, Mounting & Installation

Omega
Omega CN8200 Series user guide

Kampmann
Kampmann KaControl Assembly and installation instructions

Siemens
Siemens RDF300 Series Documentation

Laird
Laird Sentrius RS1 Series user guide

Diymore
Diymore W1209 quick start guide