CO exchanger parameters (Heating mode)
Type
Connection
cross-section
[„]
Pressure
drop in the
air ow
[Pa]
Pressure
drop in the
water ow
[kPa]
Power[kW]* Air ow
[m3/h]*
Media ow
[m3/h]*
Temperature
after exiting the
heat exchanger
[°C]*
HR95-080EC-..-...C
3/4 59 2,3 6,17 800 0,27 37,6
HR95-150EC-..-...C
3/4 73 1,6 10,74 1500 0,47 36
HR95-250EC-..-...C
1 91 2,2 17,56 2500 0,77 35,6
HR95-350EC-..-...C
1 1/2 62 2,3 27,02 3500 1,18 37,7
HR95-450EC-..-...C
1 1/2 75 1,4 31,98 4500 1,39 35,9
HR95-550EC-..-...C
1 1/2 57 2,6 43,78 5500 1,91 38,4
* For water 60/40 and the inlet temperature = +15 °C
CO exchanger parameters (Cooling mode)
Type
Connection
cross-section
[„]
Pressure
drop in the
air ow
[Pa]
Pressure
drop in the
water ow
[kPa]
Power
[kW]*
Air ow
[m3/h]*
Media ow
[m3/h]*
Temperature
after exiting the
heat exchanger
[°C]*
HR95-080EC-..-...C
3/4 66 21,1 4,92 800 0,84 15,6
HR95-150EC-..-...C
3/4 83 14,1 8,43 1500 1,45 16,3
HR95-250EC-..-...C
1 102 20,2 13,87 2500 2,38 16,4
HR95-350EC-..-...C
1 1/2 70 21,2 21,61 3500 3,71 15,6
HR95-450EC-..-...C
1 1/2 84 12,5 25,1 4500 4,3 16,3
HR95-550EC-..-...C
1 1/2 64 24,4 35,24 5500 6,04 15,3
* For water 7/12 and the inlet temperature = +25 °C
Direct evaporator (Cooling mode)
Type Air ow
[m3/h]
Power
[kW]
Temperature
after exiting the
heat exchanger
[°C]
Humidity after
exiting the heat
exchanger
[%]
Coolant pressure
loss
[kPa]
Pressure
drop in the
air ow
[Pa]
Connection
cross-section
gas (liquid)
[„]
HR95-080EC-..-...D
800 5,29 15,3 90,1 21,3 62 5/8 (5/8)
HR95-150EC-..-...D
1500 9,69 15,5 89,6 42,0 76 7/8 (1/2)
HR95-250EC-..-...D
2500 15,33 16 89,2 19,9 94 1 1/8 (7/8)
HR95-350EC-..-...D
3500 24,12 15 90 21,4 64 1 3/8 (1 1/8)
HR95-450EC-..-...D
4500 30,08 15,3 89,5 35,0 76 1 5/8 (1 1/8)
HR95-550EC-..-...D
5500 39,41 14,6 90,2 24,2 57 1 5/8 (1 1/8)
Data applies for the inlet temperature = +25°C, 70% RH and the evaporation temperature +5°C, coolant R410A