When the button is pressed, the device will act over the output according to the
length of the button press and to the current state:
➢Long press: action equivalent to a 0% or 100% control command in the
output control object. The status is sent via the associated status object.
➢Short press: initiates an increasing regulation if the output status is 0%
at that time, or a decreasing regulation if it is 100%. For values between
0 and 100%, the control of regulation is switched with each long press.
The status object will be sent to the bus after stopping the press or
reaching the minimum or maximum value.
In Test Off mode, any press on the buttons of the outputs disabled by parameter will
have no effect.
Test On Mode
After entering the Test On mode, it will only be possible to control the outputs through
the on-board pushbuttons. Orders received through communication objects will be
ignored, with independence of the channel or the output they are addressed to.
Individual output: the action performed on the output by pressing the physical
buttons will be the same as described in the Test Off mode except that the
status objects will not be affected.
Note: unlike in test on mode, in test off mode any type of output can be
controlled, not only the generic ones.
Under theTest On mode, short and long presses will cause thesame effect for disabled
outputs as for analog voltage outputs.
As described previously if the device is in Test On mode, any command sent from the
KNX bus to the actuatorwill not affect the outputs and no status objects will be sent (only
periodically timed objects such as Heartbeat or logic functions will continue to be sent to
the bus) while Test ON mode is active.
Important: the device is factory delivered with all the output channels configured as
disabled outputs, and with both manual modes (Test Off and Test On) enabled.