
036-21122-002 Rev. B (0103)
Unitary Products Group 5
COOLING CAPACITY - With Air Handler Coils
UNIT MODEL
AIR HANDLER
COIL
1
MODEL
COOLING
MODEL ELECTRIC
2
HEAT KW WRATED
CFM
NET MBH SEER
W/O TXV
SEER
+ TXV
3
EER
TOTAL SENS.
1 PH 10 SEER AC WITH N1AH / G2FD
HABA-F018S N1AHB0806 2,5,8,10 17 G2FD024(S,H)17 650 19.0 14.1 10.50 - 9.80
HABA-F024S N1AHB0806 2,5,8,10 17 G2FD024(S,H)17 800 24.4 18.1 10.50 - 9.55
N1AHB0806 2,5,8,10 17 G2FD030(S,H)17 850 25.0 18.5 10.60 - 9.65
HBBA-F030S N1AHB1206 5,8,10,15,19 17 G2FD030(S,H)17 1000 29.0 21.5 10.30 - 9.45
N1AHB1206 5,8,10,15,19 17 G2FD036(S,H)17 1000 30.0 22.2 10.50 - 9.65
HBBA-F036S N1AHB1206 5,8,10,15,19 17 G2FD036(S,H)17 1200 33.8 25.0 10.00 - 9.20
N1AHB1206 5,8,10,15,19 17 G2FD046(S,H)17 1200 34.4 25.5 10.15 - 9.30
HABA-F042S N1AHC1606 5,8,10,15,20 21 G2FD042(S,H)21 1400 39.5 29.2 10.00 - 9.00
N1AHC1606 5,8,10,15,20 21 G2FD048(S,H)21 1450 41.0 30.3 10.10 - 9.15
HABA-F048S N1AHC1606 5,8,10,15,20 21 G2FD048(S,H)21 1600 46.0 34.0 10.10 - 9.50
N1AHD2006 8,10,15,20,25,30 24 G2FD060(S,H)24 1600 47.0 34.8 10.40 - 9.70
HCBA-F060S N1AHD2006 8,10,15,20,25,30 24 G2FD060(S,H)24 1800 56.0 40.2 10.50 - 9.35
3 PH 10 SEER AC WITH N1AH / G2FD
HABA-(T,W)036S N1AHB1246 10,15 21 G2FD036(S,H)17 1200 33.8 25.0 10.00 - 9.20
N1AHB1246 10,15 21 G2FD042(S,H)21 1400 40.0 30.1 10.00 9.05
HABA-(T,W)042S N1AHC1646 10,15 21 G2FD042(S,H)21 1400 39.5 29.2 10.00 - 9.00
N1AHC1646 10,15 24 G2FD048(S,H)21 1450 41.0 30.3 10.10 - 9.15
HABA-(T,W)048S
N1AHC1646 10,15 21 G2FD048(S,H)21 1600 46.0 34.0 10.10 - 9.50
N1AHD2046 10,15,29 24 G2FD048(S,H)24 1600 24.6 34.0 10.10 - 9.50
N1AHD2046 10,15,29 24 G2FD048(S,H)24 1600 46.0 34.0 10.10 - 9.50
HABA-(T,W)060S N1AHD2046 10,15,29 24 G2FD060(S,H)24 1750 58.5 39.8 10.00 - 10.25
1 PH 10 SEER AC / F2RP / RC / FC
4
,
5
HABA-F018S
F2RC/F2FC024 5,8,10 18 - 650 17.4 12.9 10.00 - 9.00
F2RP/F2FP018 2,5,8 18 - 650 17.4 12.3 10.00 - 9.00
F2RP/F2FP024 5,8,10 18 - 650 17.4 12.9 10.00 - 9.00
HABA-F024S F2RP/F2FP024 5,8,10 18 - 800 23.4 17.3 10.00 - 9.00
F2RP/F2FP030 5,8,10,15 18 - 800 23.6 17.5 10.00 - 9.10
HBBA-F030S F2RP/F2FP030 5,8,10,15 18 - 1000 28.4 21.0 10.00 - 9.50
F2RP/F2FP036 5,8,10,15,19 21 - 1000 28.0 20.0 10.00 - 9.00
HBBA-F036S
F2RC/F2FC036 5,8,10,15 21 - 1200 33.6 21.5 10.00 - 9.10
F2RP/F2FP036 5,8,10,15,19 21 - 1200 34.4 25.2 10.20 - 9.30
F2RP/F2FP042 5,8,10,15 21 - 1200 34.4 25.2 10.15 - 9.20
HABA-F042S F2RP/F2FP042 5,8,10,15 21 - 1400 39.5 28.9 10.00 - 9.00
F2FP048 5,8,10,15,20,25 24 - 1400 40.5 30.0 10.00 - 9.20
HABA-F048S F2FP048 5,8,10,15,20,25 24 - 1600 45.5 33.7 10.00 - 9.15
F2FP060 5,8,10,15,20,25 24 - 1600 46.5 34.4 10.00 - 9.70
HCBA-F060S F2FP060 5,8,10,15,20,25 24 - 1800 56.0 41.0 10.00 - 9.15
3 PH 10 seer AC with F2RP / FP
HABA-(T,W)036S F2RC/F2FC036 5,8,10,15 21 - 1200 33.6 25.2 10.00 - 9.10
HABA-(T,W)042S F2RP/F2FP042 5,8,10,15 21 - 1400 39.0 29.2 10.00 - 9.00
F2FP048 5,8,10,15,20,25 24 - 1400 40.5 30.4 10.00 - 9.00
HABA-(T,W)048S F2FP048 5,8,10,15,20,25 24 - 1600 45.5 33.7 10.00 - 9.15
HABA-(T,W)060S F2FP060 5,8,10,15,20,25 24 - 1750 58.5 39.8 10.00 - 9.80
3 PH 10 seer AC WITH KDBC
6
HABA-(T,W)076S KDBC-S090 10,16,26,36 22 -- 2600 73.5 -- -- -- 10.00
HABA-(T,W)090S KDBC-S090 10,16,26,36 22 -- 3280 53.8/
89.0 -- -- -- 9.63/
9.30
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210/240.
Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.
1. G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Single phase units require single phase 2HK heaters. Three phase units require three phase 2HK heaters.
3. TXV = Use 1TV700 Series Kit.
4. To meet R=4.2 insulation requirements, substitute F2FP for F2RP, and F2FC for F2RC
.
models. All ratings remain the same.
5. FG8, FG9, and FL8 furnaces and F2RP / F2RC air handlers have B.O.D (Blower on Delay) standard.
6. H*BA-(T,W)090 is field convertible to two stage operation. Its IPLV = 11.2.
— = Not Applicable.