2.7 MANUAL CONTROL
The MINiBOX 0-10V devices, include manualcontrol of its outputs through the respective
pushbuttons on the top of the device. Therefore, a specific pushbutton is available per
output.
Manual operationcan bedone in two different ways, named as Test OnMode (for testing
purposes during the configuration of the device) and Test Off Mode (for a normal use,
anytime). Whether both, only one, or none of these modes can be accessed needs to be
parameterised in ETS. Moreover, it is possible to enable a specific binary object for
locking and unlocking the manual control in runtime.
Notes:
The Test Off mode will be active (unless it has been disabled by parameter)
after a download or a reset with no need of a specific activation –the
pushbuttons will respond to user presses from the beginning.
On the contrary, switching to the Test On mode (unless disabled by
parameter) needs to be done by long-pressing the Prog./Test button (for at
least three seconds), until the LED is no longer red and turns yellow. From that
moment, once the button is released, the LED light will remain green to confirm
that the device has switched from the Test Off mode to the Test On mode. After
that, an additional press will turn the LED yellow and then off, once the button
is released. This way, the device leaves the Test On mode. Note that the device
will also leave this mode if a bus powerfailure takes place or if a manual control
lock is sending from KNX bus.
Test Off Mode
Under the Test Off Mode, theoutputs canbe controlled through both their communication
objects and the actual pushbuttons located on the top of the device.
When one of these buttons is pressed, the output will behave as if an order had been
received through the corresponding communication object.
Individual voltage output: only the analog outputs configured as "generic
outputs" can be controlled manually.