© Zennio Avance y Tecnología S.L. Edition 2 Further information www.zennio.com Page 1 / 2
MAXinBOX 8 Plus
Multi-function actuator with 8 outputs 16A
ZIO-MB8P Technical Documentation
FEATURES
2 different configurable blocks:
Shutter channels (up to 4).
Individual outputs (up to 8).
2-pipe fan coil control (up to 2 units).
Manual output operation with push button and LED
status indicator.
Suitable for capacitive loads, maximum 140 µF.
Logical functions included.
Output timing facilities.
Total data saving on power failure
Size 67 x 90 x 79 mm (4.5 DIN units).
DIN rail mounting (EN 50022), through pressure.
No external power supply required other than the bus.
KNX BCU integrated.
Possibility to connect different phases in adjoining outputs.
Compliant with the CE directives (CE-mark on the right side).
Programming/test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe
mode. If this button is held for more than 3 seconds, the device enters the test mode.
Programming/Test LED: programming mode indicator (red). When the device enters into safe mode, it blinks (red) every half second. The manual
mode is indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it starts a blue blinking
sequence.
GENERAL SYSTEM SPECIFICATIONS
Type of device Electric operation control device
KNX supply
Voltage (typical) 29V DC SELV
Voltage range 21…31V DC
Maximum
consumption
Voltage mA mW
29VDC (typical) 5.8 168.2
24VDC
10 240
Bus connection Typical bus connector TP1 for rigid cable 0.80mm Ø
External power supply No
Operation temperature from 0ºC to +55ºC
Storage temperature from -20ºC to +70ºC
Operation humidity 5 to 95% RH (no condensation)
Storage humidity 5 to 95% RH (no condensation)
Complementary characteristics Class B
Protection class II
Operation type Continuous operation
Device action type Type 1
Electrical stress period Long
Degree of protection IP20, clean environment
Installation Independent device to be mounted inside electrical panels with DIN rail (EN
50022)
Response on KNX bus failure Data saving and relays open if channel configured as shutter.
Response on KNX bus restart Data recovering and output status change according to programming when
recovering.
Operation indication Programming LED indicates programming mode (red) and test mode (green).
Output status LED indicators reflect current output state.
Weight 290g
PCB CTI index 175 V
Housing material PC FR V0 halogen free
(1) Maximum consumption in the worst case scenario (KNX Fan-In model)
1. Upper outputs
2. Lower output screws
3.Programming/Test LED
4.KNX connector
5.Programming/Test button
6.Output control button
7.Output status LED indicator