10 11
2 VV. Creating innovative solutions for you and your business since 1995.
ver.1 06-04-20
The heat recovery unit must be connected using the TN-S
system which means that the neutral wire must always be
connected.
All electrical circuits into the heat recovery unit must be co-
nnected via a protective power circuitbreaker according to
the current and type. The distance in between the open con-
tacts must be bigger than 3mm.
JHeat recovery unit must be connected in such a manner so
it can be disconnected from the power supply via a single
element. Table of the minimum dimensioning of the circuit
breakers according to the type of heat recovery unit.
Recommended circuit breakers:
Circuit breakers
HRV14EC 10A, 1ph
HRV15EC 10A, 1ph
HRV30EC 10A, 1ph
HRV50EC 16A, 1ph
HRV70EC 16A, 1ph
6.5-2 Electrical ttings
Connect the unit electrical ttings to the terminal inside the
regulator box exactly according to the el. diagram for conne-
ction and according to the markings of the terminals.
DO NOT MISS!
• The connection diagram is glued to the internal side of the
removable lid of the regulator box.
• Each element must be connected using an original cable or
cable as per the specication for each element.
• To open the lid of the regulator box you will need TORX20 key.
See picture.
6.5.ELECTROINSTALLATION
AND ELECTRICAL FITTINGS
ATTENTION
• The main electrical supply must be turned o prior to any
interference with the internal parts of the ventilation unit!
• The electro installation of the ventilation unit must be
implemented according to the technical documentation
issued by a qualied electro engineer. The actual installa-
tion can be carried out by a professional educated in the
electro eld. The manual instructions must be observed
as well as the valid national regulations and directives.
• The electrical charts featured on the product have a
higher priority than the charts included in the manual!
Prior to installation, check if the marking of the termi-
nals conform to the electrical chart for connection. In the
event of any doubts, contact your supplier and under no
circumstances should you connect the ventilation unit.
• The unit must be connected to the power supply using in-
sulated xed and temperature resistant cable according
to the diameter and the relevant national regulations and
directives.
• Any interference and amendments into the internal co-
nnection of the unit are prohibited and can lead to a loss
of the warranty service.
• Correct unit functioning is guaranteed only with original
ttings.
6.5-1 Electrical power cord
The connecting terminal board of the electrical power cord is
positioned in the regulation box.
TECHNICAL INFORMATION
• The electrical parameters are stated on the manufacturer‘s
label.
Product type
Serial number
U = power supply
F = frequency
N = ventilator rpm
Ph = number of phases
Av = air ow
I = total current
P = power input
M = weight
IP = el. protection
Ver = version
6. INSTALLATION
TORX 20