89
2 VV. Creating innovative solutions for you and your business since 1995.
ver.5 05-05-20
CO exchanger parameters (Heating mode)
Type
Connection
cross-section
[„]
Pressure
drop in the
air ow
[Pa]
Pressure
drop in the
water ow
[kPa]
Power
[W]
Air ow
[m3/h]
Media ow
[m3/h]
Temperature
after exiting the
heat exchanger
[°C]
HR95-080EC-..-...C
3/4 75 2,0 6600 800 0,29 39,2
HR95-150EC-..-...C
3/4 76 0,8 10240 1500 0,45 35
HR95-250EC-..-...C
1 83 1,5 19770 2500 0,86 38,2
HR95-350EC-..-...C
1 1/2 62 1,3 29400 3500 1,28 39,7
For water 60/40 and the inlet temperature = +15 °C
CO exchanger parameters (Cooling mode)
Type
Connection
cross-section
[„]
Pressure
drop in the
air ow
[Pa]
Pressure
drop in the
water ow
[kPa]
Power
[kW]
Air ow
[m3/h]
Media ow
[m3/h]
Temperature
after exiting the
heat exchanger
[°C]
HR95-080EC-..-...C
3/4 84 18,5 5,22 800 0,9 15
HR95-150EC-..-...C
3/4 86 7,5 7,92 1500 1,36 16,7
HR95-250EC-..-...C
1 93 13,2 15,46 2500 2,65 15,4
HR95-350EC-..-...C
1 1/2 69 12,0 23,12 3500 3,97 14,8
For water 7/12 and the inlet temperature = +25 °C
Direct evaporator (Cooling mode)
Type Air ow
[m3/h]
Power
[W]
Temperature
after exiting the
heat exchanger
[°C]
Humidity after
exiting the heat
exchanger
[%]
Coolant pressure
loss
[kPa]
Pressure
drop in the
air ow
[Pa]
Connection
cross-section
gas (liquid)
[„]
HR95-080EC-..-...D
800 5410 15,1 89,9 16,4 66 5/8 (1/2)
HR95-150EC-..-...D
1500 10120 15,2 89,5 33,0 77 7/8 (5/8)
HR95-250EC-..-...D
2500 17190 15 89,6 45,1 72 1 1/8 (5/8)
HR95-350EC-..-...D
3500 25530 14,5 90,3 48,4 53 1 3/8 (1 1/8)
Data applies for the inlet temperature = +25°C, 70% RH and the evaporation temperature +5°C, coolant R410A