
The directional function is voltage polarized, current
polarized or dual polarized.
EF4PTOC can be set directional or non-directional
independently for each of the steps.
A second harmonic blocking can be set individually for
each step.
EF4PTOC can be used as main protection for phase-to-
earth faults.
EF4PTOC can also be used to provide a system back-up
for example, in the case of the primary protection being
out of service due to communication or voltage
transformer circuit failure.
Directional operation can be combined together with
corresponding communication logic in permissive or
blocking teleprotection scheme. Current reversal and
weak-end infeed functionality are available as well.
Sensitive directional residual overcurrent and power
protection SDEPSDE GUID-EB27F20E-F477-418B-83F0-744BF2988469 v2
In isolated networks or in networks with high impedance
earthing, the earth fault current is significantly smaller
than the short circuit currents. In addition to this, the
magnitude of the fault current is almost independent on
the fault location in the network. The protection can be
selected to use either the residual current or residual
power component 3U0·3I0·cos j, for operating quantity.
There is also available one non-directional 3I0 step and
one non-directional 3U0 overvoltage tripping step.
Time delayed 2-step undercurrent protection
UC2PTUC GUID-4613FD06-ECD0-44ED-8D28-CA22F80495C2 v2
Time delayed 2-step undercurrent protection (UC2PTUC
function is used to supervise the line for low current, for
example, to detect a loss-of-load condition, which
results in a current lower than the normal load current.
Thermal overload protection, one time constant
LPTTR M12020-4 v7
The increasing utilizing of the power system closer to
the thermal limits has generated a need of a thermal
overload protection also for power lines.
A thermal overload will often not be detected by other
protection functions and the introduction of the thermal
overload protection can allow the protected circuit to
operate closer to the thermal limits.
The three-phase current measuring protection has an I2t
characteristic with settable time constant and a thermal
memory.
An alarm level gives early warning to allow operators to
take action well before the line is tripped.
Breaker failure protection CCRBRF M11550-6 v8
Breaker failure protection (CCRBRF) ensures fast back-
up tripping of surrounding breakers in case the own
breaker failure to open. CCRBRF can be current based,
contact based, or an adaptive combination of these two
principles.
A current check with extremely short reset time is used
as check criterion to achieve a high security against
unnecessary operation.
A contact check criteria can be used where the fault
current through the breaker is small.
Breaker failure protection (CCRBRF) current criteria can
be fulfilled by one or two phase currents, or one phase
current plus residual current. When those currents
exceed the user defined settings, the function is
activated. These conditions increase the security of the
back-up trip command.
CCRBRF function can be programmed to give a three-
phase re-trip of the own breaker to avoid unnecessary
tripping of surrounding breakers at an incorrect
initiation due to mistakes during testing.
Breaker failure protection CSPRBRF
GUID-293A8842-8292-45D4-AD04-32CCAD2BF4C9 v1
Breaker failure protection CSPRBRF ensures fast back-
up tripping of surrounding breakers in case of own
breaker failure to open. CSPRBRF can be current based,
contact based, or adaptive combination between these
two principles.
A current check with extremely short reset time is used
as a check criterion to achieve a high security against
unnecessary operation.
A contact check criteria can be used where the fault
current through the breaker is small.
CSPRBRF function current criteria can be fulfilled by one
or two phase currents, or one phase current plus
residual current. When those currents exceed the user
defined settings, the function is activated. These
conditions increase the security of the back-up trip
command.
CSPRBRF can be programmed to give a three-phase re-
trip of the own breaker to avoid unnecessary tripping of
surrounding breakers at an incorrect initiation due to
mistakes during testing.
Stub protection STBPTOC M12902-3 v6
When a power line is taken out of service for
maintenance and the line disconnector is opened the
voltage transformers will mostly be outside on the
disconnected part. The primary line distance protection
will thus not be able to operate and must be blocked.
Line distance protection REL650
1MRK 506 328-BEN B
16 ABB Power Grids
© Copyright 2011 ABB Power Grids. All rights reserved