ABB Relion 620 Series User manual

Relion® 620 series
Advanced Recloser Protection and Control
RER620
IEC 60870-5-101/104 Point List Manual


Document ID: 1MAC302441-MB
Issued: 11/23/2010
Revision: A
Product version: 1.0
© Copyright 2010 ABB. All rights reserved.

Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third party, nor
used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and may
be used, copied, or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or product
names mentioned in this document may be trademarks or registered trademarks of their
respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB Inc.
Distribution Automation
4300 Coral Ridge Drive
Coral Springs, FL 33065, USA
Toll-free: 1 (800) 523-2620
Phone: +1 954-752-6700
Fax: +1 954 345-5329
http://www.abb.com/substationautomation

Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or
product description and are not to be deemed as a statement of guaranteed properties. All
persons responsible for applying the equipment addressed in this manual must satisfy
themselves that each intended application is suitable and acceptable, including that any
applicable safety or other operational requirements are complied with. In particular, any
risks in applications where a system failure and/or product failure would create a risk for
harm to property or persons (including but not limited to personal injuries or death) shall
be the sole responsibility of the person or entity applying the equipment, and those so
responsible are hereby requested to ensure that all measures are taken to exclude or
mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be completely
ruled out. In case any errors are detected, the reader is kindly requested to notify the
manufacturer. Other than under explicit contractual commitments, in no event shall ABB
be responsible or liable for any loss or damage resulting from the use of this manual or the
application of the equipment.

Conformity
This product complies with the directive of the Council of the European Communities on
the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use
within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is
the result of tests conducted by ABB in accordance with the product standards EN 50263
and EN 60255-26 for the directive, and with the product standards EN 60255-6 and EN
60255-27 for the directive. The IED is designed in accordance with the international
standards of the IEC 60255 series and ANSI C37.90. The DNP protocol implementation
in the IED conforms to "DNP3 Intelligent Electronic Device (IED) Certification Procedure
Subset Level 2", available at www.dnp.org.

1MAC302441-MB A Table of contents
RER620 1
Point List Manual
Table of contents
Section 1 Introduction........................................................................... 3
This manual.............................................................................................. 3
Intended audience.................................................................................... 3
Product documentation ............................................................................ 4
Product documentation set ................................................................. 4
Document revision history................................................................... 5
Related documentation ....................................................................... 5
Symbols and conventions ........................................................................ 5
Safety indication symbols.................................................................... 5
Manual conventions ............................................................................ 6
Functions, codes and symbols............................................................ 7
Section 2 IEC 60870-5-101/104 data mappings ................................ 11
Overview ................................................................................................ 11
Point list for RER620 Ver. 1.0 ................................................................ 12
Section 3 IEC 60870-5-101/104 protocol implementation.................. 39
Section 4 Glossary ............................................................................. 51

Table of contents 1MAC302441-MB A
2 RER620
Point List Manual

1MAC302441-MB A Section 1
Introduction
RER620 3
Point List Manual
Section 1 Introduction
1.1 This manual
The point list manual describes the outlook and properties of the data points specific to the
IED. The manual should be used in conjunction with the corresponding communication
protocol manual.
1.2 Intended audience
This manual addresses the communication system engineer or system integrator
responsible for pre-engineering and engineering for communication setup in a substation
from an IED perspective.
The system engineer or system integrator must have a basic knowledge of communication
in protection and control systems and thorough knowledge of the specific communication
protocol.

Section 1 1MAC302441-MB A
Introduction
4 RER620
Point List Manual
1.3 Product documentation
1.3.1 Product documentation set
Figure 1: The intended use of manuals in different lifecycles
The engineering manual contains instructions on how to engineer the IED using the
different tools in PCM600. The manual provides instructions on how to set up a PCM600
project and insert IEDs in the project structure. The manual also recommends a sequence
for engineering of protection and control functions, LHMI functions, and communication
engineering for IEC 61850 and DNP3.
The installation manual contains instructions on how to install the IED. The manual
provides procedures for mechanical and electrical installation. The chapters are organized
in chronological order in which the IED should be installed.
The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for monitoring, controlling and setting
the IED. The manual also describes how to identify disturbances and how to view
calculated and measured power grid data to determine the cause of a fault.
The application manual contains application descriptions and setting guidelines sorted per
function. The manual can be used to find out when and for what purpose a typical
protection function can be used. The manual can also be used when calculating settings.
The technical manual contains application and functionality descriptions and lists function
blocks, logic diagrams, input and output signals, setting parameters and technical data
Planning & purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
Deinstalling & Disposal
Application manual
Operation manual
Installation manual
Engineering manual
Communication Protocol
manual
Technical manual
Protocol Points List
manual

1MAC302441-MB A Section 1
Introduction
RER620 5
Point List Manual
sorted per function. The manual can be used as a technical reference during the
engineering phase, installation and commissioning phase, and during normal service.
The communication protocol manuals describe the communication protocols supported by
the IED. Each manual concentrates on vendor-specific implementations. The point list
manual describes the outlook and properties of the data points specific to the IED. The
manual should be used in conjunction with the corresponding communication protocol
manual.
1.3.2 Document revision history
1.3.3 Related documentation
1.4 Symbols and conventions
1.4.1 Safety indication symbols
Although warning hazards are related to personal injury, it should be understood that
operation of damaged equipment could, under certain operational conditions, result in
degraded process performance leading to personal injury or death. Therefore, comply fully
with all warning and caution notices.
Document revision/date Product version History
A/11/23/2010 1.0 First release
Download the latest documents from the ABB web site
http://www.abb.com/substationautomation.
Name of the document Document ID
IEC 60870-5-101/104 Communication Protocol Manual 1MAC306892-MB
The caution icon indicates important information or warning related to the
concept discussed in the text. It might indicate the presence of a hazard
which could result in corruption of software or damage to equipment or
property.
The information icon alerts the reader to important facts and conditions.
The tip icon indicates advice on, for example, how to design your project
or how to use a certain function.

Section 1 1MAC302441-MB A
Introduction
6 RER620
Point List Manual
1.4.2 Manual conventions
Conventions used in IED manuals. A particular convention may not be used in this
manual.
• Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the push
button icons, for example:
To navigate between the options, use and .
• HMI menu paths are presented in bold, for example:
Select Main Menu > Settings.
• LHMI messages are shown in Courier font, for example:
To save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics, for example:
The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks, for example:
The corresponding parameter values are "Enabled" and "Disabled".
• IED input/output messages and monitored data names are shown in Courier font, for
example:
When the function picks up, the PICKUP output is set to TRUE.
• Dimensions are provided both in inches and mm. If it is not specifically mentioned
then the dimension is in mm.

1MAC302441-MB A Section 1
Introduction
RER620 7
Point List Manual
1.4.3 Functions, codes and symbols
Table 1: RER620 functions, codes and symbols
Function IEC61850 IEC60617 ANSI/C37.2
Current Protection
Single-phase non-directional time overcurrent protection with 1-ph trip option, low stage SPHLPTOC1 3I>(1) 51P
Single-phase non-directional time overcurrent protection with 1-ph trip option, high stage 1 SPHLPTOC2 3I>(2) 50P-1
Single-phase non-directional time overcurrent protection with 1-ph trip option, high stage 2 SPHHPTOC1 3I>>(1) 50P-2
Single-phase non-directional instantaneous overcurrent protection with 1-ph trip option SPHIPTOC1 3I>>>(1) 50P-3
Non-directional time overcurrent ground-fault protection, low stage XEFLPTOC2 Io>(2) 51N
Non-directional time overcurrent ground-fault protection, high stage 1 XEFLPTOC3 Io>(3) 50N-1
Non-directional time overcurrent ground-fault protection, high stage 2 XEFHPTOC3 Io>>(3) 50N-2
Non-directional instantaneous time overcurrent ground-fault protection XEFIPTOC2 Io>>>(2) 50N-3
Non-directional sensitive earth-fault EFLPTOC3 Io>(3) 50SEF
Negative sequence non-directional time overcurrent protection 1 XNSPTOC1 I2 >(1) 46-1
Negative sequence non-directional time overcurrent protection 2 XNSPTOC2 I2 >(2) 46-2
Phase discontinuity protection PDNSPTOC1 I2/I1> 46PD
Three-phase inrush detector INPHAR 3I2f > INR
Directional Protection
Single-phase directional overcurrent protection, low stage 1 SDPHLPDOC1 3I >->(1) 67/51P-1
Single-phase directional overcurrent protection, low stage 2 SDPHLPDOC2 3I >->(2) 67/51P-2
Directional ground-fault protection, low stage 1 XDEFLPDEF1 Io>->(1) 67/51N-1
Directional ground-fault protection, low stage 2 XDEFLPDEF2 Io>->(1) 67/51N-2
Cold Load Timers
Cold load timer 1 Phase A (in seconds) TPSGAPC1 TPS(1) 62CLD-1
Cold load timer 2 Phase A (in minutes) TPMGAPC1 TPM(1) 62CLD-2
Cold load timer 1 Phase B (in seconds) TPSGAPC2 TPS(2) 62CLD-3
Cold load timer 2 Phase B (in minutes) TPMGAPC2 TPM(2) 62CLD-4
Cold load timer 1 Phase C (in seconds) TPSGAPC3 TPS(3) 62CLD-5
Cold load timer 2 Phase C (in minutes) TPMGAPC3 TPM(3) 62CLD-6
Voltage Protection
Three-phase overvoltage 1, source 1 low stage PHPTOV1 3U >(1) 59-1
Three-phase overvoltage 2, source 1 high stage PHPTOV2 3U >(2) 59-2
Three-phase overvoltage 3, source 2 low stage PHPTOV3 3U >(3) 59-3
Three-phase undervoltage 1, source 1 low stage PHPTUV1 3U <(1) 27-1
Three-phase undervoltage 2, source 1 high stage PHPTUV2 3U <(2) 27-2
Three-phase undervoltage 3, source 2 low stage PHPTUV3 3U <(3) 27-3
Positive sequence overvoltage protection, source1 PSPTOV1 U1>(1) 59PS-1
Positive sequence overvoltage protection, source 2 PSPTOV2 U1>(2) 59PS-2
Negative sequence overvoltage protection, source1 NSPTOV1 U2>(1) 47
Negative sequence overvoltage protection, source 2 NSPTOV2 U2>(2) 47-2
Zero sequence overvoltage protection, source1 ROVPTOV1 Uo>(1) 59N-1

Section 1 1MAC302441-MB A
Introduction
8 RER620
Point List Manual
Zero sequence overvoltage protection, source 2 ROVPTOV2 Uo>(2) 59N-2
Frequency Protection
Underfrequency, Overfrequency, Frequency rate of change, source1 FRPFRQ1 f</f>,df/dt(1) 81-1
Underfrequency, Overfrequency, Frequency rate of change, source 2 FRPFRQ2 f</f>,df/dt(2) 81-2
Load Shed & Restoration, source1 LSHDPFRQ1 UFLS/R(1) 81S-1
Load Shed & Restoration, source 2 LSHDPFRQ2 UFLS/R(2) 81S-2
Other Protection
High Impedance Fault Detector PHIZ1 PHIZ1 HIZ
Circuit breaker failure protection SCCBRBRF1 3I>/Io>BF 50BFT
Circuit breaker close failure protection SCCBRBCF1 SCCBRBCF1 50BFC
Directional positive sequence power protection DPSRDIR1 P>-> 32P
Directional negative/zero sequence power protection DNZSRDIR1 Q>-> 32N
Control
Autoreclosing, 1ph and/or 3ph SDARREC1 O -> I 79
Synch-check/voltage check SECRSYN1 SYNC 25
Circuit Breaker 1 (3 state inputs / 3 control outputs) SCBXCBR1 I<->O CB 52
Loop control DLCM DLCM DLCM
Supervision and Monitoring
CB condition monitoring SPSCBR1 CBCM 52CM
Fuse failure supervision SEQRFUF1 FUSEF 60
Measurement
Three-phase current CMMXU1 3I IA,IB,IC
Demand metering, Max/Min metering CSMTA1
Sequence current CSMSQI1 I1,I2,I0 I1, I2, I0
Ground current RESCMMXU1 Io IG
Three-phase voltage, source VMMXU1 3U VA,VB,VC
Three-phase voltage, load VMMXU2 3U(B) VA,VB,VC(2)
Sequence voltages, Source VSMSQI1 U1,U2,U0 V1,V2,V0
Sequence voltages, Load VSMSQI2 U1,U2,U0(B) V1,V2,V0(2)
Three-phase power and energy (incl. cos j) PEMMXU1 P,E P,E
Frequency FMMXU1 f f
Recorders
Digital fault recorder (DFR) RDRE1 DR DFR
Sequence of Events (SER) SER SER SER
Fault Recorder FLTMSTA FLTMSTA FLTMSTA
Fault Locator (FLOC) DRFLO1 FLO FLO
Other Functions
Battery voltage, current. Test the battery ZBAT1 UPS UPS
Universal Power Drive XGGIO115 X115(UPD) X115(UPD)
Programmable buttons (16 buttons) FKEYGGIO1 FKEYGGIO1 FKEYGGIO1
Move function block (8 outputs) MVGAPC1 MVGAPC1 MVGAPC1
Function IEC61850 IEC60617 ANSI/C37.2

1MAC302441-MB A Section 1
Introduction
RER620 9
Point List Manual
Move function block (8 outputs) MVGAPC2 MVGAPC2 MVGAPC2
Pulse timer (8 timers) PTGAPC1 PTGAPC1 PTGAPC1
Pulse timer (8 timers) PTGAPC2 PTGAPC2 PTGAPC2
Generic control points (16 outputs) SPCGGIO1 SPCGGIO1 SPCGGIO1
Generic control points (16 outputs) SPCGGIO2 SPCGGIO2 SPCGGIO2
Set reset flip flops (8 outputs) SRGAPC1 SRGAPC1 SRGAPC1
Set reset flip flops (8 outputs) SRGAPC2 SRGAPC2 SRGAPC2
Time delay off timers (8 timers) TOFGAPC1 TOFGAPC1 TOFGAPC1
Time delay off timers (8 timers) TOFGAPC2 TOFGAPC2 TOFGAPC2
Time delay on timers (8 timers) TONGAPC1 TONGAPC1 TONGAPC1
Time delay on timers (8 timers) TONGAPC2 TONGAPC2 TONGAPC2
Function IEC61850 IEC60617 ANSI/C37.2

Section 1 1MAC302441-MB A
Introduction
10 RER620
Point List Manual

1MAC302441-MB A Section 2
IEC 60870-5-101/104 data mappings
RER620 11
Point List Manual
Section 2 IEC 60870-5-101/104 data mappings
2.1 Overview
This document describes the IEC 60870-5-101/104 data points and structures available in
RER620 Ver. 1.0.
The point tables show all the available IEC 60870-5-101/104 data points in this IED. The
points are grouped into four tables: Analog Values, Binary Controls, Indications, and
Integrated Totals and Regulating Step Positions. Within each group the data objects are
listed in order based on the objects' Information Object Address (IOA). The IEC
60870-5-101/104 points can be freely added, removed, reorganized and reconfigured
using PCM600.
This list represents the superset of IEC 60870-5-101/104 points. The actual set of available
points is determined by the IED”s ordercode. An asterisk (*) in a No Events column
indicates that no events are enabled by default for that point. The word “Disabled” in
Disabled column indicates that the point is not active by default. Inactive points can be
made active through PCM600.

Section 2 1MAC302441-MB A
IEC 60870-5-101/104 data mappings
12 RER620
Point List Manual
2.2 Point list for RER620 Ver. 1.0
Table 2: Analog values
No events 61850 Path IOA Disabled Description Multiplier Interrogation
CMMXU1.A.phsA.cVal.mag.f 8000 "IA,IB,IC:phase A amplitude" Yes
CMMXU1.A.phsA.instCVal.ang.f 8001 "IA,IB,IC:phase A angle" Yes
CMMXU1.A.phsB.cVal.mag.f 8003 "IA,IB,IC:phase B amplitude" Yes
CMMXU1.A.phsB.instCVal.ang.f 8004 "IA,IB,IC:phase B angle" Yes
CMMXU1.A.phsC.cVal.mag.f 8006 "IA,IB,IC:phase C amplitude" Yes
CMMXU1.A.phsC.instCVal.ang.f 8007 "IA,IB,IC:phase C angle" Yes
CSMSQI1.SeqA.c1.cVal.mag.f 8012 "I1,I2,I0:amplitude" Yes
CSMSQI1.SeqA.c1.instCVal.ang.f 8013 "I1,I2,I0:angle" Yes
CSMSQI1.SeqA.c2.cVal.mag.f 8015 "I1,I2,I0:amplitude" Yes
CSMSQI1.SeqA.c2.instCVal.ang.f 8016 "I1,I2,I0:angle" Yes
CSMSQI1.SeqA.c3.cVal.mag.f 8018 "I1,I2,I0:amplitude" Yes
CSMSQI1.SeqA.c3.instCVal.ang.f 8019 "I1,I2,I0:angle" Yes
FLTMSTA1.OpCnt.stVal 8024 FLTMSTA1:OpCnt status Yes
FMMXU1.Hz.mag.f 8025 f:Hz magnitude Yes
FRPTRC1.StrDur.mag.f 8026 Freq1:StrDur magnitude Yes
FRPTRC2.StrDur.mag.f 8027 Freq2:StrDur magnitude Yes
PEMMXU1.TotPF.mag.f 8032 "P,E:TotPF magnitude" Yes
PEMMXU1.TotW.mag.f 8033 "P,E:TotW magnitude" Yes
PEMMXU1.TotVA.mag.f 8034 "P,E:TotVA magnitude" Yes
PEMMXU1.TotVAr.mag.f 8035 "P,E:TotVAr magnitude" Yes
RESCMMXU1.A.res.cVal.mag.f 8036 IG:amplitude Yes
RESCMMXU1.A.res.instCVal.ang.f 8037 IG:angle Yes
SDARREC1.OpCnt1.stVal 8041 79:OpCnt1 status Yes
SDARREC1.OpCnt2.stVal 8042 79:OpCnt2 status Yes
SDARREC1.OpCnt3.stVal 8043 79:OpCnt3 status Yes
SDARREC1.OpCnt4.stVal 8044 79:OpCnt4 status Yes
SDARREC1.OpCnt5.stVal 8045 79:OpCnt5 status Yes
VMMXU1.PhV.phsA.cVal.ang.f 8046 "VA,VB,VC:phase A angle" Yes
VMMXU1.PhV.phsA.cVal.mag.f 8047 "VA,VB,VC:phase A amplitude" Yes
VMMXU1.PhV.phsB.cVal.ang.f 8048 "VA,VB,VC:phase B angle" Yes
VMMXU1.PhV.phsB.cVal.mag.f 8049 "VA,VB,VC:phase B amplitude" Yes
VMMXU1.PhV.phsC.cVal.ang.f 8050 "VA,VB,VC:phase C angle" Yes
VMMXU1.PhV.phsC.cVal.mag.f 8051 "VA,VB,VC:phase C amplitude" Yes
VMMXU1.PPV.phsAB.cVal.mag.f 8052 "VA,VB,VC:phase AB amplitude" Yes
VMMXU1.PPV.phsAB.instCVal.ang.f 8053 "VA,VB,VC:phase AB angle" Yes
VMMXU1.PPV.phsBC.cVal.mag.f 8055 "VA,VB,VC:phase BC amplitude" Yes
VMMXU1.PPV.phsBC.instCVal.ang.f 8056 "VA,VB,VC:phase BC angle" Yes

1MAC302441-MB A Section 2
IEC 60870-5-101/104 data mappings
RER620 13
Point List Manual
VMMXU1.PPV.phsCA.cVal.mag.f 8058 "VA,VB,VC:phase CA amplitude" Yes
VMMXU1.PPV.phsCA.instCVal.ang.f 8059 "VA,VB,VC:phase CA angle" Yes
VMMXU2.PhV.phsA.cVal.ang.f 8061 "VA,VB,VC(2):phase A angle" Yes
VMMXU2.PhV.phsA.cVal.mag.f 8062 "VA,VB,VC(2):phase A amplitude" Yes
VMMXU2.PhV.phsB.cVal.ang.f 8063 "VA,VB,VC(2):phase B angle" Yes
VMMXU2.PhV.phsB.cVal.mag.f 8064 "VA,VB,VC(2):phase B amplitude" Yes
VMMXU2.PhV.phsC.cVal.ang.f 8065 "VA,VB,VC(2):phase C angle" Yes
VMMXU2.PhV.phsC.cVal.mag.f 8066 "VA,VB,VC(2):phase C amplitude" Yes
VMMXU2.PPV.phsAB.cVal.mag.f 8067 "VA,VB,VC(2):phase AB amplitude" Yes
VMMXU2.PPV.phsAB.instCVal.ang.f 8068 "VA,VB,VC(2):phase AB angle" Yes
VMMXU2.PPV.phsBC.cVal.mag.f 8070 "VA,VB,VC(2):phase BC amplitude" Yes
VMMXU2.PPV.phsBC.instCVal.ang.f 8071 "VA,VB,VC(2):phase BC angle" Yes
VMMXU2.PPV.phsCA.cVal.mag.f 8073 "VA,VB,VC(2):phase CA amplitude" Yes
VMMXU2.PPV.phsCA.instCVal.ang.f 8074 "VA,VB,VC(2):phase CA angle" Yes
VSMSQI1.SeqV.c1.cVal.mag.f 8076 "V1,V2,V0:amplitude" Yes
VSMSQI1.SeqV.c1.instCVal.ang.f 8078 "V1,V2,V0:angle" Yes
VSMSQI1.SeqV.c2.cVal.mag.f 8081 "V1,V2,V0:amplitude" Yes
VSMSQI1.SeqV.c2.instCVal.ang.f 8083 "V1,V2,V0:angle" Yes
VSMSQI1.SeqV.c3.cVal.mag.f 8087 "V1,V2,V0:amplitude" Yes
VSMSQI1.SeqV.c3.instCVal.ang.f 8088 "V1,V2,V0:angle" Yes
VSMSQI2.SeqV.c1.cVal.mag.f 8091 "V1,V2,V0(2):amplitude" Yes
VSMSQI2.SeqV.c1.instCVal.ang.f 8093 "V1,V2,V0(2):angle" Yes
VSMSQI2.SeqV.c2.cVal.mag.f 8097 "V1,V2,V0(2):amplitude" Yes
VSMSQI2.SeqV.c2.instCVal.ang.f 8098 "V1,V2,V0(2):angle" Yes
VSMSQI2.SeqV.c3.cVal.mag.f 8102 "V1,V2,V0(2):amplitude" Yes
VSMSQI2.SeqV.c3.instCVal.ang.f 8103 "V1,V2,V0(2):angle" Yes
LLN0.Beh.stVal 10000 LLN0:Beh status Yes
LLN0.LocRem.stVal 10002 LLN0:LocRem status Yes
LPHD1.NumCmpChg.stVal 10003 LPHD1:NumCmpChg status Yes
LPHD1.NumPwrUp.stVal 10004 LPHD1:NumPwrUp status Yes
LPHD1.PhyHealth.stVal 10005 LPHD1:PhyHealth status Yes
LPHD1.PhyHealth1.stVal 10006 LPHD1:PhyHealth1 status Yes
LPHD1.PhyHealth2.stVal 10007 LPHD1:PhyHealth2 status Yes
LPHD1.WacTrg.stVal 10008 LPHD1:WacTrg status Yes
LPHD1.WrmStr.stVal 10009 LPHD1:WrmStr status Yes
DNZSRDIR1.OpChrAng.mag.f 10105 32N:OpChrAng magnitude Yes
DPSRDIR1.OpChrAng.mag.f 10106 32P:OpChrAng magnitude Yes
DRFLO1.FltLoopX.mag.f 10108 FLO:FltLoopX magnitude Yes
DRFLO1.FltZ.mag.f 10109 FLO:FltZ magnitude Yes
NSPTOV2.StrDur.mag.f 10110 47-2:StrDur magnitude Yes
RDRE1.FltNum.stVal 10111 DFR:FltNum status Yes
No events 61850 Path IOA Disabled Description Multiplier Interrogation

Section 2 1MAC302441-MB A
IEC 60870-5-101/104 data mappings
14 RER620
Point List Manual
RDRE1.MemUsed.stVal 10112 DFR:MemUsed status Yes
SDARREC1.AutoRecSt.stVal 10113 79:AutoRecSt status Yes
SDARREC1.ShotPntr.stVal 10114 79:ShotPntr status Yes
SPHPTOV1.StrDur.mag.f 10115 59-1:StrDur magnitude Yes
SPHPTOV2.StrDur.mag.f 10116 59-2:StrDur magnitude Yes
SPHPTOV3.StrDur.mag.f 10117 59-3:StrDur magnitude Yes
SPHPTUV1.StrDur.mag.f 10118 27-1:StrDur magnitude Yes
SPHPTUV2.StrDur.mag.f 10119 27-2:StrDur magnitude Yes
SPHPTUV3.StrDur.mag.f 10120 27-3:StrDur magnitude Yes
SPSCBR1.AccAPwrPhA.mag.f 10121 52CM:AccAPwrPhA magnitude Yes
SPSCBR1.AccAPwrPhB.mag.f 10122 52CM:AccAPwrPhB magnitude Yes
SPSCBR1.AccAPwrPhC.mag.f 10123 52CM:AccAPwrPhC magnitude Yes
SPSCBR1.TmmsClsA.mag.f 10124 52CM:TmmsClsA magnitude Yes
SPSCBR1.TmmsClsB.mag.f 10125 52CM:TmmsClsB magnitude Yes
SPSCBR1.TmmsClsC.mag.f 10126 52CM:TmmsClsC magnitude Yes
SPSCBR1.TmmsOpnA.mag.f 10127 52CM:TmmsOpnA magnitude Yes
SPSCBR1.TmmsOpnB.mag.f 10128 52CM:TmmsOpnB magnitude Yes
SPSCBR1.TmmsOpnC.mag.f 10129 52CM:TmmsOpnC magnitude Yes
SPSCBR1.TmsSprCha.mag.f 10130 52CM:TmsSprCha magnitude Yes
XGGIO115.Swrev.mag.f 10149 XGGIO115:Swrev magnitude Yes
XNSPTOC1.StrDur.mag.f 10150 XNSPTOC1:StrDur magnitude Yes
XNSPTOC2.StrDur.mag.f 10151 XNSPTOC2:StrDur magnitude Yes
ZBAT1.AcInputVol.mag.f 10152 UPS:AcInputVol magnitude Yes
ZBAT1.Amp.mag.f 10153 UPS:Amp magnitude Yes
ZBAT1.AuxLoadI.mag.f 10154 UPS:AuxLoadI magnitude Yes
ZBAT1.BatTstDltV.mag.f 10155 UPS:BatTstDltV magnitude Yes
ZBAT1.BatTstVol.mag.f 10156 UPS:BatTstVol magnitude Yes
ZBAT1.RailVol12V.mag.f 10157 UPS:RailVol12V magnitude Yes
ZBAT1.Temp.mag.f 10158 UPS:Temp magnitude Yes
ZBAT1.UPSBldrVer.mag.f 10159 UPS:UPSBldrVer magnitude Yes
ZBAT1.UPSFwVer.mag.f 10160 UPS:UPSFwVer magnitude Yes
ZBAT1.UPSHwVer.mag.f 10161 UPS:UPSHwVer magnitude Yes
ZBAT1.Vol.mag.f 10162 UPS:Vol magnitude Yes
SECRSYN1.EnSt.stVal 10163 25:EnSt status Yes
FLTMSTA1.StrDur.mag.f 12000 Disabled FLTMSTA1:StrDur magnitude Yes
FLTMSTA1.MaxAmpsA.mag.f 12015 Disabled FLTMSTA1:MaxAmpsA magnitude Yes
FLTMSTA1.MaxAmpsB.mag.f 12016 Disabled FLTMSTA1:MaxAmpsB magnitude Yes
FLTMSTA1.MaxAmpsC.mag.f 12017 Disabled FLTMSTA1:MaxAmpsC magnitude Yes
FLTMSTA1.MaxAmpsN.mag.f 12018 Disabled FLTMSTA1:MaxAmpsN magnitude Yes
FLTMSTA1.AmpsA.mag.f 12019 Disabled FLTMSTA1:AmpsA magnitude Yes
FLTMSTA1.AmpsB.mag.f 12020 Disabled FLTMSTA1:AmpsB magnitude Yes
No events 61850 Path IOA Disabled Description Multiplier Interrogation
Other manuals for Relion 620 Series
14
This manual suits for next models
1
Table of contents
Other ABB Controllers manuals

ABB
ABB HART RSDE10 User manual

ABB
ABB NextMove e100 User manual

ABB
ABB Totalflow mflo Series User guide

ABB
ABB RTC-F-1.PB User manual

ABB
ABB MS132 User manual

ABB
ABB PME120 User manual

ABB
ABB COMMANDER 351 User manual

ABB
ABB ACH400 Series User manual

ABB
ABB PS D75 840 Series Technical specifications

ABB
ABB MS165 User manual
Popular Controllers manuals by other brands

dji
dji T1d user manual

National Instruments
National Instruments CompactRIO cRIO-9035 user manual

EverExceed
EverExceed Titan Series user manual

Samson
Samson 3277 Mounting and operating instructions

VELMEX
VELMEX VXM-3 user manual

McDonnell & Miller
McDonnell & Miller 150E Series Installation & maintenance instructions