© Zennio Avance y Tecnología S.L. Edition 3 Further information www.zennio.com Page. 1/ 2
HeatingBOX 230V 8X
Heating actuator with 8 outputs 230VAC
ZCL-8HT230 Technical Documentation
FEATURES
8 configurable outputs for 230V valve control.
8 thermostats.
10 Logic functions.
Total data saving on power failure.
Manual control through buttons and status LED indicators.
Common 230V supply required for the 8 outputs.
Integrated KNX BCU.
Size 67 x 90 x 79 mm (4.5 DIN units).
DIN rail mounting (EN 50022), through pressure.
Conformity with the CE directives (CE-mark on the right side).
GENERAL SYSTEM SPECIFICATIONS
Type of device Electric operation control device
KNX
supply
Voltage (typical) 29VDC SELV
Voltage range 21…31VDC
Maximum
consumption
Voltage mA mW
29VDC (typical) 10.7 310.3
24VDC
15 360
Bus connection Typical bus connector TP1 for rigid cable 0.80mm Ø
External power supply 230V 50/60Hz (only phase, for valve supply)
Operation temperature from 0ºC to +55ºC
Storage temperature from -20ºC to +55ºC
Operation humidity 5 to 95% RH (no condensation)
Storage humidity 5 to 95% RH (no condensation)
Complementary characteristics Class B
Protection class II
Operation type Continuous operation
Device action type Type 1
Electrical stress period Long
Degree of protection IP20, clean environment
Installation Independent device to be mounted inside electrical panels with DIN rail (EN 50022)
Minimal clearances Not required
Response on KNX bus failure Data saving according to parameterization.
Response on KNX bus restart Data recovering change according to parameterization.
Operation indication Programming LED indicates programming mode (red) and test mode (green). Each
output LEDindicates its status (fixed = active output; flashing = overload or short-
circuit error)
Weight 181g
PCB CTI index 175V
Housing material PC FR V0 halogen free
(1) Maximum consumption in the worst case scenario (KNX Fan-In model)
Programming/test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe
mode. If this button is held for more than 3 seconds, the device enters the test mode.
Programming/Test LED: programming mode indicator (red). When the device enters into safe mode, it blinks (red) every half second. The manual
mode is indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it emits a red flash.
1. 230V input (live phase) 2. Valve outputs 3. Output control button 4. Output status indicator LED
5. Programming/Test LED 6. Programming/Test button 7. KNX connector