ABB REM615 ANSI User manual

Relion® 615 series
Motor Protection and Control
REM615
DNP3 Point List Manual


Document ID: 1MRS756880
Issued: 2012-05-11
Revision: C
Product version: 4.0
© Copyright 2012 ABB. All rights reserved

Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license
and may be used, copied, or disclosed only in accordance with the terms of such
license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
http://www.abb.com/substationautomation

Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.

Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international
standards of the IEC 60255 series.

Table of contents
Section 1 Introduction.......................................................................5
This manual........................................................................................5
Intended audience..............................................................................5
Product documentation.......................................................................5
Product documentation set............................................................5
Document revision history.............................................................6
Related documentation..................................................................6
Symbols and conventions...................................................................7
Symbols.........................................................................................7
Document conventions..................................................................7
Functions, codes and symbols......................................................8
Section 2 DNP3 data mappings.....................................................11
Overview...........................................................................................11
Supported functions..........................................................................11
Point list for REM615 Ver.4.0 ME01-03............................................13
Binary inputs................................................................................13
LD0.ARCSARC1 Fault arc protection stage 1........................13
LD0.ARCSARC2 Fault arc protection stage 2........................13
LD0.ARCSARC3 Fault arc protection stage 3........................14
CTRL.Cxxxxx1 Circuit breaker (1) CB object and failure
protection................................................................................14
CTRL.Dxxxxx1 Controllable disconnector (1)........................14
CTRL.Dxxxxx2 Controllable disconnector (2)........................15
CTRL.Exxxxx1 Controllable earth switch (1)..........................15
CTRL.CCRDIF1 Current circuit failure protection..................15
LD0.CMMXU1 Phase currents (1) limit supervision...............16
LD0.DEFLPDEF1 Directional earth-fault protection - low
stage 1....................................................................................16
LD0.EFHPTOC1 Non-directional earth-fault and
sensitive earth-fault protection - high stage 1.........................16
LD0.EFLPTOC1 Non-directional earth-fault and
sensitive earth-fault protection - low stage 1..........................16
LD0.EMSGAPC1 Emergency start ........................................17
LD0.FRPFRQ1 Frequency protection (1)...............................17
LD0.FRPFRQ2 Frequency protection (2)...............................17
LD0.JAMPTOC1 Stalled motor protection .............................17
LD0.LEDGGIO1 LHMI LED indications..................................18
LD0.LEDPTRC1 Global protection signals.............................18
Table of contents
REM615 1
Point List Manual

CTRL.LLN0 Local/remote state (also present in DNP IIN-
bits).........................................................................................18
LD0.LLN0 Settings supervision..............................................19
LD0.LOFLPTUC1 Loss of load protection..............................19
LD0.MAPGAPC1 Multipurpose analog protection
function (1).............................................................................19
LD0.MAPGAPC2 Multipurpose analog protection
function (2).............................................................................19
LD0.MAPGAPC3 Multipurpose analog protection
function (3).............................................................................19
LD0.MAPGAPC4 Multipurpose analog protection
function (4).............................................................................20
LD0.MAPGAPC5 Multipurpose analog protection
function (5).............................................................................20
LD0.MAPGAPC6 Multipurpose analog protection
function (6).............................................................................20
LD0.MDSOPT1 Generic operation time supervision..............20
LD0.MNSPTOC1 Negative-sequence overcurrent
protection for motors (1).........................................................20
LD0.MNSPTOC2 Negative-sequence overcurrent
protection for motors (2).........................................................21
LD0.MPTTR1 Motor thermal overload protection...................21
LD0.MVGAPC1 Multipurpose binary inputs (1)......................21
LD0.MVGAPC2 Multipurpose binary inputs (2)......................21
LD0.NSPTOV1 Negative-sequence overvoltage
protection - stage 1.................................................................22
LD0.PHIPTOC1 Phase overcurrent protection -
instantaneous stage 1 ...........................................................22
LD0.PHLPTOC1 Phase overcurrent protection - low
stage 1 ...................................................................................22
LD0.PHPTUV1 Phase undervoltage protection - stage
1.............................................................................................22
LD0.PSPTUV1 Positive-sequence undervoltage
protection - stage 1.................................................................23
LD0.PREVPTOC1 Phase reversal protection .......................23
DR.RDRE1 Disturbance recorder..........................................23
LD0.RESCMMXU1 Residual current limit supervision...........23
LD0.RESVMMXU1 Residual voltage limit supervision...........23
LD0.SEQRFUF1 Fuse failure protection................................24
LD0.SPCGGIO2 Multipurpose binary outputs - status
(2)...........................................................................................24
LD0.SSCBR1 Circuit-breaker condition monitoring................24
LD0.STTPMSU1 Motor startup supervision...........................25
LD0.TCSSCBR1 Trip circuit supervision (1)..........................25
LD0.TCSSCBR2 Trip circuit supervision (2)..........................25
Table of contents
2REM615
Point List Manual

LD0.TRPPTRC1 Global conditioning (1)................................25
LD0.TRPPTRC2 Global conditioning (2)................................26
LD0.VMMXU1 Three-phase voltage limit supervision............26
LD0.XRGGIO130 Alarm/warning...........................................26
LD0.XAGGIO130 Physical I/O...............................................26
LD0.XGGIO100 Physical I/O..................................................27
LD0.XGGIO110 Physical I/O..................................................27
LD0.XGGIO120 Physical I/O..................................................27
Binary outputs..............................................................................28
CTRL.CBCSWI1 Circuit breaker control ...............................28
CTRL.DCCSWI1 Controllable disconnector (1) control .........28
CTRL.DCCSWI2 Controllable disconnector (2) control..........28
CTRL.ESCSWI2 Controllable earth switch (1) control ..........28
LD0.DNPGGIO1 Parameter setting group control.................29
LD0.LLN0/LPHD1 Reset indications and LEDs, reset
device.....................................................................................29
LD0.PEMMXU1 Reset accumulated energy values...............29
DR.RDRE1 Disturbance recorder..........................................29
LD0.SPCGGIO1 Multipurpose binary outputs (1)..................30
LD0.SPCGGIO2 Multipurpose binary outputs (2)..................30
LD0.SRGAPC1 Multipurpose binary outputs - flip-flop
resets (1)................................................................................31
LD0.SRGAPC1 Multipurpose binary outputs - flip-flop
resets (1)................................................................................31
LD0.SSCBR1 Reset signals of CB condition monitoring........32
Analog inputs...............................................................................32
CTRL.CBCSWI1 CB 4-pole (2 bit) position value..................32
LD0.CMMXU1 Phase currents (1)..........................................32
LD0.CSMSQI1 Sequence of currents....................................33
CTRL.DCSXSWI1 Disconnector 1, 4-pole (2 bit)
position values........................................................................33
CTRL.DCSXSWI2 Disconnector 2, 4-pole (2 bit)
position values........................................................................33
CTRL.DCSXSWI3 Disconnector 3, 4-pole (2 bit)
position values........................................................................33
CTRL.DCXSWI1 Controllable disconnector 1, 4-pole (2
bit) position values..................................................................33
CTRL.DCXSWI2 Controllable disconnector 2, 4-pole (2
bit) position values..................................................................34
CTRL.ESSXSWI1 Earth switch 1, 4-pole (2 bit) position
values.....................................................................................34
CTRL.ESSXSWI2 Earth switch 2, 4-pole (2 bit) position
values.....................................................................................34
CTRL.ESXSWI1 Controllable earth switch 1, 4-pole (2
bit) position values..................................................................34
Table of contents
REM615 3
Point List Manual

LD0.DNPGGIO1 Active parameter setting group...................34
LD0.FMMXU1 Frequency measurement ...............................35
CTRL.LLN0 Local remote station off......................................35
LD0.LPHD1 System values....................................................35
LD0.MPTTR1 Thermal protection..........................................35
LD0.PEMMTR1 Power measurement and accumulated
power values..........................................................................36
DR.RDRE1 Disturbance recorder values...............................36
LD0.RESCMMXU1 Residual current (1)................................36
LD0.RESVMMXU1 Residual voltage (1)................................36
LD0.VMMXU1 Voltage measurement ...................................37
LD0.VSMSQI1 Sequence of voltage measurement...............37
LD0.XRGGIO130 RTD inputs................................................37
Section 3 DNP3 protocol implementation.......................................39
DNP3 device profile..........................................................................39
DNP3 implementation table..............................................................41
Section 4 Glossary.........................................................................45
Table of contents
4REM615
Point List Manual

Section 1 Introduction
1.1 This manual
The point list manual describes the outlook and properties of the data points
specific to the IED. The manual should be used in conjunction with the
corresponding communication protocol manual.
1.2 Intended audience
This manual addresses the communication system engineer or system integrator
responsible for pre-engineering and engineering for communication setup in a
substation from an IED perspective.
The system engineer or system integrator must have a basic knowledge of
communication in protection and control systems and thorough knowledge of the
specific communication protocol.
1.3 Product documentation
1.3.1 Product documentation set
The application manual contains application descriptions and setting guidelines
sorted per function. The manual can be used to find out when and for what purpose
a typical protection function can be used. The manual can also be used when
calculating settings.
The communication protocol manual describes a communication protocol
supported by the IED. The manual concentrates on vendor-specific implementations.
The engineering guide provides information for IEC 61850 engineering of the 615
series protection IEDs with PCM600 and IET600. This guide concentrates
especially on the configuration of GOOSE communication with these tools. The
guide can be used as a technical reference during the engineering phase,
installation and commissioning phase, and during normal service. For more details
on tool usage, see the PCM600 documentation.
The engineering manual contains instructions on how to engineer the IEDs using
the different tools in PCM600. The manual provides instructions on how to set up a
PCM600 project and insert IEDs to the project structure. The manual also
1MRS756880 C Section 1
Introduction
REM615 5
Point List Manual

recommends a sequence for engineering of protection and control functions, LHMI
functions as well as communication engineering for IEC 61850 and other
supported protocols.
The installation manual contains instructions on how to install the IED. The
manual provides procedures for mechanical and electrical installation. The chapters
are organized in chronological order in which the IED should be installed.
The operation manual contains instructions on how to operate the IED once it has
been commissioned. The manual provides instructions for monitoring, controlling
and setting the IED. The manual also describes how to identify disturbances and
how to view calculated and measured power grid data to determine the cause of a
fault.
The point list manual describes the outlook and properties of the data points
specific to the IED. The manual should be used in conjunction with the
corresponding communication protocol manual.
The technical manual contains application and functionality descriptions and lists
function blocks, logic diagrams, input and output signals, setting parameters and
technical data sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during
normal service.
1.3.2 Document revision history
Document revision/date Product version History
A/2009-07-03 2.0 First release
B/2010-06-11 3.0 Content updated to correspond to the
product version
C/2012-05-11 4.0 Content updated to correspond to the
product version
Download the latest documents from the ABB Web site
http://www.abb.com/substationautomation.
1.3.3 Related documentation
Name of the document Document ID
DNP3 Communication Protocol Manual 1MRS756709
Section 1 1MRS756880 C
Introduction
6REM615
Point List Manual

1.4 Symbols and conventions
1.4.1 Symbols
The caution icon indicates important information or warning related
to the concept discussed in the text. It might indicate the presence
of a hazard which could result in corruption of software or damage
to equipment or property.
The information icon alerts the reader of important facts and
conditions.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to
understand that under certain operational conditions, operation of damaged
equipment may result in degraded process performance leading to personal injury
or death. Therefore, comply fully with all warning and caution notices.
1.4.2 Document conventions
A particular convention may not be used in this manual.
• Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
• Push-button navigation in the LHMI menu structure is presented by using the
push-button icons.
To navigate between the options, use and .
• HMI menu paths are presented in bold.
Select Main menu/Settings.
• LHMI messages are shown in Courier font.
To save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks.
The corresponding parameter values are "On" and "Off".
• IED input/output messages and monitored data names are shown in Courier font.
When the function starts, the START output is set to TRUE.
1MRS756880 C Section 1
Introduction
REM615 7
Point List Manual

1.4.3 Functions, codes and symbols
Table 1: REM615 functions, codes and symbols
Function IEC 61850 IEC 60617 IEC-ANSI
Protection
Three-phase non-directional overcurrent
protection, low stage PHLPTOC1 3I> (1) 51P-1 (1)
Three-phase non-directional overcurrent
protection, instantaneous stage PHIPTOC1 3I>>> (1) 50P/51P (1)
Non-directional earth-fault protection, low stage EFLPTOC1 Io> (1) 51N-1 (1)
Non-directional earth-fault protection, high stage EFHPTOC1 Io>> (1) 51N-2 (1)
Directional earth-fault protection, low stage DEFLPDEF1 Io> -> (1) 67N-1 (1)
Three-phase undervoltage protection PHPTUV1 3U< (1) 27 (1)
Positive-sequence undervoltage protection PSPTUV1 U1< (1) 47U+ (1)
Negative-sequence overvoltage protection NSPTOV1 U2> (1) 47O- (1)
Frequency protection FRPFRQ1 f>/f<,df/dt (1) 81 (1)
FRPFRQ2 f>/f<,df/dt (2) 81 (2)
Negative-sequence overcurrent protection for
motors
MNSPTOC1 I2>M (1) 46M (1)
MNSPTOC2 I2>M (2) 46M (2)
Loss of load supervision LOFLPTUC1 3I< 37
Motor load jam protection JAMPTOC1 Ist> 51LR
Motor start-up supervision STTPMSU1 Is2t n< 49,66,48,51LR
Phase reversal protection PREVPTOC1 I2>> 46R
Thermal overload protection for motors MPTTR1 3Ith>M 49M
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Master trip TRPPTRC1 Master Trip (1) 94/86 (1)
TRPPTRC2 Master Trip (2) 94/86 (2)
Arc protection ARCSARC1 ARC (1) 50L/50NL (1)
ARCSARC2 ARC (2) 50L/50NL (2)
ARCSARC3 ARC (3) 50L/50NL (3)
Multi-purpose protection MAPGAPC1 MAP (1) MAP (1)
MAPGAPC2 MAP (2) MAP (2)
MAPGAPC3 MAP (3) MAP (3)
MAPGAPC4 MAP (4) MAP (4)
MAPGAPC5 MAP (5) MAP (5)
MAPGAPC6 MAP (6) MAP (6)
Control
Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB
Disconnector control DCXSWI1 I <-> O DCC (1) I <-> O DCC (1)
DCXSWI2 I <-> O DCC (2) I <-> O DCC (2)
Earthing switch control ESXSWI1 I <-> O ESC I <-> O ESC
Table continues on next page
Section 1 1MRS756880 C
Introduction
8REM615
Point List Manual

Function IEC 61850 IEC 60617 IEC-ANSI
Disconnector position indication DCSXSWI1 I <-> O DC (1) I <-> O DC (1)
DCSXSWI2 I <-> O DC (2) I <-> O DC (2)
DCSXSWI3 I <-> O DC (3) I <-> O DC (3)
Earthing switch indication ESSXSWI1 I <-> O ES (1) I <-> O ES (1)
ESSXSWI2 I <-> O ES (2) I <-> O ES (2)
Emergergency startup ESMGAPC1 ESTART ESTART
Condition monitoring
Circuit-breaker condition monitoring SSCBR1 CBCM CBCM
Trip circuit supervision TCSSCBR1 TCS (1) TCM (1)
TCSSCBR2 TCS (2) TCM (2)
Current circuit supervision CCRDIF1 MCS 3I MCS 3I
Fuse failure supervision SEQRFUF1 FUSEF 60
Runtime counter for machines and devices MDSOPT1 OPTS OPTM
Measurement
Disturbance recorder RDRE1 - -
Three-phase current measurement CMMXU1 3I 3I
Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0
Residual current measurement RESCMMXU1 Io In
Three-phase voltage measurement VMMXU1 3U 3U
Residual voltage measurement RESVMMXU1 Uo Vn
Sequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0
Three-phase power and energy measurement PEMMXU1 P, E P, E
RTD/mA measurement XRGGIO130 X130 (RTD) X130 (RTD)
Frequency measurement FMMXU1 f f
1MRS756880 C Section 1
Introduction
REM615 9
Point List Manual

10

Section 2 DNP3 data mappings
2.1 Overview
This document describes the DNP3 data points and structures available in REM615
Ver.4.0. The data points are unmapped as a default on the DNP3 level.The point
lists describe a superset of all data available through the standard configuration A,
B, and C including the optional functionalities. The names of the standard
configurations are ME01, ME02 and ME03 respectively.
The point tables show all the available DNP3 data points in the IEDs. The data
objects in the point tables are listed based on the AFL function block and data
object IEC61850 names.
As a default, the class assignments are Class 0 and Class 1 for binary inputs and
Class 0 and Class 2 for analog inputs. These assignments can be modified later.
Analog values are provided with default scalings. The scalings can be freely
modified by the user.
This list represents the superset of DNP3 points. The actual set of available points,
meaning the actual set of available applications, is determined by the IED's ordercode.
2.2 Supported functions
Table 2: Supported functions in REM615
IEC 61850 ME01 ME02 ME03
PHLPTOC1 ● ● ●
PHIPTOC1 ● ● ●
EFLPTOC1 ●
EFHPTOC1 ● ● ●
DEFLPDEF1 ● ●
PHPTUV1 ● ●
PSPTUV1 ● ●
NSPTOV1 ● ●
FRPFRQ1 ● ●
FRPFRQ2 ● ●
MNSPTOC1 ● ● ●
MNSPTOC2 ● ● ●
LOFLPTUC1 ● ● ●
Table continues on next page
1MRS756880 C Section 2
DNP3 data mappings
REM615 11
Point List Manual

IEC 61850 ME01 ME02 ME03
JAMPTOC1 ● ● ●
STTPMSU1 ● ● ●
PREVPTOC1 ● ● ●
MPTTR1 ● ● ●
CCBRBRF1 ● ● ●
TRPPTRC1 ● ● ●
TRPPTRC2 ● ● ●
ARCSARC1 o o o
ARCSARC2 o o o
ARCSARC3 o o o
MAPGAPC1 o o
MAPGAPC2 o o
MAPGAPC3 o o
MAPGAPC4 o o
MAPGAPC5 o o
MAPGAPC6 o o
CBXCBR1 ● ● ●
DCXSWI1 ● ● ●
DCXSWI2 ● ● ●
ESXSWI1 ● ● ●
DCSXSWI1 ● ● ●
DCSXSWI2 ● ● ●
DCSXSWI3 ● ● ●
ESSXSWI1 ● ● ●
ESSXSWI2 ● ● ●
ESMGAPC1 ● ● ●
SSCBR1 ● ● ●
TCSSCBR1 ● ● ●
TCSSCBR2 ● ● ●
CCRDIF1 ● ● ●
SEQRFUF1 ● ●
MDSOPT1 ● ● ●
RDRE1 ● ● ●
CMMXU1 ● ● ●
CSMSQI1 ● ● ●
RESCMMXU1 ● ● ●
VMMXU1 ● ●
RESVMMXU1 ●
VSMSQI1 ● ●
Table continues on next page
Section 2 1MRS756880 C
DNP3 data mappings
12 REM615
Point List Manual

IEC 61850 ME01 ME02 ME03
PEMMXU1 ● ●
XRGGIO130 o o
FMMXU1 ● ●
● = available in the device variant, o = optionally available in the device variant
2.3 Point list for REM615 Ver.4.0 ME01-03
2.3.1 Binary inputs
Table 3: Explanations of the binary input table columns
Column name Description
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name The signal may have a defined label that is visible for example in ACT.
Description Short description of the signal. See the application function block documentation
for more details.
Value Meaning of the input states.
2.3.1.1 LD0.ARCSARC1 Fault arc protection stage 1
Table 4: LD0.ARCSARC1 Fault arc protection stage 1
IEC 61850 name SA name Description Values
LD0.ARCSARC11
.FADet.stVal ARC_FLT_DET Arc detected 1=Detected
LD0.ARCPTRC11
.Op.general OPERATE Operate 1=Operate
2.3.1.2 LD0.ARCSARC2 Fault arc protection stage 2
Table 5: LD0.ARCSARC2 Fault arc protection stage 2
IEC 61850 name SA name Description Values
LD0.ARCSARC21
.FADet.stVal ARC_FLT_DET Arc detected 1=Detected
LD0.ARCPTRC21
.Op.general OPERATE Operate 1=Operate
1MRS756880 C Section 2
DNP3 data mappings
REM615 13
Point List Manual

2.3.1.3 LD0.ARCSARC3 Fault arc protection stage 3
Table 6: LD0.ARCSARC3 Fault arc protection stage 3
IEC 61850 name SA name Description Values
LD0.ARCSARC31
.FADet.stVal ARC_FLT_DET Arc detected 1=Detected
LD0.ARCPTRC31
.Op.general OPERATE Operate 1=Operate
2.3.1.4 CTRL.Cxxxxx1 Circuit breaker (1) CB object and failure protection
Table 7: CTRL.Cxxxxx1 Circuit breaker (1) CB object and failure protection
IEC 61850 name SA name Description Values
CTRL.CBCILO1
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.CBCSWI1
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.CBXCBR1
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
CTRL.CCBRBRF1
.OpEx.general TRBU Failure ext.trip 1=Failure
.OpIn.general TRRET Operate, re-trip 1=Operate
.Str.general CB_FAULT_AL Start, timer running 1=Start
2.3.1.5 CTRL.Dxxxxx1 Controllable disconnector (1)
Table 8: CTRL.Dxxxxx1 Controllable disconnector (1)
IEC 61850 name SA name Description Values
CTRL.DCCILO1
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.DCCSWI1
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.DCXSWI1
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
Section 2 1MRS756880 C
DNP3 data mappings
14 REM615
Point List Manual
Other manuals for REM615 ANSI
2
Table of contents
Other ABB Industrial Equipment manuals