© Zennio Avance y Tecnología S.L. Edition 3 Further information www.zennio.com Page 1 / 2
MAXinBOX FANCOIL 4CH2P
4 channel two pipes fan coil controller
ZCL-4XFC2P Technical Documentation
FEATURES
Up to four blocks to control 2-pipe fan coil units.
Manual output operation with push button and LED status
indicator.
Logical functions included.
Output timing facilities.
Total data saving on power failure.
Size 90 x 60 x 140 mm (8 DIN units).
DIN rail mounting (EN 50022), through pressure.
No external power supply required other than the bus.
Integrated KNX BCU.
Possibility to connect different phases in adjoining outputs.
Conformity with the CE directives (CE-mark on the right side).
GENERAL SYSTEM SPECIFICATIONS
Type of device Electric operation control device
KNX
Supply
Voltage (typical) 29VDC SELV
Voltage range 21…31V DC
Maximum
consumption
Voltage mA mW
29VDC (typical) 7.5 217,5
24VDC
10 240
Bus connection Typical bus connector TP1 for rigid cable 0.80mm Ø
External power supply No
Operation temperature from 0ºC to +55ºC
Storage temperature from -20ºC to +70ºC
Operation humidity 5 to 95% RH (no condensation)
Storage humidity 5 to 95% RH (no condensation)
Complementary characteristics Class B
Protection class II
Operation type Continuous operation
Device action type Type 1
Electrical stress period Long
Degree of protection IP20, clean environment
Installation Independent device to be mounted inside electrical panels with DIN rail (EN 50022)
Response on KNX bus failure Data saving and output status change according to programming.
Response on KNX bus restart Data recovering and output status change according to programming.
Operation indication Programming LED indicates programming mode (red) and test mode (green).
Output status LED indicators reflect current output state.
Weight 440g
PCB CTI index 175V
Housing material PC FR V0 halogen free
(1) Maximum consumption in the worst case scenario (KNX Fan-In model)
Programming/test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe
mode. If this button is held for more than 3 seconds, the device enters the test mode.
Programming/Test LED: programming mode indicator (red). When the device enters into safe mode, it blinks (red) every half second. The manual
mode is indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it starts a blue blinking
sequence.
1. Upper outputs
2. Lower outputs
3.Programming/Test LED
4.KNX connector
5.Programming/Test button
6.Output control button
7.Output status LED indicator